TROUBLESHOOTING  GE  ECM

 MOTORS

CAUTION:

Disconnect power from unit before removing or replacing
connectors, or servicing motor.  To avoid electric shock
from the motor’s capacitors, disconnect power and wait at
least 5 minutes before opening motor.

Symptom

Cause/Procedure

Motor rocks slightly

• 

This is normal start-up for ECM

when starting

Motor won’t start

• 

Check blower turns by hand

• No movement

• Check power at motor
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
  (G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
   motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
• 

Perform Moisture Check

• Motor rocks,

• Check for loose or compliant motor mount

  but won’t start

• Make sure blower wheel is tight on shaft
• Perform motor/control replacement check

Motor oscillates up

• It is normal for motor to oscillate with no

load 

& down while being

  on shaft

tested off of blower

Motor starts, but
runs erratically

• Varies up and down

• Check line voltage for variation or “sag”

  or intermittent

• Check low voltage connections
  (G, Y, W, R, C) at motor, unseated pins in
  motor harness connectors
• Check “Bk” for erratic CFM command (in
   variable-speed applications)
• Check out system controls, Thermostat
• 

Perform Moisture Check

• “Hunts” or “puffs” at

• Does removing panel or filter reduce

  high CFM (speed)

  “puffing”?
 - Reduce restriction
 - Reduce max airflow

• Stays at low CFM

• Check low voltage (Thermostat) wires and

  despite system call

  connections

  for cool or heat CFM

• Verify fan is not in delay mode; wait until
   delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check

• Stays at high CFM

• “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
  complete
• Perform motor/control replacement check

• Blower won’t shut off

• Current leakage from controls into G, Y or W?
  Check for Triac switched thermostat or solid-
  state relay

Excessive noise

• Determine if it’s air noise, cabinet, duct or
  motor noise; interview customer, if necessary

• Air noise

• High static creating high blower speed?
 - Is airflow set properly?
 - Does removing filter cause blower to slow
   down?  Check filter
 - Use low-pressure drop filter
 - Check/correct duct restrictions

Symptom

Cause/Procedure

• Noisy blower or cabinet

• 

Check for loose blower housing, panels, etc.

• High static creating high blower speed?

  - Check for air whistling through seams in
     ducts, cabinets or panels
  - Check for cabinet/duct deformation

• “Hunts” or “puffs” at

• 

Does removing panel or filter reduce

   high CFM (speed)

   “puffing”?
  - Reduce restriction
  - Reduce max. airflow

Evidence of Moisture

• Motor failure or

• Replace motor and 

Perform Moisture

Check

  malfunction has occurred

  

and moisture is present

• Evidence of moisture

• 

Perform Moisture Check

  present inside air mover

Do

Don’t

• Check out motor, controls,

• 

Automatically assume the motor is bad.

  wiring and connections
  thoroughly before replacing
  motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
  water can’t get in

   positions

 - Install “drip loops”
• Use authorized motor and

• Replace one motor or control model # with

  model #’s for replacement    another (unless an authorized replacement)
• Keep static pressure to a

• Use high pressure drop filters some have 

½"

  

minimum:

   H20 drop!

 - Recommend high

• Use restricted returns

   efficiency, low static filters
 - Recommend keeping filters
   clean.
 - Design ductwork for min.
   static, max. comfort
 - Look for and recommend
   ductwork improvement,
   where necessary

• Size the equipment wisely

• Oversize system, then compensate with low

    airflow

• Check orientation before

• Plug in power connector backwards

  inserting motor connectors

• Force plugs

Moisture Check

• Connectors are oriented “down” (or as recommended by equipment
  manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airflow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet

Comfort Check

• Check proper airflow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?

Содержание W38A1

Страница 1: ...ON INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W38A1 W49A1 W61A1 Manual 2100 530A Supersedes 2100 530 File Volume III Tab 16 Date 12 15 11 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...ed 19 Table 7 Optional Accessories 20 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 7 General 7 Duct Work 7 Filters 8 Fres...

Страница 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Страница 4: ...o Coating 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front CAPACITY 38 3 Ton 49 4 Ton 61 5 Ton W 38 A 1 A 10 X X X X X X Note...

Страница 5: ...om Installation Bracket Back View E 44 M T R S2 P S2 L O S1 Q N S1 S1 B l a n i m o N s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o...

Страница 6: ...i n i M t i u c r i C y t i c a p m A 1 m u m i x a M e s u F l a n r e t x E r k r B t k C r o 2 d l e i F r e w o P e z i S e r i W 2 d n u o r G e z i S e r i W A t k C B t k C A t k C B t k C A t...

Страница 7: ...90B Where local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design airflow requireme...

Страница 8: ...shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 All c...

Страница 9: ...a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance t...

Страница 10: ...2 Wall Opening and Hole Location View Right Side View 29 OPENING SUPPLIED Supply Opening NOTES SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF Return Opening SILICONE CAULKING BE PLACED BEHIND THE SIDE MO...

Страница 11: ...is is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible ma...

Страница 12: ...Manual 2100 530A Page 12 of 22 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 530A Page 13 of 22 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...minutes the compressor s internal protector will trip All three phase ZR compressors are wired identically internally As a result once the correct phasing is determined for a specific system or insta...

Страница 17: ...s and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch t...

Страница 18: ...4 9 3 1 3 7 4 0 4 1 2 0 5 2 4 1 3 3 5 B D 5 8 B W 2 7 e d i S w o L e d i S h g i H 0 3 1 8 3 3 4 3 1 9 5 3 6 3 1 2 8 3 8 3 1 7 0 4 0 4 1 3 3 4 2 4 1 1 6 4 4 4 1 0 9 4 5 4 1 0 2 5 7 4 1 2 5 5 1 A 9 4...

Страница 19: ...S H E 0 1 A A 3 0 S H E 5 1 A A 4 0 S H E 5 8 0 1 5 1 6 0 B A 3 0 S H E 9 0 B A 4 0 S H E 5 1 B A 4 0 S H E 6 9 5 1 6 0 C A 3 0 S H E 9 0 C A 4 0 S H E 5 1 C A 4 0 S H E 6 9 5 1 1 A 1 6 W 5 0 A A 5 0...

Страница 20: ...r e m m o C t s u a h x E h t i w r e z i m o n o c E V 0 3 2 r o t a l i t n e V y r e v o c e R y g r e n E V 0 6 4 r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X...

Страница 21: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 22: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...