background image

Manual 2100-592C
Page 

51 of 69  

37.  REFRIGERANT CHARGE

The correct system R-410A charge is shown on the unit 
rating plate.

Reference Table 18 to validate proper system operation 
(+2 psig suction, +5 psig discharge).  However, it is 
recommended that if incorrect charge is suspected, the 
system refrigerant be reclaimed, evacuated and charged 
to the nameplate charge quantity and type.

TABLE 18

Refrigerant Charge – Pressure Tables

The nameplate charge quantity is optimized for thermal 
performance and efficiency of this self-contained 
package system.

The system operating pressures in Table 18 are based 
upon rated airflow across the evaporator during cooling 
cycle.

Total system charge for these models can be found in 
Table 1. 

Low  side pressure  ± 2 PSIG
High side pressure  ± 5 PSIG

Tables based upon rated CFM (airflow) across the evaporator coil.
If there is any doubt as to correct operating charge being in the system, the charge should be reclaimed, system evacuated 
and recharged to serial plate instruction.

Model

Return Air 

Temperature

Pressure

60°

65°

70°

75°

80°

85°

90°

95°

100° 105° 110° 115° 120° 125°

W24G2

75° DB

62° WB

Low Side

High Side

105
227

108
250

111
273

115
296

118
319

121
342

124
364

127
387

129
415

131
442

134
469

136
497

138
524

140
552

80° DB

67° WB

Low Side

High Side

120
235

123
258

126
282

129
305

131
329

134
352

137
376

140
399

142
427

145
456

147
484

149
512

152
540

155
569

85° DB

72° WB

Low Side

High Side

133
245

136
268

139
292

141
316

144
340

147
363

150
387

153
411

156
440

158
469

161
498

164
527

166
556

169
585

W30G2

75° DB

62° WB

Low Side

High Side

110
238

113
262

116
287

119
311

122
335

125
359

128
383

131
407

133
435

134
463

136
491

138
519

139
547

141
575

80° DB

67° WB

Low Side

High Side

126
246

129
271

131
296

134
321

137
345

139
370

142
395

145
420

146
449

148
477

150
506

152
535

154
564

156
592

85° DB

72° WB

Low Side

High Side

139
257

142
282

145
307

147
332

150
357

153
382

155
407

158
432

160
461

162
491

164
521

166
550

168
580

170
609

W36G2

75° DB

62° WB

Low Side

High Side

112
256

115
280

117
304

120
328

123
352

125
377

128
401

131
425

132
452

133
480

135
508

136
536

138
563

139
591

80° DB

67° WB

Low Side

High Side

128
265

130
290

132
314

135
339

137
364

139
388

142
413

144
438

146
466

147
495

149
524

150
552

152
581

153
610

85° DB

72° WB

Low Side

High Side

141
276

144
301

146
326

148
351

150
376

153
400

155
425

157
450

159
480

161
509

162
539

164
568

166
597

168
627

W42G2

75° DB

62° WB

Low Side

High Side

107
231

109
254

112
277

115
299

118
322

121
345

123
368

126
391

128
417

130
444

132
470

133
497

135
523

137
550

80° DB

67° WB

Low Side

High Side

122
239

124
262

127
286

129
309

132
333

134
356

137
380

139
403

141
430

143
458

145
485

147
512

149
539

151
567

85° DB

72° WB

Low Side

High Side

134
249

137
272

139
296

142
320

144
343

147
367

149
391

152
415

154
443

156
471

159
499

161
527

163
555

165
583

W48G2

75° DB

62° WB

Low Side

High Side

104
241

107
264

110
287

113
311

116
334

119
358

122
381

125
404

126
433

128
462

130
490

132
519

133
548

135
576

80° DB

67° WB

Low Side

High Side

118
249

121
273

124
297

126
321

129
345

132
369

135
393

137
417

139
446

141
476

143
505

145
535

147
565

149
594

85° DB

72° WB

Low Side

High Side

131
259

133
283

136
308

139
332

142
356

144
381

147
404

150
429

152
459

154
489

156
520

159
550

161
581

163
611

W60G2

75° DB

62° WB

Low Side

High Side

108
241

111
267

114
292

116
318

119
343

122
369

125
394

127
420

129
447

130
475

132
503

133
531

135
559

137
587

80° DB

67° WB

Low Side

High Side

123
249

126
275

128
302

131
328

133
354

136
380

138
406

140
433

142
461

144
490

145
519

147
548

149
576

151
605

85° DB

72° WB

Low Side

High Side

136
260

139
286

141
313

144
339

146
366

149
392

151
418

154
445

155
474

157
504

159
534

161
563

163
593

164
622

Содержание W24G2DA

Страница 1: ...ONS AND THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR THE INSTALLATION LOCATION IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS FAILURE TO DO SO COU...

Страница 2: ...ping 27 19 Manifold Pressure Adjustment 28 20 Checking Gas Input Rate 28 21 Standard Orifice Sizing and High Altitude Derate 30 22 Conversion of Gas Input BTUH from High to Low Rating 33 23 Measuring...

Страница 3: ...and Shutdown Instruction Label 36 Figure 16 Top View of Gas Control 37 Figure 17 Sequence of Operation Electronic Blower Control 40 Figure 18 Furnace Control Board and Blower Control 41 Figure 19 Cir...

Страница 4: ...exdale Boulevard Rexdale Ontario Canada M9W 1R3 Telephone 416 447 4044 BARD MANUFACTURING COMPANY INC BRYAN OHIO 43506 USA These publications can help when installing the furnace They can usually be f...

Страница 5: ...andard N NOx Certified 125 000 BTU input model is not NOx certified HEATING INPUT GAS ELECTRIC 2 3 Ton A 45 000 B 67 500 C 90 000 3 5 Ton B 75 000 C 100 000 D 125 000 Low ambient control is required w...

Страница 6: ...ing the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment All duct work supply and return must be properly sized for the design airflow requirement...

Страница 7: ...230 208 230 208 460 Rated Load Amps 9 9 10 9 6 4 7 1 3 9 11 8 12 9 7 5 8 2 4 7 15 3 16 7 13 3 14 6 5 1 Branch Circuit Selection Current 12 8 8 3 5 1 14 1 9 0 5 6 17 9 15 6 6 0 Lock Rotor Amps 64 58 28...

Страница 8: ...1 14 5 6 4 21 6 24 7 12 8 14 7 7 8 Branch Circuit Selection Current 19 9 13 1 6 1 21 4 14 5 6 4 26 3 15 6 7 8 Lock Rotor Amps 109 83 1 41 135 98 55 134 110 52 Fan Motor and Compressor Fan Motor HP RP...

Страница 9: ...OUTLET AIR EXHAUST COMBUSTION ENTRANCES FRONT CIRCUIT BREAKER MIS 3239 HIGH VOLTAGE ENTRANCES FRONT DOOR FILTER SERVICE DOOR UNIT A B C D E F G H I J K L M N O P Q R W24G W30G W36G 7 88 27 88 13 88 24...

Страница 10: ...of specific recommendations from the local authority having jurisdiction equipment ratings shall be reduced as specified in Section 21 5 TRANSPORTATION DAMAGE All units are packed securely in shipping...

Страница 11: ...mbustible wall use a minimum of Figure 1 A dimension plus 2 and B dimension plus 2 See Figures 4 and 5 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location 4 Mount bot...

Страница 12: ...PTIONAL 12 FLANGE SCREWS UNIT SUPPORT 1 MIN NECCESSARY NO CLEARANCE SUPPLY AIR DUCT RETURN AIR DUCT CONTROL PANEL VESTIBULE DOOR WALL STRUCTURE OUTSIDE 1 CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT...

Страница 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...

Страница 14: ...of one 1 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first three 3 feet of ducting It is important to insure that the one 1 inch m...

Страница 15: ...Manual 2100 592C Page 15 of 69 FIGURE 4 Wall Mounting Instructions FIGURE 5 Wall Mounting Instructions...

Страница 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...

Страница 17: ...d the condenser inlet and discharge openings DO NOT install the unit in a location that will permit discharged air from the condenser to recirculate to the condenser inlet TABLE 2 Minimum Installation...

Страница 18: ...ncludes a stainless steel transition drain tee silicone sealant and drain tubing If unit is installed with vertical vent kit annually inspect the vent system and drain Replace any portion of the vent...

Страница 19: ...nce spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle 6 After it has been determined that each appliance connected to the venting sy...

Страница 20: ...oper electrical ground could result in electric shock or fire 15 WIRING MAIN POWER Refer to unit rating plate for wire sizing information and maximum fuse or circuit breaker size Each outdoor unit is...

Страница 21: ...nal is the dehumidification input This energizes compressor blower and 3 way dehumidification valve W1 terminal is the heating input 230 208 Volt Units All models are equipped with dual primary voltag...

Страница 22: ...r Manual changeover 8403 060 1120 445 3 Stage Cool 3 Stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover Transformer VA FLA Wire Gauge Maximum Distance in...

Страница 23: ...al A W2 E Y2 Y1 2 3 L W1 Y2 Unit 24V W1 E C 2 Thermostat Subbase A Y NEEDED FOR ECONOMIZER ONLY 1120 445 O B Unit Control Panel Factory Installed Jumper G Part 8403 060 R 1 W2 CONFIGURE THERMOSTAT FOR...

Страница 24: ...7 057 8403 058 OR OTHER THERMOSTAT THAT DOES NOT 1 INSTALL IF YOU REQUIRE VENTILATION ANYTIME BLOWER IS ON HAVE OCCUPANCY OUTPUT B O 2 3 SET SWITCH ON THERMOSTAT TO GAS OIL TO 6 2 HEAT 2 COOL CONVENTI...

Страница 25: ...D TAPE OFF 1 1 3 1 G Y 2 Block R C W1 A W2 E Y2 Y1 2 3 WGJIFM 3 5 2 Unit 24V C02 OUT 5 24VAC 6 1 2 3 4 TEMP OUT Optional CO2 Controller Bard Part 8403 067 FIGURE 11D Economizer Low Voltage Connections...

Страница 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...

Страница 27: ...d Immediately after turning on gas the system should be checked for leaks This can be done by watching the 1 2 cubic foot test dial and allowing 4 minutes to show any movement and by soaping each pipe...

Страница 28: ...Adjust manifold pressure by turning gas control regulator adjusting screw clockwise to increase pressure or turning counterclockwise to decrease pressure Manifold pressure must be within allowable ran...

Страница 29: ...on this is the furnace gas input 9 If water heater dryer or range pilots were left on allow for them in calculating correct furnace gas input A quick way is to allow 1 000 BTU per hour for a water he...

Страница 30: ...34 992 38 880 34 182 37 980 33 696 37 440 33 048 36 720 32 643 36 270 32 076 35 640 61 000 68 000 60 750 67 500 58 806 65 340 56 862 63 180 54 918 61 020 53 460 59 400 52 488 58 320 51 273 56 970 50 5...

Страница 31: ...Change and Orifice Change Based on BTU Content 8 001 to 10 000 Requires Pressure Switch Change and Orifice Change Based on BTU Content 20250 BTU Per Burner 700 749 2 60 2 50 2 45 750 799 2 50 2 45 2...

Страница 32: ...ed orifice size 2 30 orifices are shipped with the unit for field installed optional 10 derate Optional 10 Field Converted Derate Gas Heat Value BTU Cu Ft Up to 6 000 Feet No Changes Except for BTU Co...

Страница 33: ...tely 2 from furnace Locate thermometer tip in center of plenum to ensure proper temperature measurement 6 Place second thermometer in return air duct approximately 2 from furnace Locate thermometer ti...

Страница 34: ...he high pressure switch opens the compressor contactor will de energize immediately The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the...

Страница 35: ...DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of delay on break DOB setting 0 5 minute 30 seconds DOB 123 second DOM 1 0 minute 60 seconds DOB 126 second DOM 2 0...

Страница 36: ...llow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appli...

Страница 37: ...ht on small mirror or an extension handle Remove the screws securing the inducer and collector box Now inspect the upper tubes of the heat exchanger Check the exterior of the heat exchanger and the in...

Страница 38: ...sure the supply and return air flange sleeves or duct work are securely fastened to unit and physically sound d Supply and return grilles must be open and free from obstructions e Inspect to make sur...

Страница 39: ...QUENCE OF OPERATION COOLING On a call for cooling from the room thermostat the high speed blower relay will be energized as well as the compressor contactor Following termination of the cooling cycle...

Страница 40: ...purge timing Heat fan off delay timing begins When timing is complete the circulating fan is de energized Thermostat begins call for cool G and Y1 terminals re energized Cooling contactor is energized...

Страница 41: ...heating modes to check for proper blower operation If it is desirable to have both HEAT COOL blower motor speed at the same speed install a jumper wire between HEAT and COOL terminals of the integrate...

Страница 42: ...gh Medium Low High Medium Low 0 0 890 1350 1120 1120 940 0 1 820 1260 1160 1160 870 0 2 950 770 1200 1010 1200 1010 0 3 880 700 1120 1120 940 0 4 790 1030 1030 860 0 5 910 710 950 0 6 800 840 ESP Inch...

Страница 43: ...370 1200 1010 0 3 1080 880 1290 1120 940 1290 1120 940 0 4 1150 990 1190 1030 860 1190 1030 860 0 5 1050 910 1090 950 780 1090 950 780 0 6 940 980 840 660 980 840 660 ESP Inches H2 O COOLING MODE MANU...

Страница 44: ...20 0 1 1220 1000 1260 1060 1260 1060 0 2 1160 950 1370 1200 1010 1200 1010 0 3 1250 1080 1290 1120 940 1120 940 0 4 1150 990 1190 1030 1190 1030 860 0 5 1050 1090 950 1090 950 0 6 940 980 980 840 ESP...

Страница 45: ...510 1090 0 3 1360 1760 1460 1460 0 4 1250 1670 1340 1670 1340 0 5 1460 1150 1560 1240 1560 1240 0 6 1340 1040 1430 1130 1430 1130 ESP Inches H2 O COOLING MODE MANUAL FAN and HEATING MODE Wet Coil 100...

Страница 46: ...880 1510 1510 1110 0 3 1670 1360 1760 1460 1460 1090 0 4 1570 1250 1670 1340 1670 1340 0 5 1460 1560 1240 1560 1240 0 6 1340 1430 1430 1130 ESP Inches H2 O COOLING MODE MANUAL FAN and HEATING MODE Wet...

Страница 47: ...0 1880 1510 1510 1110 0 3 1670 1360 1760 1460 1460 1090 0 4 1570 1670 1340 1670 1340 0 5 1460 1560 1240 1560 1240 0 6 1340 1430 1430 1130 ESP Inches H2 O COOLING MODE MANUAL FAN and HEATING MODE Wet C...

Страница 48: ...uation the inducer will operate for the 30 second postpurge and the comfort air blower will operate for the selected off delay If on Manual Fan operation the comfort air blower will continue to operat...

Страница 49: ...ry default setting If jumper is set to 2 3 occupied dehumidification only outputs will be off 24V Terminal Block Connections G Y 3 W1 Outputs from Board Inputs to Board G Y D W2 G1 TWV YO Cooling Mode...

Страница 50: ...nergizes both the compressor circuit and the three way valve thus directing the hot refrigerant discharge gas into a separate desuperheating condenser circuit which reheats the conditioned air before...

Страница 51: ...95 145 420 146 449 148 477 150 506 152 535 154 564 156 592 85 DB 72 WB Low Side High Side 139 257 142 282 145 307 147 332 150 357 153 382 155 407 158 432 160 461 162 491 164 521 166 550 168 580 170 60...

