Manual 2100-592C
Page
45 of 69
TABLE 13
W42G Indoor Blower Performance @ 230 and 460 Volts
Recommended W42G cooling airflow range at rated 1300 CFM @ .35 ESP (WC) is 1500
–
1030 CFM
Factory set on medium dpeed for heating and cooling.
Voltage adjustment
– Reduce airflow by 130 CFM for 208 Volt
Top outlet adjustment
– Increase airflow by 65 CFM for top outlet models
SG-5, RG-5, non-ducted application adjustment
– Reduce airflow by 170 CFM for SG-5 and RG-5 installations
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
125,000 BTU Input
113,000 BTU Input
High
Medium
Low
High
Medium
Low
High
Medium
Low
0.0
- - -
1540
1140
- - -
1640
1230
- - -
1640
1230
0.1
- - -
1480
1090
- - -
1580
1180
- - -
1580
1180
0.2
- - -
1410
1030
1880
1510
- - -
- - -
1510
1090
0.3
- - -
1360
- - -
1760
1460
- - -
- - -
1460
- - -
0.4
- - -
1250
- - -
1670
1340
- - -
1670
1340
- - -
0.5
1460
1150
- - -
1560
1240
- - -
1560
1240
- - -
0.6
1340
1040
- - -
1430
1130
- - -
1430
1130
- - -
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
100,000 BTU
90,000 BTU Input
High
Medium
Low
High
Medium
Low
High
Medium
Low
0.0
- - -
- - -
1190
- - -
1690
1280
- - -
1690
1280
0.1
- - -
1530
1140
- - -
1630
1230
- - -
1630
1230
0.2
- - -
1460
1070
- - -
1560
1160
- - -
1560
1160
0.3
- - -
1410
1050
1810
1510
1140
- - -
1510
1140
0.4
- - -
1300
- - -
1720
1390
- - -
1720
1390
1020
0.5
1510
1200
- - -
1610
1290
- - -
1610
1290
970
0.6
1390
1090
- - -
1480
1180
- - -
1480
1180
- - -
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
75,000 BTU Input
68,000 BTU Input
High
Medium
Low
High
Medium
Low
High
Medium
Low
0.0
- - -
- - -
1240
- - -
1740
1330
- - -
1740
1330
0.1
- - -
- - -
1190
- - -
1680
1280
- - -
1680
1280
0.2
- - -
1510
1120
- - -
1610
1210
- - -
1610
1210
0.3
- - -
1460
1100
1860
1560
1190
- - -
1560
1190
0.4
- - -
1340
- - -
1770
1440
1070
- - -
1440
1070
0.5
- - -
1260
- - -
1660
1340
970
1660
1340
970
0.6
1440
1140
- - -
1530
1230
- - -
1530
1230
- - -
Содержание W24G2DA
Страница 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Страница 15: ...Manual 2100 592C Page 15 of 69 FIGURE 4 Wall Mounting Instructions FIGURE 5 Wall Mounting Instructions...
Страница 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Страница 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Страница 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Страница 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Страница 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Страница 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Страница 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Страница 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Страница 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...