Manual 2100-752B
Page
48 of 49
1
Values listed are with ventilation package disabled
2
Return air temperature °F @ Default airflow (1300 CFM) for AC tests and Balanced Climate airflow (910 CFM) for
dehumidification tests
3
Suction pr/- 4 psi, Discharge pr/- 10 psi
DB/WB
2
OD Temp.
75°F
85°F
95°F
Mode
A/C
Dehum
A/C
Dehum
A/C
Dehum
075/64.1
(55% RH)
Total Cooling Btuh
49,500
17,800
46,700
13,700
43,600
8,000
Sensible Btuh
34,200
3,900
32,800
1,100
31,200
-3,200
S/T
0.691
0.219
0.702
0.080
0.716
0
Latent Btuh
15,300
13,900
13,900
12,600
12,400
11,200
Lbs. H20/hr.
14.4
13.1
13.1
11.9
11.7
10.6
Supply Air DB
54.7
71.9
55.6
74.5
56.5
78.2
Supply Air WB
53.1
58.7
53.8
60.1
54.5
61.9
Suction PSIG
3
127
116
129
119
130
121
Discharge PSIG
3
339
292
382
323
428
354
75/65.5
(60% RH)
Total Cooling Btuh
50,300
20,200
47,700
15,100
44,600
9,300
Sensible Btuh
32,200
3,500
30,700
0
29,100
-4,400
S/T
0.640
0.173
0.644
0.000
0.652
0
Latent Btuh
18,100
16,700
17,000
15,100
15,500
13,700
Lbs. H20/hr.
17.1
15.8
16
14.2
14.6
12.9
Supply Air DB
56
72.4
56.9
75.6
57.8
79.3
Supply Air WB
54.5
59.6
55.3
61.3
56
63.1
Suction PSIG
3
129
119
132
122
133
124
Discharge PSIG
3
341
296
384
326
430
357
75/66.7
(65% RH)
Total Cooling Btuh
51,300
21,500
48,600
16,500
45,600
10,700
Sensible Btuh
30,200
2,400
28,700
-1,200
27,100
-5,500
S/T
0.589
0.112
0.591
0
0.594
0
Latent Btuh
21,100
19,100
19,900
17,700
18,500
16,200
Lbs. H20/hr.
19.9
18
18.8
16.7
17.5
15.3
Supply Air DB
57.3
73.5
58.1
76.6
59.1
80.3
Supply Air WB
56
60.7
56.8
62.4
57.5
64.2
Suction PSIG
3
132
122
134
125
136
127
Discharge PSIG
3
344
300
387
330
433
361
Q48A4D Cooling and Dehumidification Application Data