manualshive.com logo in svg
background image

Manual 2100-508A
Page

18 of 25

TROUBLESHOOTING

FIGURE  8

FAN BLADE SETTING

MIS-1724

TABLE  1

FAN BLADE DIMENSION

REMOVAL OF FAN SHROUD

1. Disconnect all power to the unit.

2. Remove the screws holding both grilles, one on each

side of unit, and remove grilles.

3. Remove screws holding fan shroud to condenser and

bottom.  Nine (9) screws.

4. Unwire condenser fan motor.

5. Slide complete motor, fan blade, and shroud

assembly out the left side of the unit.

6. Service motor/fan as needed.

7. Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-410A charge is shown on the unit
rating plate.  Optimum unit performance will occur with
a refrigerant charge resulting in a suction line
temperature (6" from compressor) as shown in Table
2A.  If charge quantity is in doubt, reclaim unit and
recharge to factory nameplate quantity.

The suction line temperatures in Table 2 above are
based upon 80°F dry bulb / 67°F wet bulb (50% R.H.)
temperature and rated airflow across the evaporator
during cooling cycle.

TABLE  2A

REFRIGERANT CHARGE

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

D

O

F

°

5

9

e

r

u

t

a

r

e

p

m

e

T

D

O

F

°

2

8

e

r

u

t

a

r

e

p

m

e

T

1

L

8

1

W

/

1

A

8

1

W

0

0

6

5

6

-

1

6

6

6

-

2

6

1

L

4

2

W

/

1

A

4

2

W

0

0

8

0

6

-

6

5

0

6

-

6

5

1

L

0

3

W

/

1

A

0

3

W

0

0

0

1

1

6

-

7

5

1

6

-

7

5

1

L

6

3

W

/

1

A

6

3

W

0

0

1

1

0

6

-

6

5

1

6

-

7

5

1

L

2

4

W

/

1

A

2

4

W

0

0

4

1

2

6

-

8

5

4

6

-

0

6

1

L

8

4

W

/

1

A

8

4

W

0

5

5

1

7

6

-

3

6

9

6

-

5

6

1

L

0

6

W

/

1

A

0

6

W

0

5

6

1

7

6

-

3

6

8

6

-

4

6

The correct system R-410A charge is shown on the unit
nameplate.  Optimum unit performance will occur with
a refrigerant charge resulting in a liquid subcooling as
shown in Table 2B.  If charge is in doubt, reclaim and
recharge to factory nameplate charge.

TABLE  2B

REFRIGERANT CHARGE

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

F

°

5

9

g

n

i

l

o

o

c

b

u

S

F

°

2

8

g

n

i

l

o

o

c

b

u

S

1

L

0

7

W

/

1

A

0

7

W

0

0

8

1

°

8

1

-

5

1

°

9

1

-

6

1

l

e

d

o

M

n

o

i

s

n

e

m

i

D

A

1

L

8

1

W

/

1

A

8

1

W

1

L

4

2

W

/

1

A

4

2

W

"

0

0

.

1

1

L

0

3

W

/

1

A

0

3

W

1

L

6

3

W

/

1

A

6

3

W

"

5

2

.

1

1

L

2

4

W

/

1

A

2

4

W

1

L

8

4

W

/

1

A

8

4

W

1

L

0

6

W

/

1

A

0

6

W

"

5

7

.

1

1

L

0

7

W

/

1

A

0

7

W

"

5

7

.

FAN BLADE SETTING DIMENSIONS

Shown in Figure 8 is the correct fan blade setting for
proper air delivery across the outdoor coil.  Refer to
Table 1 for unit specific dimension.

Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.

Содержание W18A1

Страница 1: ...IONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1 Manual 2100 508A Supersedes 2100 508 File Volume III Tab 16 Date 02 10 09 Bard Manufacturi...

Страница 2: ...e 22 Table 8 Maximum ESP Electric Heat Only 22 Table 9 Electric Heat 23 Table 10 Optional Accessories 24 Table 11 Vent Control Options 25 Getting Other Information and Publications 3 Wall Mount Genera...

Страница 3: ...ial ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washi...

Страница 4: ...ny way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...insure that they are capable of carrying the weight of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at bot...

Страница 7: ...Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on W70A W70L models 2 Optional top outlet factory installed only for W30A and W36A models only FIGURE 2 l a n i m o N s t n e m e...

Страница 8: ...LEARANCE ON ALL HEATER ACCESS IS ON OPPOSITE LEFT SIDE TOP FLASHING AT TIME OF INSTALLATION Wall Opening and Hole Location View OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULKING ALONG PANEL FOA...

Страница 9: ...NG AT TIME OF INSTALLATION NOTES TOP DUCT FROM COMBUSTABLE RAIN FLASHING THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR FOUR SIDES OF SUPPLY Right Side View WALL IT IS RECOMMENDED THAT A BEAD OF W A U...

Страница 10: ...2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 29 OPENING Supply Opening Dimension is 21 on W70A and W70L Units IT IS RECOMMENDED THAT A BEAD OF SUPPLY AIR NOTES TOP FLASHING AT TIME OF INSTALLATION Return Openin...

Страница 11: ...y air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could r...

Страница 12: ...000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high s...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...eral minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for a specific system or inst...

Страница 17: ...Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the con...

Страница 18: ...e p m e T 1 L 8 1 W 1 A 8 1 W 0 0 6 5 6 1 6 6 6 2 6 1 L 4 2 W 1 A 4 2 W 0 0 8 0 6 6 5 0 6 6 5 1 L 0 3 W 1 A 0 3 W 0 0 0 1 1 6 7 5 1 6 7 5 1 L 6 3 W 1 A 6 3 W 0 0 1 1 0 6 6 5 1 6 7 5 1 L 2 4 W 1 A 2 4...

Страница 19: ...1 3 1 5 4 4 3 3 1 0 7 4 6 3 1 6 9 4 8 3 1 4 2 5 0 4 1 2 5 5 3 4 1 1 8 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 3 1 9 5 3 4 3 1 2 8 3 6 3 1 6 0 4 8 3 1 1 3 4 0 4 1 6 5 4 2 4 1 2 8...

Страница 20: ...1 4 2 3 3 1 5 0 2 5 2 5 3 0 6 2 1 0 1 8 8 2 1 0 1 0 1 0 1 Z 0 C 0 0 C 1 A 0 3 W 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 1 1 2 1 7 1 6 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 0 0 A 1 A 6 3 W...

Страница 21: ...A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 4 2 2 3 8 4 8 5 4 8 5 3 5 3 0 5 0 6 0 9 8 8 8 6 4 0 1 0 1 0 1 0 1 8 8 5 6 2 0 6 0 3 6 0 1 0 1 0 1 Z 0 B 0 0 B 1 L 0 3 W 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 8 1...

Страница 22: ...l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 3 4 5 0 2 0 1 0 6 9 5 6 8 0 2 8 5 3 7 5 1 6 5 7 9 5 0 9 0 0 8 5 3 7 0 5 6 5 3 5 5 9 3 1 0 4 3 1 5 8 2 1 5 0 2 1 0 1...

Страница 23: ...1 0 5 6 3 1 4 4 1 0 4 2 0 1 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6...

Страница 24: ...0 B A 6 3 W H E X 9 0 B 3 0 A W H E X X 5 1 B 7 3 A W H E X X 6 0 C A 3 0 C W H E X X 9 0 C A 3 0 C W H E X X 5 1 C A 3 0 A W H E X X 5 0 A 5 0 A W H E X X 0 1 A 5 0 A W H E X X X X 5 1 A 5 0 A W H E...

Страница 25: ...f f O k n a l B X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X 3 S V R C n r u t e R g n i r p S r o t a l i t n e V l a i c r e m m o C X 3 P V R C n r u t e R r e w o P r o t a l i t n...

Отзывы: