CHECKING TEMPERATURE SENSOR
OUTSIDE UNIT CIRCUIT

1. Disconnect temperature sensor from board and from

outdoor coil.

2. Use an ohmmeter and measure the resistance of the

sensor.  Also use ohmmeter to check for short or
open.

3. Check resistance reading to chart of resistance use

sensor ambient temperature.  (Tolerance of part is
± 10%)

4. If sensor resistance reads very low, then sensor is

shorted and will not allow proper operation of the
heat pump control.

5. If sensor is out of tolerance, shorted, open, or reads

very low ohms then it should be replaced.

     F

        R

     F

        R

     F

             R

-25.0

-24.0

-23.0

-22.0

-21.0

-20.0

-19.0

-18.0

-17.0

-16.0

-15.0

-14.0

-13.0

-12.0

-11.0

-10.0

-9.0

-8.0

-7.0

-6.0

-5.0

-4.0

-3.0

-2.0

-1.0

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

11.0

12.0

13.0

14.0

15.0

16.0

17.0

18.0

19.0

20.0

21.0

22.0

23.0

24.0

196871

190099

183585

177318

171289

165487

159904

154529

149355

144374

139576

134956

130506

126219

122089

118108

114272

110575

107010

103574

100260

97064

93981

91008

88139

85371

82699

80121

77632

75230

72910

70670

68507

66418

64399

62449

60565

58745

56985

55284

53640

52051

50514

49028

47590

46200

44855

43554

42295

41077

25.0

26.0

27.0

28.0

29.0

30.0

31.0

32.0

33.0

34.0

35.0

36.0

37.0

38.0

39.0

40.0

41.0

42.0

43.0

44.0

45.0

46.0

47.0

48.0

49.0

50.0

51.0

52.0

53.0

54.0

55.0

56.0

57.0

58.0

59.0

60.0

61.0

62.0

63.0

64.0

65.0

66.0

67.0

68.0

69.0

70.0

71.0

72.0

73.0

74.0

39898

38757

37652

36583

35548

34545

33574

32634

31723

30840

29986

29157

28355

27577

26823

26092

25383

24696

24030

23384

22758

22150

21561

20989

20435

19896

19374

18867

18375

17898

17434

16984

16547

16122

15710

15310

14921

14544

14177

13820

13474

13137

12810

12492

12183

11883

11591

11307

11031

10762

75.0

76.0

77.0

78.0

79.0

80.0

81.0

82.0

83.0

84.0

85.0

86.0

87.0

88.0

89.0

90.0

91.0

92.0

93.0

94.0

95.0

96.0

97.0

98.0

99.0

100.0

101.0

102.0

103.0

104.0

105.0

106.0

107.0

108.0

109.0

110.0

111.0

112.0

113.0

114.0

115.0

116.0

117.0

118.0

119.0

120.0

121.0

122.0

123.0

124.0

10501

10247

10000

9760

9526

9299

9077

8862

8653

8449

8250

8057

7869

7686

7507

7334

7165

7000

6840

6683

6531

6383

6239

6098

5961

5827

5697

5570

5446

5326

5208

5094

4982

4873

4767

4663

4562

4464

4367

4274

4182

4093

4006

3921

3838

3757

3678

3601

3526

3452

TEMPERATURE F VS RESISTANCE R OF TEMPERATURE

Содержание SH611

Страница 1: ...NSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH611 Manual 2100 411G Supersedes 2100 411F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 19...

Страница 2: ...d CFM and Rated ESP 22 Table 9 Indoor Blower Performance 22 Table 10 Maximum ESP of Operation 22 Table 11 Pressure Table Cooling 23 Table 12 Pressure Table Heating 23 Getting Other Information and Pub...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...2 0 2 2 3 8 0 6 2 8 6 4 2 7 0 0 2 1 5 MODEL NUMBER CONTROL MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Dampe...

Страница 5: ...Manual 2100 411G Page 5 of 23 FIGURE 1 UNIT DIMENSIONS SH611...

Страница 6: ...an adequate duct system than a straight air conditioning unit All duct work supply and return must be properly sized for the design airflow requirement of the equipment Air Conditioning Contractors o...

Страница 7: ...using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The filter slides into position...

Страница 8: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 3 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Страница 9: ...796 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Supply flange Side view of wall w...

Страница 10: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 11: ...Manual 2100 411G Page 11 of 23 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 12: ...Manual 2100 411G Page 12 of 23 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 13: ...Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits requir...

Страница 14: ...pment at the time of manufacture is not designated for any specific destination of the country and are installed in areas not approaching the lower outdoor temperature range outdoor thermostats are no...

Страница 15: ...ermostat This is done to maximize efficiency by utilizing the heat pump to bring the FIGURE 12 ELECTRIC HEAT HOLD OFF WIRING 15 20KW 1 PH 3 PH FIGURE 11 ELECTRIC HEAT HOLD OFF WIRING 4 10KW 1 PH 6 9KW...

Страница 16: ...uired 5 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Removing...

Страница 17: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Страница 18: ...the system operating pressures can be observed Pressure tables can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure ta...

Страница 19: ...r time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch...

Страница 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Страница 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Страница 22: ...e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 1 1 6 H S 0 5 3 1 0 2 0 0 1 1 5 7 4 1 Subtract 08 static for 2 filter TABLE 9 INDOOR BLOWER PERFORMANCE CFM 230V 460V P S E H n I 2 O 1 1 6...

Страница 23: ...i S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2...

Отзывы: