SEQUENCE OF OPERATION

Cooling

 – Circuit R-Y makes the thermostat pull in 

the compressor contactor starting the compressor 

and outdoor motor.  The G (indoor motor) circuit 

is automatically completed on any call for cooling 

operation, or can be energized by manual fan switch on 

subbase for constant air circulation.

Heating

 – Circuit is completed for R-W1 on each 

heating “on” cycle, energizing the electric heat contactor.  

R-G also makes starting indoor blower motor.
Second stage heat – Energized circuit R-W2 and the 

electric heat contactor for the second bank of heaters (if 

equipped) is energized.

High / Low Pressure control

 provides protection for 

the compressor.  In the event system pressures go 

above 600 PSI or below 40 PSI in cooling mode the 

compressor will be stopped.  This will activate the 

red light located in the control panel.  The lockout 

circuit will hold compressor off line.  When the system 

problem is corrected, the unit operation can be restored 

by turning of the main power supply off and then back 

on, or reset the room thermostat.  The low pressure 

control has a bypass to eliminate nuisance lockout on 

cold start up.  Factory set to 2 minutes.

Dehumidification / Reheat Circuit 

– Both cooling and 

heating take precedence over dehumidification.

Reheat Circuit 

– There is a small capillary tube 

inserted between the reheat coil return line and suction 

line that will prevent liquid from accumulating in the 

reheat coil when it is inactive.  This drain does not 

affect the normal operation of the system.
There is a check valve located in the reheat coil return 

line.  It has a soft spring to hold the ball on the seat. 

This will make the method of checking the ball freedom 

with a magnet difficult.  Refer to Figures 24 and 25 for 

the location of the check valve and drain back capillary.
When the system is operating in the dehumidification mode 

the suction pressure will be reduced by 4 to 8 psig and the 

discharge pressure will be reduced by 19 to 22 psig.

CRV / QERV OPERATION

QERV is energized by applying 24 VAC to the “F” 

terminal of the low voltage terminal strip on units 

with “X” climate control option.  It is energized by the 

“A” terminal of the thermostat on units with “E, J or 

K” climate control option.  On climate option “I” it is 

energized by the brown/white wire at the CO

2

 controller.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on 

all units so that the system operating pressures can be 

observed.  Pressure curves can be found later in the 

manual covering all models on both cooling and heating 

cycles.  It is imperative to match the correct pressure 

curve to the unit by model number.  Upper and lower  

service doors must be attached to obtain proper reading.

FIGURE  23 

CO

2

 CONTROLLER – FACTORY SET TO 1000 PPM

PRESS UP AND DOWN

ARROWS TO ENTER

CONFIGURATION MODE

USE ARROWS TO SELECT

SETTING. PUSH MIDDLE

BUTTON TO CHANGE.

CONTROLLER WILL 

SHOW SET.

NOTE: MENU

JUMPER MUST

BE SET TO "ON"

TO CHANGE ANY

SETTINGS WITH 

THE FRONT BUTTONS.

TO LOCK THE CO2

CONTROLLER MOVE

JUMPER TO "OFF" AFTER

IT HAS BEEN CONFIGURED

Settings Recommended

Default

RON

1000

1000

ROF

950

950

DSP

C

CT

UNI

US

US

COL

Not Used

COH

Not Used

TOL

Not Used

TOH

Not Used

BAR See Instrution with Controller 

For High Altitude Installations

CAL

Used for Field Calibration

MIS-3326

Содержание Q24A2DA

Страница 1: ...Inc Bryan Ohio 43506 www bardhvac com Manual No 2100 602A Supersedes 2100 602 Date 7 25 17 Q TECTM SERIES PACKAGED AIR CONDITIONER Models Q24A2DA Q24A2DB Q24A2DC Q30A2DA Q30A2DB Q30A2DC Q36A2DA Q36A2...

Страница 2: ...ic Heat Table 5 Table 2 Electrical Specifications 6 Table 3 Operating Voltage Range 20 Table 4 Wall Thermostats 22 Table 5A Troubleshooting 37 Table 5B Dehumidification Relay Logic Board 37 Table 6 Fa...

Страница 3: ...ummer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditi...

Страница 4: ...l and reheat if applicable VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commercial Ventilator Motorized w Exhaust Spring Return P Commercial Ventilator Motorized w Ex...

Страница 5: ...08V 1 240V 1 208V 1 480V 3 240V 1 208V 1 240V 1 208V 1 480V 3 KW BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH 5 0 16 380 12 290 16 380 12 290 6 0 20 500 15...

Страница 6: ...60 25 6 10 10 10 Q42A2DB0Z B06 B09 B15 230 208 3 1 1 1 1 26 26 35 53 35 35 35 60 8 8 8 6 10 10 10 10 Q42A2DC0Z C06 C09 C15 460 3 1 1 1 1 13 14 18 27 15 15 20 30 14 14 12 10 14 14 12 10 Q48A2DA0Z A05 A...

Страница 7: ...Manual 2100 602A Page 7 of 41 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Страница 9: ...eparate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attache...

Страница 10: ...Manual 2100 602A Page 10 of 41 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...justable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension can be...

Страница 12: ...rom the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be ins...

Страница 13: ...REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 O...

Страница 14: ...Manual 2100 602A Page 14 of 41 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 16: ...Manual 2100 602A Page 16 of 41 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 17: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 19: ...eck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necess...

Страница 20: ...t Depending on the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection w...

Страница 21: ...at or cool modes to maintain the temperature set on the thermostat The CO2 controller will energize the vent option and the ID blower when the room CO2 levels rise over set level Default CO2 set point...

Страница 22: ...2 stage Cool 2 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover with Humidity and Occupancy Sensor BACnet CSB9E THO 3 stage Cool 3 stage Heat Programma...

Страница 23: ...for 2 stage electronic heat on 15 KW models operation and for Humidity Control output D Yo to be active 4 3 Must be configured for Heat Cool and No Economizer for proper 5 R C 6 W1 E Y1 D YO A G 12 4...

Страница 24: ...ED THERMOSTAT WIRING DIAGRAM E THERMOSTAT OPTION Red White Blue 9 D YO 10 Orange A 7 PART 8403 060 5 Black White G 3 Brown White 6 8 4102 074 11 R Y1 Plug 2 C 1 Yellow 4 2 12 Brown W1 E Temp and Humid...

Страница 25: ...hite I Thermostat Option Orange Red White Blue Out 6 Temp and Humidity Part 8403 060 5 Black White G 3 11 8 4102 075 A R Y1 Plug 2 C W2 1 Yellow 12 Purple White Brown 7 A Brown White 2 4 CO Controller...

Страница 26: ...WIRING DIAGRAM J OR K THERMOSTAT OPTION Y1 Orange A Blue 9 1 6 SC D W2 K CS9BE THOC 5 Black White G 3 Brown White 11 8 4102 077 4 R 10 Plug 2 C Red White Yellow 2 12 Purple White Brown 7 SC W1 E Temp...

Страница 27: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Страница 28: ...prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light...

Страница 29: ...lockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer t...

Страница 30: ...pected from the outside of the building by looking through the outdoor grille The mist eliminator can be serviced from the outside by using a vacuum cleaner The outdoor grille must be removed Use the...

Страница 31: ...te slide out of the QERV The mist eliminator can be seen through the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and...

Страница 32: ...Manual 2100 602A Page 32 of 41 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 33: ...Manual 2100 602A Page 33 of 41 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 34: ...valve located in the reheat coil return line It has a soft spring to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 24 and 2...

Страница 35: ...Manual 2100 602A Page 35 of 41 FIGURE 24 AIR CONDITIONING MODE CIRCUIT DIAGRAM...

Страница 36: ...Manual 2100 602A Page 36 of 41 FIGURE 25 DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Страница 37: ...terminal and within 10 seconds power should appear between CC C Remove speed up jumper after 10 seconds Contactor defective Check for open or shorted coil winding Replace contactor Motor defective Ch...

Страница 38: ...t s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 39: ...ion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and...

Страница 40: ...y ratings were determined by testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the...

Страница 41: ...25 300 38 500 24 600 37 000 24 000 35 400 23 300 33 900 22 500 32 300 21 800 Q42A2D 75 DB 62 WB Total Cooling Sensible Cooling 40 400 29 500 39 000 29 000 37 600 28 500 36 200 27 800 34 800 27 300 33...

Отзывы: