START  UP

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil
with a dish washing detergent.

CRANKCASE HEATERS

SH611-B and -C are provided with compressor
crankcase heat.  All other models are not provided with
crankcase heat.  They are either single phase or the
system refrigerant charge is not of sufficient quantity to
require crankcase heat.

The SH611-B and -C models have a wrap around type
heater located on the lower section of the compressor
housing.  This is an on/off heater that is controlled by
the compressor contactor.

The label in Figure 13 is affixed to all SH611-B and -C
units detailing start up procedure.  This is 

very

important. 

 Please read carefully

.

HIGH PRESSURE SWITCH

All models are supplied with a remote reset high
pressure switch.  If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.  All three
phase units incorporate a phase monitor to ensure proper
field wiring.  See the “Phase Monitor” section later in
this manual.

Verification of 

proper rotation

 must be made any time a

compressor is changed or rewired.  If improper rotation
is corrected at this time there will be no negative impact
on the durability of the compressor.  However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor’s
internal protector will trip.

All three phase ZR3 compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotations, as well as, substantially
reduced current draw compared to tabulate values.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

FIGURE  13

START UP LABEL

IMPORTANT

7961-411

These procedures must be followed at
initial start up and at any time power has
been removed for 12 hours or longer.

To prevent compressor damage which
may result from the presence of liquid
refrigerant in the compressor crankcase:

1.

Make certain the room thermostat is in
the “off” position. (The compressor is not
to operate.)

2.

Apply power by closing the system
disconnect switch. This energizes the
compressor heater which evaporates
the liquid refrigerant in the crankcase.

3.

Allow 4 hours or 60 minutes per pound
of refrigerant in the system as noted on
the unit rating plate, whichever is
greater.

4.

After proper elapsed time the thermostat
may be set to operate the compressor.

5.

Except as required for safety while
servicing, 

do not open system

disconnect switch.

Содержание SH611

Страница 1: ...NSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH611 Manual 2100 411G Supersedes 2100 411F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 19...

Страница 2: ...d CFM and Rated ESP 22 Table 9 Indoor Blower Performance 22 Table 10 Maximum ESP of Operation 22 Table 11 Pressure Table Cooling 23 Table 12 Pressure Table Heating 23 Getting Other Information and Pub...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...2 0 2 2 3 8 0 6 2 8 6 4 2 7 0 0 2 1 5 MODEL NUMBER CONTROL MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Dampe...

Страница 5: ...Manual 2100 411G Page 5 of 23 FIGURE 1 UNIT DIMENSIONS SH611...

Страница 6: ...an adequate duct system than a straight air conditioning unit All duct work supply and return must be properly sized for the design airflow requirement of the equipment Air Conditioning Contractors o...

Страница 7: ...using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The filter slides into position...

Страница 8: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 3 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Страница 9: ...796 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Supply flange Side view of wall w...

Страница 10: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 11: ...Manual 2100 411G Page 11 of 23 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 12: ...Manual 2100 411G Page 12 of 23 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 13: ...Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits requir...

Страница 14: ...pment at the time of manufacture is not designated for any specific destination of the country and are installed in areas not approaching the lower outdoor temperature range outdoor thermostats are no...

Страница 15: ...ermostat This is done to maximize efficiency by utilizing the heat pump to bring the FIGURE 12 ELECTRIC HEAT HOLD OFF WIRING 15 20KW 1 PH 3 PH FIGURE 11 ELECTRIC HEAT HOLD OFF WIRING 4 10KW 1 PH 6 9KW...

Страница 16: ...uired 5 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Removing...

Страница 17: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Страница 18: ...the system operating pressures can be observed Pressure tables can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure ta...

Страница 19: ...r time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch...

Страница 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Страница 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Страница 22: ...e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 1 1 6 H S 0 5 3 1 0 2 0 0 1 1 5 7 4 1 Subtract 08 static for 2 filter TABLE 9 INDOOR BLOWER PERFORMANCE CFM 230V 460V P S E H n I 2 O 1 1 6...

Страница 23: ...i S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2...

Отзывы: