FAN BLADE SETTING DIMENSIONS
Any service work requiring removal or adjustment
in the fan and/or motor area will require that the
dimensions in Table 5 be checked and blade adjusted in
or out of the motor shaft accordingly.
j
Maximum ESP (inches WC) shown is with 1" thick disposable filter (reduced by .2 for 2" filter).
Rated CFM for ducted applications – required for maximum performance rating. To obtain full CFM on models Q36A2, Q42A2, Q48A2 and
Q60A2 connect the pink jumper wire (provided) to terminal #G2 and #Y on the low voltage terminal block located in the circuit breaker box.
Optional CFM – the unit is shipped from the factory set to operate at the optional CFM level shown. This provides lower operating sound
levels for non-ducted, free discharge applications. This reduces system capacity performance by approximately 2% at the same energy
efficiency.
Continuous fan CFM is the total air being circulated during continuous fan mode.
Model Q24A2 – when operating on 2nd stage heating the indoor air will increase to 1000 CFM.
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efficiency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specific situations
can affect the pressure readings, this information should
only be used by certified technicians as a guide for
evaluating proper system performance. They shall not
be used to adjust charge. If charge is in doubt, reclaim,
evacuate and recharge the unit to the serial plate charge.
FIGURE 28
FAN BLADE SETTING
TABLE 5
FAN BLADE DIMENSIONS
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjust itself to maintain
approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at
both 230/208 or 460 volts.
TABLE 6
INDOOR BLOWER PERFORMANCE
MODEL
DIMENSION A
(INCHES)
All
Q**A2
Models
.750
Model
Rated ESP
j
Max. ESP
Rated CFM
Optional
CFM
Continuous
CFM
CFM @
Max. ESP
Q24A2
.10
0.5
800
800
700
Q30A2
.15
0.8
1000
1000
910
Q36A2
.15
0.8
1200
1000
1000
1175
Q42A2
.15
0.8
1200
1000
1000
1175
Q48A2
.15
0.8
1400
1100
1100
1175
Q60A2
.20
0.5
1550
1250
1250
1400
Содержание Q24A2-A
Страница 7: ...Manual 2100 600C Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...
Страница 10: ...Manual 2100 600C Page 10 of 38 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...
Страница 14: ...Manual 2100 600C Page 14 of 38 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 16: ...Manual 2100 600C Page 16 of 38 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 12C If Used...
Страница 32: ...Manual 2100 600C Page 32 of 38 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...