Manual 2100-581B 

Page  22 of 26

TABLE  5

RECOMMENDED AIRFLOW

TABLE  6

INDOOR BLOWER PERFORMANCE

TABLE  7

MAXIMUM ESP OF OPERATION 

ELECTRIC HEAT ONLY

Values shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter.

Derate ESP by .15 for 2-inch pleated filters.

Model

Nominal 

Rated 

CFM  *

Nominal 

Rated 

ESP  *

Recommended 

Airflow Range

Factory Speed 

Connection

W17A, W17L

600

.40

550 - 725

Low

W18A, W18L

550

.45

550 - 725

Low

W24A, W24L

800

.30

700 - 950

Single

W30A, W30L

1000

.30

850 - 1300

High

W36A, W36L

1100

.20

930 - 1350

High

W42A, W42L

1400

.45

1600 - 1150

High

W48A, W48L

1550

.30

1750 - 1285

High

W60A, W60L

1700

.40

1950 - 1375

High

W70A, W70L

1700

.20

1950 - 1375

High

Speed

W17/18

W24

W30

W36

W42/48

W60

W70

High

Low

Single

High

Low

High

Low

High

Low

High

Low

High

Low

ESP

(Inch 

H20)

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

Dry 

Coil

Wet 

Coil

0.0

1045 1025

760

745

990

970

1370 1285 910

885

1415 1275 955

925

1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400

0.1

1010 970

730

715

945

925

1305 1225 885

860

1350 1215 945

915

1775 1725 1545 1500 2020 1960 1450 1405 1970 1770 1425 1340

0.2

940

905

700

685

890

870

1225 1135

850

815

1265 1125

925

900

1685 1640 1460 1415 1925 1865 1395 1355 1905 1700 1375 1295

0.3

860

830

670

655

820

800

1115 1020 790

755

1190 1060 875

850

1590 1550 1390 1345 1870 1815 1340 1300 1830 1645 1225 1150

0.4

780

750

610

595

735

720

1005 910

695

660

1085 975

780

755

1495 1460 1310 1270 1755 1705 1225 1185 1725 1550 1140 1070

0.5

665

640

485

455

605

590

865

775

590

560

970

865

640

615

1400 1365 1225 1185 1660 1610 1125 1085 1500 1350 1050 985

Model

W17A/L,

W18A/L, 

W24A/L

W30A/L, W36A/L

W42A/L, W48A/L

W60A/L, W70A/L

Outlet

FRONT

FRONT

TOP

FRONT

FRONT

Speed

Single

High

Low

High

Low

High

Low

High

Low

-A0Z

-A04

-A05

-A08

-A10

-A15

-A20

.50

.50

.50

.50

.50

.50

.50

.40

.50

.50

.50

.45

.35

.50

.50

.50

.50

.45

.35

.50

.50

.50

.50

.50

.50

.50

.50

.50

.45

.50

.50

.50

.50

.50

.50

.50

.50

.50

.40

-B0Z

-B06

-B09

-B15

-B18

.50

.50

.50

.50

.50

.45

.50

.40

.50

.30

.50

.45

.50

.40

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

-C0Z

-C06

-C09

-C15

.50

.50

.50

.45

.50

.50

.40

.35

.50

.45

.50

.40

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

* Rated CFM and ESP on factory speed connection.

Содержание W17A2

Страница 1: ...TIONERS MODELS W17A2 W17L2 W18A2 W18L2 W24A2 W24L2 W30A2 W30L2 W36A2 W36L2 W42A2 W42L2 W48A2 W48L2 W60A2 W60L2 W70A2 W70L2 Manual 2100 581B Supersedes 2100 581A File Volume III Tab 16 Date 11 25 13 Ba...

Страница 2: ...eat 23 Table 9A Optional Accessories Right Hand 24 Table 9B Optional Accessories Left Hand 25 Table 10 Vent Control Options 26 Getting Other Information and Publications 3 Wall Mount General Informati...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...n should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...T 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of in...

Страница 7: ...1 88 3 11 7 88 1 00 31 88 Heat models Electric Hood for ECONWMT MIS 2487 G 1 1 1 Condenser Filter Access Panel Front View Air Outlet Standard flush vent door for non ERV Econ models Ventilation Air 5...

Страница 8: ...G AT TIME OF INSTALLATION OPENING MIS 3157 ENTIRE LENGTH OF TOP RETURN AIR DUCT Wall Opening and Hole Location View Right Side View OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACC...

Страница 9: ...TES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER...

Страница 10: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Страница 11: ...ir duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could resu...

Страница 12: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...it breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starti...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Страница 17: ...e manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardl...

Страница 18: ...ge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding fan shroud to condenser and bot...

Страница 19: ...5 483 137 509 137 536 139 565 80 67 Low Side High Side 130 344 133 367 136 391 138 416 140 442 142 468 144 495 146 522 147 550 149 579 85 72 Low Side High Side 135 356 138 380 141 405 143 431 145 457...

Страница 20: ...1 or 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30A2 B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 18 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30A2 C00 C0Z C06 C09 C15...

Страница 21: ...6 56 30 30 50 60 10 10 8 6 10 10 10 10 W24L2 B00 B0Z B06 230 208 3 1 1 15 22 20 25 12 10 12 10 W24L2 C00 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30L2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2...

Страница 22: ...0 1285 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400 0 1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 19...

Страница 23: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12 1...

Страница 24: ...10 X X EHWA03 A15 X X EHWA03 B06 X EHW36A B06 X EHWA03 B09 X X EHWA37 B15 X X EHWC03A C06 X X EHWC03A C09 X X EHWA03A C12 X X EHWA03A C15 X X EHWA05 A05 X X EHWA05 A10 X X X X EHWA05 A15 X X X X EHWA0...

Страница 25: ...HWA03 A05L X X EHWA03 A08L X EHWA03 A10L X X EHWA03 A15L X X EHWA03 B09L X X EHWA37 B15L X X EHWC03 C09L X X EHWA03 C15L X X EHWA05 A05L X X X EHWA05 A10L X X X X EHWA05 A15L X X X X EHWA05 B09L X X E...

Страница 26: ...Damper Standard X BOP 3 Blank Off Plate X MFAD 3 Motorized Fresh Air Damper X CRVS 3 Commercial Ventilator Spring Return X CRVP 3 Commercial Ventilator Power Return X ECONWMS E3 ECONWMT E3 ECONWMT T3...