manualshive.com logo in svg
background image

Manual 2100-508A
Page

17 of 25

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling

in compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.  On a call for
heating, circuit R-W1 make at the thermostat pulling in
heat contact for the strip heat and blower operation.  On
a call for second stage heat, R-W2 makes bringing on
second heat contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all
models covered by this manual.  The compressor control
module is an anti-short cycle/lockout timer with high
and low pressure switch monitoring and alarm relay
output.

Adjustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to
the unit, the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch and low pressure switch is closed, the compressor
contactor is energized.  Upon shutdown, the delay on
break timer starts and prevents restart until the delay on
break and delay on make periods have expired.

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle, the unit will go
into 

manual lockout

 condition and the alarm relay circuit

will energize.  Recycling the wall thermostat resets the
manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds, the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever the compressor is locked out due to
HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner unit model.  The lockout features,
both soft and manual, are a function of the
Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.
See Table 3.

Содержание W18A1

Страница 1: ...IONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1 Manual 2100 508A Supersedes 2100 508 File Volume III Tab 16 Date 02 10 09 Bard Manufacturi...

Страница 2: ...e 22 Table 8 Maximum ESP Electric Heat Only 22 Table 9 Electric Heat 23 Table 10 Optional Accessories 24 Table 11 Vent Control Options 25 Getting Other Information and Publications 3 Wall Mount Genera...

Страница 3: ...ial ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washi...

Страница 4: ...ny way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...insure that they are capable of carrying the weight of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at bot...

Страница 7: ...Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on W70A W70L models 2 Optional top outlet factory installed only for W30A and W36A models only FIGURE 2 l a n i m o N s t n e m e...

Страница 8: ...LEARANCE ON ALL HEATER ACCESS IS ON OPPOSITE LEFT SIDE TOP FLASHING AT TIME OF INSTALLATION Wall Opening and Hole Location View OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULKING ALONG PANEL FOA...

Страница 9: ...NG AT TIME OF INSTALLATION NOTES TOP DUCT FROM COMBUSTABLE RAIN FLASHING THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR FOUR SIDES OF SUPPLY Right Side View WALL IT IS RECOMMENDED THAT A BEAD OF W A U...

Страница 10: ...2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 29 OPENING Supply Opening Dimension is 21 on W70A and W70L Units IT IS RECOMMENDED THAT A BEAD OF SUPPLY AIR NOTES TOP FLASHING AT TIME OF INSTALLATION Return Openin...

Страница 11: ...y air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could r...

Страница 12: ...000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high s...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...eral minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for a specific system or inst...

Страница 17: ...Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the con...

Страница 18: ...e p m e T 1 L 8 1 W 1 A 8 1 W 0 0 6 5 6 1 6 6 6 2 6 1 L 4 2 W 1 A 4 2 W 0 0 8 0 6 6 5 0 6 6 5 1 L 0 3 W 1 A 0 3 W 0 0 0 1 1 6 7 5 1 6 7 5 1 L 6 3 W 1 A 6 3 W 0 0 1 1 0 6 6 5 1 6 7 5 1 L 2 4 W 1 A 2 4...

Страница 19: ...1 3 1 5 4 4 3 3 1 0 7 4 6 3 1 6 9 4 8 3 1 4 2 5 0 4 1 2 5 5 3 4 1 1 8 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 3 1 9 5 3 4 3 1 2 8 3 6 3 1 6 0 4 8 3 1 1 3 4 0 4 1 6 5 4 2 4 1 2 8...

Страница 20: ...1 4 2 3 3 1 5 0 2 5 2 5 3 0 6 2 1 0 1 8 8 2 1 0 1 0 1 0 1 Z 0 C 0 0 C 1 A 0 3 W 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 1 1 2 1 7 1 6 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 0 0 A 1 A 6 3 W...

Страница 21: ...A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 4 2 2 3 8 4 8 5 4 8 5 3 5 3 0 5 0 6 0 9 8 8 8 6 4 0 1 0 1 0 1 0 1 8 8 5 6 2 0 6 0 3 6 0 1 0 1 0 1 Z 0 B 0 0 B 1 L 0 3 W 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 8 1...

Страница 22: ...l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 3 4 5 0 2 0 1 0 6 9 5 6 8 0 2 8 5 3 7 5 1 6 5 7 9 5 0 9 0 0 8 5 3 7 0 5 6 5 3 5 5 9 3 1 0 4 3 1 5 8 2 1 5 0 2 1 0 1...

Страница 23: ...1 0 5 6 3 1 4 4 1 0 4 2 0 1 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6...

Страница 24: ...0 B A 6 3 W H E X 9 0 B 3 0 A W H E X X 5 1 B 7 3 A W H E X X 6 0 C A 3 0 C W H E X X 9 0 C A 3 0 C W H E X X 5 1 C A 3 0 A W H E X X 5 0 A 5 0 A W H E X X 0 1 A 5 0 A W H E X X X X 5 1 A 5 0 A W H E...

Страница 25: ...f f O k n a l B X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X 3 S V R C n r u t e R g n i r p S r o t a l i t n e V l a i c r e m m o C X 3 P V R C n r u t e R r e w o P r o t a l i t n...

Отзывы: