Manual 2100-581B 

Page  6 of 26

Clearances Required for Service Access 

and Adequate Condenser Airflow

MODELS

LEFT

SIDE

RIGHT

SIDE

DISCHARGE 

SIDE

W17A, W18A, W24A, W30A, W36A

15"

20"

10'

W17L, W18L, W24L, W30L, W36L

20"

15"

10'

W42A, W48A, W60A, W70A

20"

20"

10'

W42L, W48L, W60L, W70L

20"

20"

10'

Minimum Clearances Required to
Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST THREE FEET CABINET

W17A, L / W18A, L / W24A, L

0"

0"

W30A, L / W36A, L

1/4"

0"

W42A, L / W48A, L 

W60A, L / W70A, L

1/4"

0"

NOTE: For side by side installation of two (2) W**A models there 

must be 20" between units.  This can be reduced to 15" by using a 

W**L model (left side compressor and controls) for the left unit and 

WA (right side compressor and controls) for right unit.

See W**A Specification S3397 & W**L Specification S3400.

INSTALLATION INSTRUCTIONS

        WARNING

Failure to provide the 1/4 inch clearance 

between the supply duct and a combustible 

surface for the first 3 feet of duct can result in 

fire causing damage, injury or death.

WALL MOUNTING INFORMATION

  1. Two holes for the supply and return air openings 

must be cut through the wall as shown in Figure 3.

  2. On wood frame walls, the wall construction must be 

strong and rigid enough to carry the weight of the 
unit without transmitting any unit vibration.

  3. Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installed unit.

MOUNTING THE UNIT

  1. These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.  A bottom mounting bracket, attached 
to skid for shipping, is provided for ease of 
installation, but is not required.

  2. The unit itself is suitable for 0 inch clearance, 

but the supply air duct flange and the first 3 feet 

of supply air duct require a minimum of 1/4 inch 
clearance to combustible material for model series 
W30, W36, W42, W48, W60 and W70.  However, 
it is generally recommended that a 1-inch clearance 
is used for ease of installation and maintaining the 
required clearance to combustible material.  See 
Figure 3 for details on opening sizes.

  3. Locate and mark lag bolt locations and bottom 

mounting bracket location.  See Figure 3.

  4. Mount bottom mounting bracket.

  5. Hook top rain flashing, attached to front - right of 

supply flange for shipping, under back bend of top.

 6.  Position unit in opening and secure with 5/16 lag 

bolts; use 7/8 inch diameter flat washers on the lag 

bolts.

  7. Secure rain flashing to wall and caulk across entire 

length of top.  See Figure 3.

  8. For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

  9. On side-by-side installations, maintain a minimum 

of 20 inches clearance on right side to allow access 
to control panel and heat strips, and to allow proper 

airflow to the outdoor coil.  Additional clearance 

may be required to meet local or national codes.

Содержание W17A2

Страница 1: ...TIONERS MODELS W17A2 W17L2 W18A2 W18L2 W24A2 W24L2 W30A2 W30L2 W36A2 W36L2 W42A2 W42L2 W48A2 W48L2 W60A2 W60L2 W70A2 W70L2 Manual 2100 581B Supersedes 2100 581A File Volume III Tab 16 Date 11 25 13 Ba...

Страница 2: ...eat 23 Table 9A Optional Accessories Right Hand 24 Table 9B Optional Accessories Left Hand 25 Table 10 Vent Control Options 26 Getting Other Information and Publications 3 Wall Mount General Informati...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...n should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...T 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of in...

Страница 7: ...1 88 3 11 7 88 1 00 31 88 Heat models Electric Hood for ECONWMT MIS 2487 G 1 1 1 Condenser Filter Access Panel Front View Air Outlet Standard flush vent door for non ERV Econ models Ventilation Air 5...

Страница 8: ...G AT TIME OF INSTALLATION OPENING MIS 3157 ENTIRE LENGTH OF TOP RETURN AIR DUCT Wall Opening and Hole Location View Right Side View OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACC...

Страница 9: ...TES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER...

Страница 10: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Страница 11: ...ir duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could resu...

Страница 12: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...it breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starti...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Страница 17: ...e manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardl...

Страница 18: ...ge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding fan shroud to condenser and bot...

Страница 19: ...5 483 137 509 137 536 139 565 80 67 Low Side High Side 130 344 133 367 136 391 138 416 140 442 142 468 144 495 146 522 147 550 149 579 85 72 Low Side High Side 135 356 138 380 141 405 143 431 145 457...

Страница 20: ...1 or 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30A2 B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 18 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30A2 C00 C0Z C06 C09 C15...

Страница 21: ...6 56 30 30 50 60 10 10 8 6 10 10 10 10 W24L2 B00 B0Z B06 230 208 3 1 1 15 22 20 25 12 10 12 10 W24L2 C00 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30L2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2...

Страница 22: ...0 1285 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400 0 1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 19...

Страница 23: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12 1...

Страница 24: ...10 X X EHWA03 A15 X X EHWA03 B06 X EHW36A B06 X EHWA03 B09 X X EHWA37 B15 X X EHWC03A C06 X X EHWC03A C09 X X EHWA03A C12 X X EHWA03A C15 X X EHWA05 A05 X X EHWA05 A10 X X X X EHWA05 A15 X X X X EHWA0...

Страница 25: ...HWA03 A05L X X EHWA03 A08L X EHWA03 A10L X X EHWA03 A15L X X EHWA03 B09L X X EHWA37 B15L X X EHWC03 C09L X X EHWA03 C15L X X EHWA05 A05L X X X EHWA05 A10L X X X X EHWA05 A15L X X X X EHWA05 B09L X X E...

Страница 26: ...Damper Standard X BOP 3 Blank Off Plate X MFAD 3 Motorized Fresh Air Damper X CRVS 3 Commercial Ventilator Spring Return X CRVP 3 Commercial Ventilator Power Return X ECONWMS E3 ECONWMT E3 ECONWMT T3...

Отзывы: