background image

Manual 2100-526H
Page 

21 of 24

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower 
motor you need to take the following steps:
  1. You MUST have the correct replacement module.  The controls 
are factory programmed for specific operating modes.  Even though 
they look alike, different modules may have completely different 
functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT WARRANTIES 
AND MAY PRODUCE UNEXPECTED RESULTS.
 

2. Begin by removing AC power from the furnace or air handler 

being serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect power 
and wait at least 5 minutes before opening motor.
  3. It is usually not necessary to remove the motor from the blower 
assembly.  However, it is recommended that the whole blower 
assembly, with the motor, be removed from the furnace/air handler.  
(Follow the manufacturer’s procedures).  Unplug the two cable 
connectors to the motor.  There are latches on each connector.  

DO NOT 

PULL ON THE WIRES.  

The plugs remove easily when properly released.

  4. Locate the two standard ¼” hex head bolts at the rear of the 
control housing (at the back end of the control opposite the shaft end).  

Refer to Figure 9.  

Remove these two bolts from the motor and control 

assembly while holding the motor in a way that will prevent the motor 
or control from falling when the bolts are removed.  If an ECM2.0 
control is being replaced (recognized by an aluminum casting rather 
that a deep-drawn black steel can housing the electronics), remove 
only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD SCREWS.

  5. The control module is now free of mechanical attachment to 
the motor endshield but is still connected by a plug and three wires 
inside the control.  Carefully rotate the control to gain access to the 
plug at the control end of the wires.  With thumb and forefinger, reach 
the latch holding the plug to the control and release it by squeezing 
the latch tab and the opposite side of the connector plug and gently 
pulling the plug out of the connector socket in the control.  

DO NOT 

PULL ON THE WIRES.  GRIP THE PLUG ONLY.

  6. The control module is now completely detached from the motor.  
Verify with a standard ohmmeter that the resistance from each motor 
lead (in the motor plug just removed) to the motor shell is >100K 
ohms.  

Refer to Figure 10.  

(Measure to unpainted motor end plate.)  

If any motor lead fails this test, do not proceed to install the control 
module.  

THE MOTOR IS DEFECTIVE AND MUST BE REPLACED.

  Installing 

the new control module will cause it to fail also.
  7. Verify that the replacement control is correct for your application.  
Refer to the manufacturer’s authorized replacement list.  

USING THE 

WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION.

  

Orient the control module so that the 3-wire motor plug can be 
inserted into the socket in the control.  Carefully insert the plug and 
press it into the socket until it latches.  

A SLIGHT CLICK WILL BE HEARD 

WHEN PROPERLY INSERTED.

  Finish installing the replacement control 

per one of the three following paragraphs, 8a, 8b or 8c.
 8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast aluminum 

can with air vents on the back of the can) 

WITH AN ECM 2.3 CONTROL

 

(control containing black potting for water protection in black deep-
drawn steel case with no vents in the bottom of the can), locate the 
two through-bolts and plastic tab that are packed with the replacement 
control.  Insert the plastic tab into the slot at the perimeter of the 
open end of the can so that the pin is located on the inside of the 
perimeter of the can.  Rotate the can so that the tab inserts into the 
tab locater hole in the endshield of the motor.  Using the two through-
bolts provided with the replacement control, reattach the can to the 
motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE REPLACEMENT ECM 2.3 
CONTROL ARE SHORTER THAN THE BOLTS ORIGINALLY REMOVED FROM THE 
ECM 2.0 CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF THE 
CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS.

 

 8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM 2.3 CONTROL

the plastic tab and shorter through-bolts are not needed.  The 
control can be oriented in two positions 180° apart.  

MAKE SURE THE 

ORIENTATION YOU SELECT FOR REPLACING THE CONTROL ASSURES THE 
CONTROL’S CABLE CONNECTORS WILL BE LOCATED DOWNWARD IN THE 
APPLICATION SO THAT WATER CANNOT RUN DOWN THE CABLES AND INTO 
THE CONTROL.

  Simply orient the new control to the motor’s endshield, 

insert bolts, and tighten.  

DO NOT OVERTIGHTEN THE BOLTS.

 

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0 CONTROL 

(It 

is recommended that ECM 2.3 controls be used for all replacements), 

the new control must be attached to the motor using through 
bolts identical to those removed with the original control.  

DO NOT 

OVERTIGHTEN THE BOLTS.

  9. Reinstall the blower/motor assembly into the HVAC equipment.  
Follow the manufacturer’s suggested procedures.
  10. Plug the 16-pin control plug into the motor.  The plug is keyed.  
Make sure the connector is properly seated and latched.
  11. Plug the 5-pin power connector into the motor.  Even though 
the plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT FORCE 

THE CONNECTOR.

  It plugs in very easily when properly oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE FAILURE OF THE CONTROL 
MODULE.

  12. Final installation check.  Make sure the motor is installed as 
follows:
    a. Unit is as far INTO the blower housing as possible.
    b. Belly bands are not on the control module or covering vent  
   holes.
    c. Motor connectors should be oriented between the 4 o’clock  
      and 8 o’clock positions when the blower is positioned in its  
      final location and orientation.
    d. Add a drip loop to the cables so that water cannot enter the  
      motor by draining down the cables.  

Refer to Figure 11.

The installation is now complete.  Reapply the AC power to the HVAC 
equipment and verify that the new motor control module is working 
properly.  Follow the manufacturer’s procedures for disposition of the 
old control module.

Figure 10

Figure 9

Figure 11

Содержание THE WALL-MOUNT WA3S3-A

Страница 1: ...NSTRUCTIONS WA3S3 A WA3S3 B WA3S3 C WA4S3 A WA4S3 B WA4S3 C WA5S3 A WA5S3 B WA5S3 C WL3S2 A WL3S2 B WL3S2 C WL4S2 A WL4S2 B WL4S2 C WL5S2 A WL5S2 B WL5S2 C Bard Manufacturing Company Inc Bryan Ohio 43...

Страница 2: ...3 General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High and Low Pressure Switch 14 Three Phase Scroll Compressor Start Up Information 14 Ser...

Страница 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning For more information contact these publishers ACCA Air...

Страница 4: ...in 480V units only VOLTS PHASE A 230 208 1 B 230 208 60 3 C 460 60 3 KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 06 6 KW 08 8 KW 09 9 KW 10 10 KW 15 15 KW 20 20 KW VENTILATION OPTIONS B...

Страница 5: ...scale I A C K 2 13 H J 2 63 9 06 P M L O E 44 W 5 75 F G R S S S S S T D Return Air Opening MIS 2488 B Drain Inlet Air Air Outlet Front View Side View Cond 1 Back View Condenser Bracket Installation B...

Страница 6: ...1 1 28 29 38 56 40 40 40 60 10 10 8 6 10 10 10 10 WA L4S C0Z C06 C09 C15 460 3 1 1 1 1 15 16 21 30 20 20 25 30 12 12 10 10 12 12 10 10 WA L5S A0Z A05 A08 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 1 or...

Страница 7: ...ons thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure availab...

Страница 8: ...ting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance...

Страница 9: ...nded that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation B 16 16 16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Typ 6 1...

Страница 10: ...IR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRU...

Страница 11: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 12: ...CE Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover 8403 058 TH5220D1151 2 stage Cool...

Страница 13: ...rigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refriger...

Страница 14: ...he Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no ne...

Страница 15: ...ng When the delay on make is complete and the high pressure and low pressure switches are closed the compressor contactor is energized Upon shutdown the delay or break timer starts and prevents restar...

Страница 16: ...erve whether unit is operating in high cool or low cool when utilizing the charts This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader va...

Страница 17: ...another click as the solenoid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil re...

Страница 18: ...h this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shou...

Страница 19: ...465 146 492 148 519 85 DB 72 WB Low Side High Side 137 216 139 237 140 258 141 279 142 300 143 321 146 346 148 370 151 395 153 419 155 447 157 474 158 502 160 529 LOW CAPAPACITY COOLING AIR TEMPERATU...

Страница 20: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 21: ...g and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement control per one of the three following paragraphs 8a 8b or 8c 8a I...

Страница 22: ...at Will occur automatically with a call for W1 signal from thermostat Will occur automatically with a call for W2 or Emergency Heat signal from thermostat TABLE 9 INDOOR BLOWER PERFORMANCE Model Rated...

Страница 23: ...er Package X EHWA5S A15 Heater Package X EHWA5S A20 Heater Package X EHWA3S B06 Heater Package X EHWA5S B06 Heater Package X X EHWA5S B09 Heater Package X X X EHWA5S B15 Heater Package X X X EHWA5S C0...

Страница 24: ...r Package X EHWA5S A15L Heater Package X EHWA5S A20L Heater Package X EHWA3S B06L Heater Package X EHWA5S B06L Heater Package X X EHWA5S B09L Heater Package X X X EHWA5S B15L Heater Package X X X EHWA...

Отзывы: