34. W**G DEHUMIDIFICATION RELAY LOGIC BOARD
TABLE 17
Dehumidification Relay Logic Board
Cooling takes precedence over dehumidification. A cooling call cancels dehumidification.
First stage heating cancels dehumidification.
If jumper on RLB is set to “1-2 full-time dehumidification”, outputs will energize. This
is the factory default setting. If jumper is set to “2-3 occupied dehumidification only”,
outputs will be off.
24V Terminal Block Connections
G
Y
3
W1
Outputs from Board
Inputs to Board
G
Y
D
W2
G1
TWV
YO
Cooling Mode
Unoccupied
X
X
X
X
Cooling Mode
Occupied
X
X
X
X
Cooling Mode
with Dehum
X
X
X
X
X
1st Stage Heating
Unoccupied
X
X
1st Stage Heating
Occupied
X
X
1st Stage Heating
with Dehum
X
X
X
2nd Stage Heating
Unoccupied
X
X
2nd Stage Heating
Occupied
X
X
2nd Stage Heating
with Dehum
X
X
X
Dehumidification
Unoccupied
X
Dehumidification
Occupied
X
X
X
X
Содержание W24G2DA
Страница 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Страница 15: ...Manual 2100 592C Page 15 of 69 FIGURE 4 Wall Mounting Instructions FIGURE 5 Wall Mounting Instructions...
Страница 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Страница 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Страница 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Страница 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Страница 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Страница 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Страница 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Страница 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Страница 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...