DUCT WORK

All duct work, supply and return, must be properly sized
for the design airflow requirement of the equipment.  Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or portions
thereof not in the conditioned space should be properly
insulated in order to both conserve energy and prevent
condensation or moisture damage.

Refer to Maximum ESP of operation Electric Heat Table 6.

Design the duct work according to methods given by the Air
Conditioning Contractors of America (ACCA).  When duct
runs through unheated spaces, it should be insulated with a
minimum of one inch of insulation.  Use insulation with a
vapor barrier on the outside of the insulation.  Flexible joints
should be used to connect the duct work to the equipment in
order to keep the noise transmission to a minimum.

Models W18 & W24 as approved for zero inch clearance to
the supply duct.  For model series W30, W36, W42, W48,
W60 and W70 a 1/4 inch clearance to combustible material
for the first three feet of duct attached to the outlet air frame
is required.  See Wall Mounting Instructions and Figures 3
and 4 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the wall
cavity.

Some installations may not require any return air duct.  A
metallic return air grille is required with installations not
requiring a return air duct.  The spacing between louvers on
the grille shall not be larger than 5/8 inch.

Any grille that meets with 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used.  Contact distributor or factory
for ordering information.  If using a return air filter grille,
filters must be of sufficient size to allow a maximum
velocity of 400 fpm.

NOTE: If no return air duct is used, applicable installation

codes may limit this cabinet to installation only in a
single story structure.

FILTERS

A 1-inch throwaway filter is standard with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the filter access panel.  A 1-inch washable filter and 2-
inch pleated filter are also available as optional
accessories.  The internal filter brackets are adjustable
to accommodate the 2-inch filter by bending two (2)
tabs down on each side of the filter support bracket.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in
the service door.

If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit.
The damper blade is locked in the closed position.  To
allow the damper to operate, the maximum and
minimum blade position stops must be installed.  See
Figure 1.

All capacity, efficiency and cost of operation
information is based upon the fresh air blank-off plate in
place and is recommended for maximum energy
efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base.  There are
openings in the unit base for the drain hose to pass
through.  In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.

FIGURE  1

FRESH AIR DAMPER

Содержание W18A1

Страница 1: ...IONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1 Manual 2100 508A Supersedes 2100 508 File Volume III Tab 16 Date 02 10 09 Bard Manufacturi...

Страница 2: ...e 22 Table 8 Maximum ESP Electric Heat Only 22 Table 9 Electric Heat 23 Table 10 Optional Accessories 24 Table 11 Vent Control Options 25 Getting Other Information and Publications 3 Wall Mount Genera...

Страница 3: ...ial ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washi...

Страница 4: ...ny way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...insure that they are capable of carrying the weight of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at bot...

Страница 7: ...Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on W70A W70L models 2 Optional top outlet factory installed only for W30A and W36A models only FIGURE 2 l a n i m o N s t n e m e...

Страница 8: ...LEARANCE ON ALL HEATER ACCESS IS ON OPPOSITE LEFT SIDE TOP FLASHING AT TIME OF INSTALLATION Wall Opening and Hole Location View OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULKING ALONG PANEL FOA...

Страница 9: ...NG AT TIME OF INSTALLATION NOTES TOP DUCT FROM COMBUSTABLE RAIN FLASHING THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR FOUR SIDES OF SUPPLY Right Side View WALL IT IS RECOMMENDED THAT A BEAD OF W A U...

Страница 10: ...2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 29 OPENING Supply Opening Dimension is 21 on W70A and W70L Units IT IS RECOMMENDED THAT A BEAD OF SUPPLY AIR NOTES TOP FLASHING AT TIME OF INSTALLATION Return Openin...

Страница 11: ...y air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could r...

Страница 12: ...000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high s...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...eral minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for a specific system or inst...

Страница 17: ...Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the con...

Страница 18: ...e p m e T 1 L 8 1 W 1 A 8 1 W 0 0 6 5 6 1 6 6 6 2 6 1 L 4 2 W 1 A 4 2 W 0 0 8 0 6 6 5 0 6 6 5 1 L 0 3 W 1 A 0 3 W 0 0 0 1 1 6 7 5 1 6 7 5 1 L 6 3 W 1 A 6 3 W 0 0 1 1 0 6 6 5 1 6 7 5 1 L 2 4 W 1 A 2 4...

Страница 19: ...1 3 1 5 4 4 3 3 1 0 7 4 6 3 1 6 9 4 8 3 1 4 2 5 0 4 1 2 5 5 3 4 1 1 8 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 3 1 9 5 3 4 3 1 2 8 3 6 3 1 6 0 4 8 3 1 1 3 4 0 4 1 6 5 4 2 4 1 2 8...

Страница 20: ...1 4 2 3 3 1 5 0 2 5 2 5 3 0 6 2 1 0 1 8 8 2 1 0 1 0 1 0 1 Z 0 C 0 0 C 1 A 0 3 W 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 1 1 2 1 7 1 6 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 0 0 A 1 A 6 3 W...

Страница 21: ...A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 4 2 2 3 8 4 8 5 4 8 5 3 5 3 0 5 0 6 0 9 8 8 8 6 4 0 1 0 1 0 1 0 1 8 8 5 6 2 0 6 0 3 6 0 1 0 1 0 1 Z 0 B 0 0 B 1 L 0 3 W 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 8 1...

Страница 22: ...l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 3 4 5 0 2 0 1 0 6 9 5 6 8 0 2 8 5 3 7 5 1 6 5 7 9 5 0 9 0 0 8 5 3 7 0 5 6 5 3 5 5 9 3 1 0 4 3 1 5 8 2 1 5 0 2 1 0 1...

Страница 23: ...1 0 5 6 3 1 4 4 1 0 4 2 0 1 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6...

Страница 24: ...0 B A 6 3 W H E X 9 0 B 3 0 A W H E X X 5 1 B 7 3 A W H E X X 6 0 C A 3 0 C W H E X X 9 0 C A 3 0 C W H E X X 5 1 C A 3 0 A W H E X X 5 0 A 5 0 A W H E X X 0 1 A 5 0 A W H E X X X X 5 1 A 5 0 A W H E...

Страница 25: ...f f O k n a l B X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X 3 S V R C n r u t e R g n i r p S r o t a l i t n e V l a i c r e m m o C X 3 P V R C n r u t e R r e w o P r o t a l i t n...

Отзывы: