Manual 2100-526H
Page
22 of 24
TABLE 10
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Motor will deliver consistent CFM through voltage supply range with no deterioration.
(197-253V for 230/208V models, 414-506V for 460V models)
Continuous CFM is the total air being circulated during continuous (manual) fan mode.
Will occur automatically with a call for "Y1" signal from thermostat.
Will occur automatically with a call for "Y2" signal from thermostat.
Will occur automatically with a call for "W1" signal from thermostat.
Will occur automatically with a call for "W2" or "Emergency Heat" signal from thermostat.
TABLE 9
INDOOR BLOWER PERFORMANCE
Model
Rated ESP
MAX ESP
Continuous
CFM
Rated 1st
Stage CFM
Rated 2nd
Stage CFM
5-10KW
CFM
15-20 KW
CFM
WA/L3S*
0.15
0.80
800
800
1100
1100
1400
WA/L4S*
0.20
0.80
825
1100
1500
1100
1500
WA/L5S*
0.20
0.80
850
1300
1700
1100
1500
KW-Heat
WA/L3S*
WA/L4S*
WA/L5S*
-A05
-A08
-A10
-A15
-A20
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
-B06
-B09
-B12
-B15
-B18
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
-C06
-C09
-C12
-C15
-C18
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80
.80