Страница 52: ...for nitrogen oxide emission levels Refer to Figure 21 for NOx insert information IMPORTANT For propane LP conversions the NOx reduction screen inserts shown below must be removed This is accomplished...

Страница 53: ...167 60 4085 168 61 W30G2DB 4085 265 62 4085 266 63 W30G2DC 4085 388 64 4085 389 65 W36G2DA 4085 167 60 4085 168 61 W36G2DB 4085 265 62 4085 266 63 W36G2DC 4085 388 64 4085 389 65 W42G2DA 4085 167 60...

Страница 54: ...t Black 32 Black Freeze 32 64 71 BLACK SPEED 150 135 120 BLACK BLACK FUSE BLACK WHITE BLACK WHITE BLACK WHITE BLACK BLACK P3 BROWN GRAY BROWN BLACK WHITE BLACK OPT 208 230 60 1 USE COPPER CONDUCTORS S...

Страница 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...

Страница 56: ...PLE WHITE WHITE 65 ORANGE BLACK 32 YELLOW BLACK PINK 65 BROWN 67 CONTROL DEHUM BLACK PINK YELLOW 61 RELAY LOCKOUT BLACK 63 BLACK 64 Thermostat Black 32 Black Freeze 71 BLACK SPEED 150 135 120 BLACK BL...

Страница 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...

Страница 58: ...ED 150 135 120 BLACK WHITE FUSE BLACK CONTROL BLACK BLACK BLACK P3 BROWN GRAY BROWN BLACK WHITE BLACK OPT 460 60 3 BLACK WHITE BLACK WHITE BLACK WHITE BLACK BLACK WHITE BLACK BLACK BLACK BLACK WHITE B...

Страница 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...

Страница 60: ...2 3 4 5 6 8 9 7 12 10 11 BLUE BLUE L2 A L1 A BLUE PURPLE PURPLE MV NO C MV ORANGE YELLOW YELLOW YELLOW YELLOW YELLOW YELLOW RED YELLOW YELLOW Brown Brown BROWN WHITE RED RED RED RED WHITE RED Indoor F...

Страница 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...

Страница 62: ...OL DEHUM BLACK PINK YELLOW 61 RELAY LOCKOUT BLACK 63 BLACK 64 Thermostat Black 32 Black Freeze 52 71 BROWN SPEED 150 135 120 BLACK BLACK FUSE BLACK BLACK BLACK WHITE BLACK BLACK P3 BROWN GRAY BLACK BL...

Страница 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...

Страница 64: ...EHUM SPEED 150 135 120 BLACK WHITE FUSE BLACK CONTROL BLACK BLACK BLACK P3 BROWN GRAY BROWN BLACK WHITE BLACK OPT 460 60 3 BLACK WHITE BLACK WHITE BLACK WHITE BLACK BLACK WHITE BLACK BLACK BLACK BLACK...

Страница 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...

Страница 66: ...k 32 Black Freeze 32 64 71 BLACK SPEED 150 135 120 BLACK BLACK FUSE BLACK WHITE BLACK WHITE BLACK WHITE BLACK BLACK P3 BROWN GRAY BROWN BLACK WHITE BLACK OPT 208 230 60 1 USE COPPER CONDUCTORS SUITABL...

Страница 67: ...LACK PINK YELLOW 61 RELAY LOCKOUT BLACK 63 BLACK 64 Thermostat Black 32 Black Freeze 71 FUSE SPEED 150 135 120 BLACK BLACK BLACK BLACK BLACK BLACK WHITE BLACK BLACK P3 BROWN GRAY BROWN BLACK WHITE BLA...

Страница 68: ...A BLUE PURPLE WHITE PURPLE PURPLE PURPLE PURPLE PURPLE WHITE MV NO C MV ORANGE ORANGE YELLOW YELLOW YELLOW YELLOW YELLOW BLACK YELLOW RED YELLOW YELLOW YELLOW YELLOW YELLOW BLACK YELLOW YELLOW YELLOW...

Страница 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...

Отзывы: