Page

16 of 22

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil
with a dish washing detergent.

HIGH PRESSURE SWITCH

The W38A1, W49A1 and W61A1 models are supplied
with a remote reset high pressure switch.  If tripped, this
pressure switch may be reset by turning the thermostat
off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the

time the equipment is put into service.  If improper
rotation is corrected at this time, there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation

for several minutes, the compressor’s internal
protector will trip.

All three phase ZR compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

CONDENSER FAN OPERATION

The condenser fan motor on 230/208 volt, one and three
phase, 60 HZ units is a two-speed motor that comes
factory wired on high speed for peak performance.  If
ambient conditions permit, it can be reconnected to low
speed (red wire) for lower sound level.  See wiring
diagram.

50 HZ models must have fan wired on low speed.
These models are factory wired on low speed.

SERVICE HINTS

1. Caution owner/operator to maintain clean air filters

at all times.  Also, not to needlessly close off supply
and return air registers.  This reduces airflow
through the system, which shortens equipment
service life as well as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

Содержание W38A1

Страница 1: ...ON INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W38A1 W49A1 W61A1 Manual 2100 530A Supersedes 2100 530 File Volume III Tab 16 Date 12 15 11 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...ed 19 Table 7 Optional Accessories 20 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 7 General 7 Duct Work 7 Filters 8 Fres...

Страница 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Страница 4: ...o Coating 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front CAPACITY 38 3 Ton 49 4 Ton 61 5 Ton W 38 A 1 A 10 X X X X X X Note...

Страница 5: ...om Installation Bracket Back View E 44 M T R S2 P S2 L O S1 Q N S1 S1 B l a n i m o N s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o...

Страница 6: ...i n i M t i u c r i C y t i c a p m A 1 m u m i x a M e s u F l a n r e t x E r k r B t k C r o 2 d l e i F r e w o P e z i S e r i W 2 d n u o r G e z i S e r i W A t k C B t k C A t k C B t k C A t...

Страница 7: ...90B Where local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design airflow requireme...

Страница 8: ...shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 All c...

Страница 9: ...a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance t...

Страница 10: ...2 Wall Opening and Hole Location View Right Side View 29 OPENING SUPPLIED Supply Opening NOTES SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF Return Opening SILICONE CAULKING BE PLACED BEHIND THE SIDE MO...

Страница 11: ...is is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible ma...

Страница 12: ...Manual 2100 530A Page 12 of 22 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 530A Page 13 of 22 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...minutes the compressor s internal protector will trip All three phase ZR compressors are wired identically internally As a result once the correct phasing is determined for a specific system or insta...

Страница 17: ...s and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch t...

Страница 18: ...4 9 3 1 3 7 4 0 4 1 2 0 5 2 4 1 3 3 5 B D 5 8 B W 2 7 e d i S w o L e d i S h g i H 0 3 1 8 3 3 4 3 1 9 5 3 6 3 1 2 8 3 8 3 1 7 0 4 0 4 1 3 3 4 2 4 1 1 6 4 4 4 1 0 9 4 5 4 1 0 2 5 7 4 1 2 5 5 1 A 9 4...

Страница 19: ...S H E 0 1 A A 3 0 S H E 5 1 A A 4 0 S H E 5 8 0 1 5 1 6 0 B A 3 0 S H E 9 0 B A 4 0 S H E 5 1 B A 4 0 S H E 6 9 5 1 6 0 C A 3 0 S H E 9 0 C A 4 0 S H E 5 1 C A 4 0 S H E 6 9 5 1 1 A 1 6 W 5 0 A A 5 0...

Страница 20: ...r e m m o C t s u a h x E h t i w r e z i m o n o c E V 0 3 2 r o t a l i t n e V y r e v o c e R y g r e n E V 0 6 4 r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X...

Страница 21: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 22: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Отзывы: