background image

Manual 2100-581B 

Page 

19 of 26

TABLE  2 

COOLING PRESSURE TABLE

Air Temperature Entering Outdoor Coil °F

Low side pressure  ± 4 PSIG                                                         

High side pressure ± 10 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil.  If there is any doubt as to correct operating charge 

being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.

NOTE: 

Pressure table based on high speed condenser fan operation.  If condensing pressures appear elevated check  

 

condenser fan wiring.  See “Condenser Fan Operation”.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

W17A/L

75/62

Low Side

High Side

124

321

126

340

128

362

130

384

132

409

133

434

135

461

137

490

138

521

140

553

80/67

Low Side

High Side

133

329

135

349

137

371

139

394

141

419

142

445

144

473

146

503

148

534

150

567

85/72

Low Side

High Side

138

341

140

361

142

384

144

408

146

434

147

461

149

490

151

521

153

553

155

587

W18A/L

75/62

Low Side

High Side

127

318

129

339

131

362

133

385

135

409

137

434

138

459

140

486

143

513

145

541

80/67

Low Side

High Side

136

326

138

348

140

371

142

395

144

419

146

445

148

471

150

498

153

526

155

555

85/72

Low Side

High Side

141

337

143

360

145

384

147

409

149

434

151

461

153

487

155

515

158

544

160

574

W24A/L

75/62

Low Side

High Side

119

340

121

361

122

383

124

407

127

432

129

459

131

488

133

518

135

550

137

583

80/67

Low Side

High Side

127

349

129

370

131

393

133

417

136

443

138

471

140

500

142

531

144

564

146

598

85/72

Low Side

High Side

131

361

134

383

136

407

138

432

141

459

143

487

145

518

147

550

149

584

151

619

W30A/L

75/62

Low Side

High Side

122

335

124

358

127

381

129

406

131

431

133

456

135

483

137

509

137

536

139

565

80/67

Low Side

High Side

130

344

133

367

136

391

138

416

140

442

142

468

144

495

146

522

147

550

149

579

85/72

Low Side

High Side

135

356

138

380

141

405

143

431

145

457

147

484

149

512

151

540

152

569

154

599

W36A/L

75/62

Low Side

High Side

120

339

122

366

124

392

126

418

129

446

130

473

132

501

134

529

135

558

136

586

80/67

Low Side

High Side

128

348

130

375

133

402

135

429

138

457

139

485

141

514

143

543

144

572

145

601

85/72

Low Side

High Side

132

360

135

388

138

416

140

444

143

473

144

502

146

532

148

562

149

592

150

622

W42A/L

75/62

Low Side

High Side

123

320

124

342

126

367

128

391

130

416

132

443

134

469

136

496

137

526

139

554

80/67

Low Side

High Side

132

328

133

351

135

376

137

401

139

427

141

454

143

481

145

509

147

539

149

568

85/72

Low Side

High Side

137

339

138

363

140

389

142

415

144

442

146

470

148

498

150

527

152

558

154

588

W48A/L

75/62

Low Side

High Side

117

355

119

378

121

403

123

427

125

454

127

482

129

510

131

539

133

570

135

603

80/67

Low Side

High Side

125

364

127

388

129

413

132

438

134

466

136

494

138

523

140

553

142

585

144

618

85/72

Low Side

High Side

129

377

131

402

134

427

137

453

139

482

141

511

143

541

145

572

147

605

149

640

W60A/L

75/62

Low Side

High Side

122

346

124

371

126

396

128

421

130

447

131

473

133

499

135

526

137

553

138

580

80/67

Low Side

High Side

131

355

133

380

135

406

137

432

139

458

140

485

142

512

144

539

146

567

148

595

85/72

Low Side

High Side

136

367

138

393

140

420

142

447

144

474

145

502

147

530

149

558

151

587

153

616

W70A/L

75/62

Low Side

High Side

118

349

121

371

122

395

123

419

125

444

127

470

129

497

131

525

132

553

134

583

80/67

Low Side

High Side

126

358

129

381

131

405

132

430

134

455

136

482

138

510

140

538

141

567

143

598

85/72

Low Side

High Side

130

371

134

394

136

419

137

445

139

471

141

499

143

528

145

557

146

587

148

619

Содержание W17A2

Страница 1: ...TIONERS MODELS W17A2 W17L2 W18A2 W18L2 W24A2 W24L2 W30A2 W30L2 W36A2 W36L2 W42A2 W42L2 W48A2 W48L2 W60A2 W60L2 W70A2 W70L2 Manual 2100 581B Supersedes 2100 581A File Volume III Tab 16 Date 11 25 13 Ba...

Страница 2: ...eat 23 Table 9A Optional Accessories Right Hand 24 Table 9B Optional Accessories Left Hand 25 Table 10 Vent Control Options 26 Getting Other Information and Publications 3 Wall Mount General Informati...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...n should be consulted before the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according...

Страница 5: ...RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient...

Страница 6: ...T 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of in...

Страница 7: ...1 88 3 11 7 88 1 00 31 88 Heat models Electric Hood for ECONWMT MIS 2487 G 1 1 1 Condenser Filter Access Panel Front View Air Outlet Standard flush vent door for non ERV Econ models Ventilation Air 5...

Страница 8: ...G AT TIME OF INSTALLATION OPENING MIS 3157 ENTIRE LENGTH OF TOP RETURN AIR DUCT Wall Opening and Hole Location View Right Side View OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACC...

Страница 9: ...TES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER...

Страница 10: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Страница 11: ...ir duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could resu...

Страница 12: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...it breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starti...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Страница 17: ...e manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardl...

Страница 18: ...ge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screws holding fan shroud to condenser and bot...

Страница 19: ...5 483 137 509 137 536 139 565 80 67 Low Side High Side 130 344 133 367 136 391 138 416 140 442 142 468 144 495 146 522 147 550 149 579 85 72 Low Side High Side 135 356 138 380 141 405 143 431 145 457...

Страница 20: ...1 or 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30A2 B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 18 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30A2 C00 C0Z C06 C09 C15...

Страница 21: ...6 56 30 30 50 60 10 10 8 6 10 10 10 10 W24L2 B00 B0Z B06 230 208 3 1 1 15 22 20 25 12 10 12 10 W24L2 C00 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30L2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2...

Страница 22: ...0 1285 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400 0 1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 19...

Страница 23: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12 1...

Страница 24: ...10 X X EHWA03 A15 X X EHWA03 B06 X EHW36A B06 X EHWA03 B09 X X EHWA37 B15 X X EHWC03A C06 X X EHWC03A C09 X X EHWA03A C12 X X EHWA03A C15 X X EHWA05 A05 X X EHWA05 A10 X X X X EHWA05 A15 X X X X EHWA0...

Страница 25: ...HWA03 A05L X X EHWA03 A08L X EHWA03 A10L X X EHWA03 A15L X X EHWA03 B09L X X EHWA37 B15L X X EHWC03 C09L X X EHWA03 C15L X X EHWA05 A05L X X X EHWA05 A10L X X X X EHWA05 A15L X X X X EHWA05 B09L X X E...

Страница 26: ...Damper Standard X BOP 3 Blank Off Plate X MFAD 3 Motorized Fresh Air Damper X CRVS 3 Commercial Ventilator Spring Return X CRVP 3 Commercial Ventilator Power Return X ECONWMS E3 ECONWMT E3 ECONWMT T3...

Отзывы: