Manual 2100-508A
Page

15 of 25

START UP

THESE UNITS REQUIRE R-410A
REFRIGERANT AND POLYOL
ESTER OIL.

GENERAL:

1. Use separate service equipment to avoid cross

contamination of oil and refrigerants.

2. Use recovery equipment rated for R-410A

refrigerant.

3. Use manifold gauges rated for R-410A (800 psi/250

psi low).

4. R-410A is a binary blend of HFC-32 and HFC-125.

5. R-410A is nearly azeotropic - similar to R-22 and

R-12.  Although nearly azeotropic, charge with
liquid refrigerant.

6. R-410A operates at 40-70% higher pressure than

R-22, and systems designed for R-22 cannot
withstand this higher pressure.

7. R-410A has an ozone depletion potential of zero,

but must be reclaimed due to its global warming
potential.

8. R-410A compressors use polyolester oil.

9. Polyol Ester oil is hygroscopic; it will rapidly absorb

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug

compressor immediately after removal.  Purge with
small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard Manufacturing
recommends reclaiming, evacuating (see criteria above),
and charging to the nameplate charge.  If done correctly,
topping off the system charge can be done without
problems.

With R-410A, there are no significant changes in the
refrigerant composition during multiple leaks and
recharges.  R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound or
single component refrigerant).  The remaining
refrigerant charge, in the system, may be used after
leaks have occurred and then “top-off” the charge by
utilizing the charging charts on the inner control panel
cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, it

must come out of the charging cylinder/tank as a liquid
to avoid any fractionation, and to insure optimal system
performance.  Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1. Never mix R-410A with other refrigerants.

2. Use gloves and safety glasses, Polyol Ester oils can

be irritating to the skin, and liquid refrigerant will
freeze the skin.

3. Never use air and R-410A to leak check; the

mixture may become flammable.

4. Do not inhale R-410A – the vapor attacks the

nervous system, creating dizziness, loss of
coordination and slurred speech.  Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.

5. Do not burn R-410A.  This decomposition

produces hazardous vapors.  Evacuate the area if
exposed.

6. Use only cylinders rated DOT4BA/4BW 400.

7. Never fill cylinders over 80% of total capacity.

8. Store cylinders in a cool area, out of direct

sunlight.

9. Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge

lines or cylinders.  R-410A expands significantly
at warmer temperatures.  Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.

        WARNING

Failure to conform to these practices
could lead to damage, injury or death.

Содержание W18A1

Страница 1: ...IONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1 Manual 2100 508A Supersedes 2100 508 File Volume III Tab 16 Date 02 10 09 Bard Manufacturi...

Страница 2: ...e 22 Table 8 Maximum ESP Electric Heat Only 22 Table 9 Electric Heat 23 Table 10 Optional Accessories 24 Table 11 Vent Control Options 25 Getting Other Information and Publications 3 Wall Mount Genera...

Страница 3: ...ial ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washi...

Страница 4: ...ny way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...insure that they are capable of carrying the weight of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at bot...

Страница 7: ...Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on W70A W70L models 2 Optional top outlet factory installed only for W30A and W36A models only FIGURE 2 l a n i m o N s t n e m e...

Страница 8: ...LEARANCE ON ALL HEATER ACCESS IS ON OPPOSITE LEFT SIDE TOP FLASHING AT TIME OF INSTALLATION Wall Opening and Hole Location View OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULKING ALONG PANEL FOA...

Страница 9: ...NG AT TIME OF INSTALLATION NOTES TOP DUCT FROM COMBUSTABLE RAIN FLASHING THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR FOUR SIDES OF SUPPLY Right Side View WALL IT IS RECOMMENDED THAT A BEAD OF W A U...

Страница 10: ...2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 29 OPENING Supply Opening Dimension is 21 on W70A and W70L Units IT IS RECOMMENDED THAT A BEAD OF SUPPLY AIR NOTES TOP FLASHING AT TIME OF INSTALLATION Return Openin...

Страница 11: ...y air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could r...

Страница 12: ...000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high s...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...eral minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for a specific system or inst...

Страница 17: ...Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the con...

Страница 18: ...e p m e T 1 L 8 1 W 1 A 8 1 W 0 0 6 5 6 1 6 6 6 2 6 1 L 4 2 W 1 A 4 2 W 0 0 8 0 6 6 5 0 6 6 5 1 L 0 3 W 1 A 0 3 W 0 0 0 1 1 6 7 5 1 6 7 5 1 L 6 3 W 1 A 6 3 W 0 0 1 1 0 6 6 5 1 6 7 5 1 L 2 4 W 1 A 2 4...

Страница 19: ...1 3 1 5 4 4 3 3 1 0 7 4 6 3 1 6 9 4 8 3 1 4 2 5 0 4 1 2 5 5 3 4 1 1 8 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 3 1 9 5 3 4 3 1 2 8 3 6 3 1 6 0 4 8 3 1 1 3 4 0 4 1 6 5 4 2 4 1 2 8...

Страница 20: ...1 4 2 3 3 1 5 0 2 5 2 5 3 0 6 2 1 0 1 8 8 2 1 0 1 0 1 0 1 Z 0 C 0 0 C 1 A 0 3 W 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 1 1 2 1 7 1 6 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 0 0 A 1 A 6 3 W...

Страница 21: ...A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 4 2 2 3 8 4 8 5 4 8 5 3 5 3 0 5 0 6 0 9 8 8 8 6 4 0 1 0 1 0 1 0 1 8 8 5 6 2 0 6 0 3 6 0 1 0 1 0 1 Z 0 B 0 0 B 1 L 0 3 W 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 8 1...

Страница 22: ...l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 3 4 5 0 2 0 1 0 6 9 5 6 8 0 2 8 5 3 7 5 1 6 5 7 9 5 0 9 0 0 8 5 3 7 0 5 6 5 3 5 5 9 3 1 0 4 3 1 5 8 2 1 5 0 2 1 0 1...

Страница 23: ...1 0 5 6 3 1 4 4 1 0 4 2 0 1 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6...

Страница 24: ...0 B A 6 3 W H E X 9 0 B 3 0 A W H E X X 5 1 B 7 3 A W H E X X 6 0 C A 3 0 C W H E X X 9 0 C A 3 0 C W H E X X 5 1 C A 3 0 A W H E X X 5 0 A 5 0 A W H E X X 0 1 A 5 0 A W H E X X X X 5 1 A 5 0 A W H E...

Страница 25: ...f f O k n a l B X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X 3 S V R C n r u t e R g n i r p S r o t a l i t n e V l a i c r e m m o C X 3 P V R C n r u t e R r e w o P r o t a l i t n...

Отзывы: