SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling 

in compressor contactor, starting the compressor and 
outdoor motor.  (See 

NOTE

 under Condenser Fan 

Operation if equipped with Low Ambient Control.)  The 
G (indoor motor) circuit is automatically completed 
by the thermostat on any call for cooling operation or 
can be energized by manual fan switch on subbase for 
constant air circulation.  On a call for heating, circuit 
R-W1 make at the thermostat pulling in heat contactor 
for the strip heat and blower operation.  On a call for 
second stage heat, R-W2 makes bringing on second heat 
contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all 
models covered by this manual.  The compressor 
control module is an anti-short cycle/lockout timer with 
high and low pressure switch monitoring and alarm 
relay output.

Adjustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to 
the unit, the 

delay on make

 period begins, which will 

be 2 minutes plus 10% of the 

delay on break

 setting.  

When the delay on make is complete and the high 
pressure switch and low pressure switch is closed, the 
compressor contactor is energized.  Upon shutdown, the 
delay on break timer starts and prevents restart until the 
delay on break and delay on make periods have expired.  

During routine operation of the unit with no power 
interruptions, the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes and the delay on  
break time has expired.  If the high pressure switch 
opens again in this same operating cycle, the unit will 
go into 

manual lockout

 condition and the alarm relay 

circuit will energize.  Recycling the wall thermostat 
resets the manual lockout. 

Low Pressure Switch, Bypass, and Lockout 

Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize 
and go into a soft lockout.  Regardless the state of the 
low pressure switch, the contactor will reenergize after 
the delay on make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
than 120 seconds, the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications 
where alarm relay is employed.  This terminal is 
powered whenever the compressor is locked out due to 
HPC or LPC sequences as described.

NOTE:  Both high and low pressure switch controls are 

inherently automatic reset devices.  The high 
pressure switch and low pressure switch cut 

out and cut in settings are fixed by specific air 

conditioner unit model.  The lockout features, 
both soft and manual, are a function of the 
Compressor Control Module. 

ADJUSTMENTS
Adjustable Delay on Make and Delay on Break 

Timer

The potentiometer is used to select Delay on Break time 
from 30 seconds to 5 minutes.  Delay on Make (DOM) 
timing on power-up and after power interruptions is 
equal to 2 minutes plus 10% of Delay on Break (DOB) 
setting:

  0.5 minute  (30 seconds)  DOB = 123  second DOM
  1.0 minute  (60 seconds)  DOB = 126  second DOM
  2.0 minute  (120 seconds)  DOB = 132  second DOM
  3.0 minute  (180 seconds)  DOB = 138  second DOM
  4.0 minute  (240 seconds)  DOB = 144  second DOM
  5.0 minute  (300 seconds)  DOB =  150  second DOM

During routine operation of the unit with no power 
interruptions the compressor will operate on demand 
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on 
all units so that the system operating pressures can be 
observed.  A pressure table can be found later in the 
manual covering all models.  It is imperative to match 
the correct pressure table to the unit by model number.  
See Table 2.

Содержание W17A2

Страница 1: ...TIONERS MODELS W17A2 W17L2 W18A2 W18L2 W24A2 W24L2 W30A2 W30L2 W36A2 W36L2 W42A2 W42L2 W48A2 W48L2 W60A2 W60L2 W70A2 W70L2 Manual 2100 581B Supersedes 2100 581A File Volume III Tab 16 Date 11 25 13 Ba...

Страница 2: ...eat 23 Table 9A Optional Accessories Right Hand 24 Table 9B Optional Accessories Left Hand 25 Table 10 Vent Control Options 26 Getting Other Information and Publications 3 Wall Mount General Informati...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...n should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...T 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of in...

Страница 7: ...1 88 3 11 7 88 1 00 31 88 Heat models Electric Hood for ECONWMT MIS 2487 G 1 1 1 Condenser Filter Access Panel Front View Air Outlet Standard flush vent door for non ERV Econ models Ventilation Air 5...

Страница 8: ...G AT TIME OF INSTALLATION OPENING MIS 3157 ENTIRE LENGTH OF TOP RETURN AIR DUCT Wall Opening and Hole Location View Right Side View OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACC...

Страница 9: ...TES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER...

Страница 10: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Страница 11: ...ir duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could resu...

Страница 12: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...it breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starti...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Страница 17: ...e manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardl...

Страница 18: ...ge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding fan shroud to condenser and bot...

Страница 19: ...5 483 137 509 137 536 139 565 80 67 Low Side High Side 130 344 133 367 136 391 138 416 140 442 142 468 144 495 146 522 147 550 149 579 85 72 Low Side High Side 135 356 138 380 141 405 143 431 145 457...

Страница 20: ...1 or 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30A2 B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 18 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30A2 C00 C0Z C06 C09 C15...

Страница 21: ...6 56 30 30 50 60 10 10 8 6 10 10 10 10 W24L2 B00 B0Z B06 230 208 3 1 1 15 22 20 25 12 10 12 10 W24L2 C00 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30L2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2...

Страница 22: ...0 1285 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400 0 1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 19...

Страница 23: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12 1...

Страница 24: ...10 X X EHWA03 A15 X X EHWA03 B06 X EHW36A B06 X EHWA03 B09 X X EHWA37 B15 X X EHWC03A C06 X X EHWC03A C09 X X EHWA03A C12 X X EHWA03A C15 X X EHWA05 A05 X X EHWA05 A10 X X X X EHWA05 A15 X X X X EHWA0...

Страница 25: ...HWA03 A05L X X EHWA03 A08L X EHWA03 A10L X X EHWA03 A15L X X EHWA03 B09L X X EHWA37 B15L X X EHWC03 C09L X X EHWA03 C15L X X EHWA05 A05L X X X EHWA05 A10L X X X X EHWA05 A15L X X X X EHWA05 B09L X X E...

Страница 26: ...Damper Standard X BOP 3 Blank Off Plate X MFAD 3 Motorized Fresh Air Damper X CRVS 3 Commercial Ventilator Spring Return X CRVP 3 Commercial Ventilator Power Return X ECONWMS E3 ECONWMT E3 ECONWMT T3...

Отзывы: