background image

Manual 2100-526H
Page 

8 of 24

WALL MOUNTING INFORMATION

1.  Two holes, for the supply and return air openings, 

must be cut through the wall as shown in Figure 3.

2.  On wood-frame walls, the wall construction must 

be strong and rigid enough to carry the weight of 
the unit without transmitting any unit vibration.  
See Figures 4 and 5.  

INSTALLATION

3.  Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installing unit.  See Figure 4.

MOUNTING THE UNIT

1.  These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.  A bottom mounting bracket is provided 
for ease of installation.

2.  The unit itself is suitable for “0” inch clearance, 

but the supply air duct flange and the first 3 feet 
of supply air duct require a minimum of 1/4 inch 
clearance to combustible material.  If a combustible 
wall, use a minimum of 30-1/2” x 10-1/2” 
dimensions for sizing.  However, it is generally 
recommended that a 1-inch clearance is used for 
ease of installation and maintaining the required 
clearance to combustible material.  The supply air 
opening would then be 32” x 12”.  See Figures 2, 3 
and 6 for details.

3.  Locate and mark lag bolt locations and bottom 

mounting bracket location.  See Figure 4.

4.  Mount bottom mounting bracket.

5.  Hook top rain flashing under back bend of top.  Top 

rain flashing is shipped secured to the right side of 
the back.

6.  Position unit in opening and secure with 5/16 lag 

bolts; use 7/8 inch diameter flat washers on the lag 
bolts.

7.  Secure rain flashing to wall and caulk across entire 

length of top.  See Figure 2.

8.  For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

9.  On side-by-side installations, maintain a minimum 

of 20 inches clearance on right side to allow access 
to heat strips and control panel and to allow proper 
airflow to the outdoor coil.  Additional clearance 
may be required to meet local or national codes.

TYPICAL INSTALLATIONS

See Figure 5 for common ways to install the wall mount 
unit.

WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information 
and maximum fuse or circuit breaker size.  Each 
outdoor unit is marked with a “Minimum Circuit 
Ampacity”.  This means that the field wiring used must 
be sized to carry that amount of current.  Depending on 
the installed KW of electric heat, there may be two field 
power circuits required.  If this is the case, the unit 
serial plate will so indicate.  All models are suitable 
only for connection with copper wire.  Each unit and/or 
wiring diagram will be marked “Use Copper Conductors 
Only”.  These instructions 

must be

 adhered to.  Refer 

to the National Electrical Code (NEC) for complete 
current carrying capacity data on the various insulation 
grades of wiring material.  All wiring must conform to 
NEC and all local codes.

The electrical data lists fuse and wire sizes (75ºC 
copper) for all models, including the most commonly 
used heater sizes.  Also shown are the number of field 
power circuits required for the various models with 
heaters.

        WARNING 

Fire hazard can result if 1/4 inch clearance 

to combustible materials for supply air duct is 

not maintained.  See Figure 3.                                                  

        WARNING

  

Failure to provide the 1/4 inch clearance 

between the supply duct and a combustible 

surface for the first 3 feet of duct can result in 

fire.                                                            

Содержание THE WALL-MOUNT WA3S3-A

Страница 1: ...NSTRUCTIONS WA3S3 A WA3S3 B WA3S3 C WA4S3 A WA4S3 B WA4S3 C WA5S3 A WA5S3 B WA5S3 C WL3S2 A WL3S2 B WL3S2 C WL4S2 A WL4S2 B WL4S2 C WL5S2 A WL5S2 B WL5S2 C Bard Manufacturing Company Inc Bryan Ohio 43...

Страница 2: ...3 General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High and Low Pressure Switch 14 Three Phase Scroll Compressor Start Up Information 14 Ser...

Страница 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning For more information contact these publishers ACCA Air...

Страница 4: ...in 480V units only VOLTS PHASE A 230 208 1 B 230 208 60 3 C 460 60 3 KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 06 6 KW 08 8 KW 09 9 KW 10 10 KW 15 15 KW 20 20 KW VENTILATION OPTIONS B...

Страница 5: ...scale I A C K 2 13 H J 2 63 9 06 P M L O E 44 W 5 75 F G R S S S S S T D Return Air Opening MIS 2488 B Drain Inlet Air Air Outlet Front View Side View Cond 1 Back View Condenser Bracket Installation B...

Страница 6: ...1 1 28 29 38 56 40 40 40 60 10 10 8 6 10 10 10 10 WA L4S C0Z C06 C09 C15 460 3 1 1 1 1 15 16 21 30 20 20 25 30 12 12 10 10 12 12 10 10 WA L5S A0Z A05 A08 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 1 or...

Страница 7: ...ons thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure availab...

Страница 8: ...ting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance...

Страница 9: ...nded that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation B 16 16 16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Typ 6 1...

Страница 10: ...IR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRU...

Страница 11: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 12: ...CE Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover 8403 058 TH5220D1151 2 stage Cool...

Страница 13: ...rigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refriger...

Страница 14: ...he Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no ne...

Страница 15: ...ng When the delay on make is complete and the high pressure and low pressure switches are closed the compressor contactor is energized Upon shutdown the delay or break timer starts and prevents restar...

Страница 16: ...erve whether unit is operating in high cool or low cool when utilizing the charts This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader va...

Страница 17: ...another click as the solenoid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil re...

Страница 18: ...h this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shou...

Страница 19: ...465 146 492 148 519 85 DB 72 WB Low Side High Side 137 216 139 237 140 258 141 279 142 300 143 321 146 346 148 370 151 395 153 419 155 447 157 474 158 502 160 529 LOW CAPAPACITY COOLING AIR TEMPERATU...

Страница 20: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 21: ...g and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement control per one of the three following paragraphs 8a 8b or 8c 8a I...

Страница 22: ...at Will occur automatically with a call for W1 signal from thermostat Will occur automatically with a call for W2 or Emergency Heat signal from thermostat TABLE 9 INDOOR BLOWER PERFORMANCE Model Rated...

Страница 23: ...er Package X EHWA5S A15 Heater Package X EHWA5S A20 Heater Package X EHWA3S B06 Heater Package X EHWA5S B06 Heater Package X X EHWA5S B09 Heater Package X X X EHWA5S B15 Heater Package X X X EHWA5S C0...

Страница 24: ...r Package X EHWA5S A15L Heater Package X EHWA5S A20L Heater Package X EHWA3S B06L Heater Package X EHWA5S B06L Heater Package X X EHWA5S B09L Heater Package X X X EHWA5S B15L Heater Package X X X EHWA...

Отзывы: