Manual 2100-602A
Page
20 of 41
OPTIONAL CLIMATE CONTROLS
SEQUENCE OF OPERATION
The standard Climate Control
Option X
is a remote
thermostat connection terminal block. See Figure 17 for
wiring diagram. Compatible thermostats are listed in
Table 4.
The Climate Control
Option E
is an electronic,
programmable thermostat with humidistat. The subbase
of the thermostat is factory wired to the front panel of
the unit. See Figure 18 for wiring diagram. Compatible
for use with Energy Recovery Ventilator. The thermostat
can be set in the heat, cool or automatic mode. When
the thermostat is set in the heat mode, it can heat only to
maintain the temperature set on the thermostat. When
the thermostat is set in the cool mode, it can cool only
to maintain the temperature set on the thermostat.
When the thermostat is set in the automatic mode, the
thermostat can change automatically to the heat or cool
modes to maintain the temperature set on the thermostat.
The Climate Control
Option I
is an electronic,
programmable thermostat with humidistat and a CO
2
controller. The subbase of the thermostat and CO
2
controller are factory wired to the front panel of the unit.
See Figure 19 for wiring diagram. The thermostat can
be set in the heat, cool or automatic mode. When the
thermostat is set in the heat mode, it can heat only to
maintain the temperature set on the thermostat. When
the thermostat is set in the cool mode, it can cool only
to maintain the temperature set on the thermostat.
When the thermostat is set in the automatic mode, the
thermostat can change automatically to the heat or cool
modes to maintain the temperature set on the thermostat.
WIRING – MAIN POWER
Refer to the unit rating plate and/or Table 2 for wire
sizing information and maximum fuse or “HACR
Type” circuit breaker size. Each unit is marked with
a “Minimum Circuit Ampacity”. This means that the
field wiring used must be sized to carry that amount
of current. Depending on the installed KW of electric
heat, there may be two field power circuits required. If
this is the case, the unit serial plate will so indicate. All
models are suitable only for connection with copper
wire. Each unit and/or wiring diagram will be marked
“Use Copper Conductors Only”. These instructions
MUST BE
adhered to. Refer to the National Electrical
Code (NEC) for complete current carrying capacity
data on the various insulation grades of wiring material.
All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper)
for all models, including the most commonly used heater
sizes. Also shown are the number of field power circuits
required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR Type” circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection, and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.
FIGURE 15
COMPONENT LOCATION
TABLE 3
OPERATING VOLTAGE RANGE
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
See “Start Up” section for information on three phase
scroll compressor start-ups.
The field wiring connections are located behind the
top and hinged panel in the circuit breaker panel. See
Figure 15.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 PHASE AND 3 PHASE EQUIPMENT
DUAL PRIMARY VOLTAGE TRANSFORMERS.
All Equipment leaves the factory wired on 240V tap.
For 208V operation, reconnect from 240V to 208V tap.
The acceptable operating voltage range for the 240 and
208V taps are as noted in Table 3.
TAP
RANGE
240V
253 – 216
208V
220 – 187
DEHUMIDIFICATION
CONTROL
(OPTIONAL)
UNIT
MOUNTED
THERMOSTAT
LOCATION
ELECTRIC
HEATERS
CIRCUIT
BREAKER PANEL
& CONTROLS
INDOOR
BLOWER
SIDE FIELD WIRE
ENTRANCE
LOWER
CONTROL
PANEL
REMOTE
THERMOSTAT
TERMINAL
BLOCK
Содержание Q24A2DA
Страница 7: ...Manual 2100 602A Page 7 of 41 FIGURE 1 UNIT DIMENSIONS...
Страница 10: ...Manual 2100 602A Page 10 of 41 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...
Страница 14: ...Manual 2100 602A Page 14 of 41 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 16: ...Manual 2100 602A Page 16 of 41 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 32: ...Manual 2100 602A Page 32 of 41 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...
Страница 35: ...Manual 2100 602A Page 35 of 41 FIGURE 24 AIR CONDITIONING MODE CIRCUIT DIAGRAM...
Страница 36: ...Manual 2100 602A Page 36 of 41 FIGURE 25 DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...