Manual 2100-526H
Page
6 of 24
Model
Rated V
olts and
Phase
No. Field
Power Circuits
Minimum
Circuit Ampacity
Maximum External
Fuse or
Ckt. Brkr
.
Field Power W
ire
Size
Ground
W
ire
Minimum
Circuit Ampacity
Maximum
External Fuse or
Ckt. Brkr
.
Field Power W
ire Size
Ground
W
ire
Ckt. A
Ckt. B
Ckt. C
Ckt. A
Ckt. B
Ckt. C
Ckt. A
Ckt. B
Ckt. C
Ckt. A
Ckt. B
Ckt. C
W
A/L3S* - A0Z
- A05
- A08
- A10
- A15
- A20
230/208-1
1
1
1
1 or 2
1 or 2
1 or 3
31
35
51
61
87
113
45
45
60
70
90
115
8
8
6
6
3
2
10
10
10
8
8
6
35
35
35
26
52
52
26
45
45
45
30
60
60
30
8
8
8
10
6
6
10
10
10
10
10
10
10
10
W
A/L3S* - B0Z
- B06
- B09
- B15
230/208-3
1
1
1
1
23
27
36
55
30
30
40
60
10
10
8
6
10
10
10
10
W
A/L3S* - C0Z
- C06
- C09
- C15
460-3
1
1
1
1
12
13.5
19
28
15
15
20
30
14
14
12
10
14
14
12
10
W
A/L4S* - A0Z
- A05
- A08
- A10
- A15
- A20
230/208-1
1
1
1
1 or 2
1 or 2
1 or 3
38
38
53
63
89
115
45
45
60
70
90
120
8
8
6
4
3
2
10
10
10
8
8
6
37
37
37
26
52
52
26
45
45
45
30
60
60
30
8
8
8
10
6
6
10
10
10
10
10
10
10
10
W
A/L4S* - B0Z
- B06
- B09
- B1
230/208-3
1
1
1
1
28
29
38
56
40
40
40
60
10
10
8
6
10
10
10
10
W
A/L4S* - C0Z
- C06
- C09
- C15
460-3
1
1
1
1
15
16
21
30
20
20
25
30
12
12
10
10
12
12
10
10
W
A/L5S* - A0Z
- A05
- A08
- A10
- A15
- A20
230/208-1
1
1
1
1 or 2
1 or 2
1 or 3
44
44
53
63
89
115
50
50
60
70
90
120
8
8
6
6
3
2
10
10
10
8
8
6
44
44
44
26
52
52
26
50
50
50
30
60
60
30
8
8
8
10
6
6
10
10
10
10
10
10
10
10
W
A/L5S* - B0Z
- B06
- B09
- B15
230/208-3
1
1
1
1
34
34
38
56
40
40
40
60
8
8
8
6
10
10
10
10
W
A/L5S* - C0Z
- C06
- C09
- C15
460-3
1
1
1
1
17
17
21
30
25
25
25
30
10
10
10
10
10
10
10
10
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electric Code (NEC) and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest version), Article 310 for power
conductor sizing.
CAUTION: When more than one filed power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to Note * of T
able 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway
.
TABLE 3
ELECTRICAL SPECIFICA
TIONS