Manual 2100-600C
Page
38 of 38
MODEL
RETURN
AIR
TEMP.
PRESSURE
AIR TEMPERATURE ENTERING OUTDOOR COIL
75
80
85
90
95
100
105
110
115
Q24A2
75 DB
62 WB
Low Side
High Side
116
314
119
335
122
358
124
380
127
404
130
428
132
452
134
478
136
503
80 DB
67 WB
Low Side
High Side
124
322
127
344
130
367
133
390
134
414
139
439
141
464
143
490
145
516
85 DB
72 WB
Low Side
High Side
128
333
131
356
135
380
138
404
141
428
144
454
146
480
148
507
150
534
Q30A2
75 DB
62 WB
Low Side
High Side
119
321
121
344
122
368
124
391
127
414
129
437
131
460
133
484
135
507
80 DB
67 WB
Low Side
High Side
127
329
129
353
131
377
133
401
136
425
138
448
140
472
142
496
144
520
85 DB
72 WB
Low Side
High Side
131
341
134
365
136
390
138
415
141
440
143
464
145
489
147
513
149
538
Q36A2
75 DB
62 WB
Low Side
High Side
112
347
118
373
123
401
128
428
132
454
136
481
137
508
139
534
140
561
80 DB
67 WB
Low Side
High Side
120
356
126
383
132
411
137
439
141
440
145
493
147
521
149
548
150
575
85 DB
72 WB
Low Side
High Side
124
368
130
396
137
425
142
454
146
482
150
510
152
539
154
567
155
595
Q42A2
75 DB
62 WB
Low Side
High Side
116
356
119
380
122
406
124
431
127
457
129
483
131
509
133
535
135
563
80 DB
67 WB
Low Side
High Side
124
365
127
390
130
416
133
442
136
469
138
495
140
522
142
549
144
577
85 DB
72 WB
Low Side
High Side
128
378
131
404
135
431
138
457
141
485
143
512
145
540
147
568
149
597
Q48A2
75 DB
62 WB
Low Side
High Side
119
343
121
366
122
390
124
414
127
440
129
466
131
493
134
522
136
551
80 DB
67 WB
Low Side
High Side
127
352
129
375
131
400
133
425
135
450
138
478
140
506
143
535
145
565
85 DB
72 WB
Low Side
High Side
131
364
134
388
136
414
138
440
141
467
143
495
145
524
148
554
150
585
Q60A2
75 DB
62 WB
Low Side
High Side
112
362
116
386
120
410
122
436
124
462
125
488
126
514
126
541
125
568
80 DB
67 WB
Low Side
High Side
120
371
124
396
128
421
130
447
131
474
134
500
135
527
135
555
134
583
85 DB
72 WB
Low Side
High Side
124
384
128
410
132
436
135
463
138
491
139
518
140
545
140
574
139
603
Low side pressure ± 4 psig
High side pressure ± 10 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct
operating charge being in the system, the charge should be removed, system evacuated and recharged to
serial plate instructions.
TABLE 7
COOLING PRESSURE
(ALL TEMPERATURES IN DEGREES F)
Содержание Q24A2-A
Страница 7: ...Manual 2100 600C Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...
Страница 10: ...Manual 2100 600C Page 10 of 38 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...
Страница 14: ...Manual 2100 600C Page 14 of 38 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 16: ...Manual 2100 600C Page 16 of 38 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 12C If Used...
Страница 32: ...Manual 2100 600C Page 32 of 38 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...