WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required.  If this is the
case, the unit serial plate will so indicate.  All models
are suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions 

must be 

adhered

to.  Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material.  All wiring must
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.  To
convert for the locking capability, bend the tab located
in the bottom left-hand corner of the disconnect opening
under the disconnect access panel straight out.  This tab
will now line up with the slot in the door.  When shut, a
padlock may be placed through the hole in the tab
preventing entry.

See “Start Up” section for important information on
three phase scroll compressor start ups.

See Table 2 for Electrical Specifications.

WIRING  –  LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary
voltage transformers.  All equipment leaves the factory
wired on 240V tap.  For 208V operation, reconnect from
240V to 208V tap.  The acceptable operating voltage
range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power

connection point in the unit and while the unit is
operating at full load (maximum amperage
operating condition).

For wiring size and connections, refer to Wiring Manual
2100-507.

Содержание W38A1

Страница 1: ...ON INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W38A1 W49A1 W61A1 Manual 2100 530A Supersedes 2100 530 File Volume III Tab 16 Date 12 15 11 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...ed 19 Table 7 Optional Accessories 20 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 7 General 7 Duct Work 7 Filters 8 Fres...

Страница 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Страница 4: ...o Coating 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front CAPACITY 38 3 Ton 49 4 Ton 61 5 Ton W 38 A 1 A 10 X X X X X X Note...

Страница 5: ...om Installation Bracket Back View E 44 M T R S2 P S2 L O S1 Q N S1 S1 B l a n i m o N s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o...

Страница 6: ...i n i M t i u c r i C y t i c a p m A 1 m u m i x a M e s u F l a n r e t x E r k r B t k C r o 2 d l e i F r e w o P e z i S e r i W 2 d n u o r G e z i S e r i W A t k C B t k C A t k C B t k C A t...

Страница 7: ...90B Where local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design airflow requireme...

Страница 8: ...shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 All c...

Страница 9: ...a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance t...

Страница 10: ...2 Wall Opening and Hole Location View Right Side View 29 OPENING SUPPLIED Supply Opening NOTES SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF Return Opening SILICONE CAULKING BE PLACED BEHIND THE SIDE MO...

Страница 11: ...is is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible ma...

Страница 12: ...Manual 2100 530A Page 12 of 22 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 530A Page 13 of 22 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...minutes the compressor s internal protector will trip All three phase ZR compressors are wired identically internally As a result once the correct phasing is determined for a specific system or insta...

Страница 17: ...s and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch t...

Страница 18: ...4 9 3 1 3 7 4 0 4 1 2 0 5 2 4 1 3 3 5 B D 5 8 B W 2 7 e d i S w o L e d i S h g i H 0 3 1 8 3 3 4 3 1 9 5 3 6 3 1 2 8 3 8 3 1 7 0 4 0 4 1 3 3 4 2 4 1 1 6 4 4 4 1 0 9 4 5 4 1 0 2 5 7 4 1 2 5 5 1 A 9 4...

Страница 19: ...S H E 0 1 A A 3 0 S H E 5 1 A A 4 0 S H E 5 8 0 1 5 1 6 0 B A 3 0 S H E 9 0 B A 4 0 S H E 5 1 B A 4 0 S H E 6 9 5 1 6 0 C A 3 0 S H E 9 0 C A 4 0 S H E 5 1 C A 4 0 S H E 6 9 5 1 1 A 1 6 W 5 0 A A 5 0...

Страница 20: ...r e m m o C t s u a h x E h t i w r e z i m o n o c E V 0 3 2 r o t a l i t n e V y r e v o c e R y g r e n E V 0 6 4 r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X...

Страница 21: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 22: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Отзывы: