INSTALLATION INSTRUCTIONS

MOUNTING THE UNIT

When installing a Q-TEC

 

unit near an interior wall on 

the left side, a minimum of 8 inches is required; 12 

inches is preferred.
When installing a Q-TEC

 

unit near an interior wall on 

the right side, a minimum of 18 inches is required as 

additional space is required to connect the side drain.  

If the rear condensate drain kit QCDS48 is used the 

minimum can be reduced to 8 inches.
This clearance is required to allow for the attachment of 

the unit to the sleeve and side trim pieces to the wall.
This unit is to be secured to the wall sleeve with 

mounting brackets provided.  The unit itself, the supply 

duct and the free blow plenum are suitable of “0” 

clearance to combustible material.
Following are the steps for mounting the Q-TEC

.  F

or 

reference see Figure 13A for external mounting bracket 

or 13B for internal bolt secured bracket (recommended).
  1.  Attach mounting brackets to the wall sleeve with 

screws provided.  Either use external mounting 

bracket (Fig. 13A) or internal bolt bracket (Fig. 13B).

  2.  Position the unit in front of the sleeve with the 

condenser section toward the sleeve.

  3.  Remove the locking screws from the wheels.  

Refer to Figure 14.

  4.  Roll the unit into the sleeve.  Make sure to check 

both sides of the unit as it is being rolled to 

keep it centered in the sleeve.  Also check the 

alignment to the mounting brackets.  This unit 

must be level from side to side.  If adjustments 

are necessary, shim up under the rollers with 

sheets of steel or any substance that is not 

affected by moisture.

  5.  Make sure the gasket on the rear of the unit is 

touching the sleeve across the top and down both 

sides.  This is a rain water seal.

  6.  Secure the mounting brackets to the unit with 

screws provided, #10 hex head sheet metal 

screws (Figure 13A) or use nut and washer to 

secure sleeve (Figure 13B).

  7.  Bottom trim extensions are provided for use when 

wall is less than 14 inches but greater than 10.5 

inches.  Secure to wall with screws (not provided).

  8.  Attach the bottom trim piece to the unit with the 

screws provided (dark colored).

  9.  Position side trim pieces to wall and attach with 

field supplied screws.  There are two long pieces 

and two short pieces supplied.  The long pieces 

are to enclose the gap behind the unit.  The 

short pieces are to fill the gap behind the cabinet 

extension or the free blow plenum box.  They 

may be cut to suit your ceiling height or overlap 

the unit side trim.  There is sufficient length to 

trim up to a 10'2" ceiling.

NOTE: If the exterior wall thickness is between 5  

inches to 10.5 inches, a side trim extension  

piece kit, model QSTX42, is available.

REMOVE SCREWS FROM WHEELS 

BEFORE ROLLING INTO PLACE

FIGURE  14

REMOVING LOCKING SCREWS FROM WHEELS

Содержание Q24A2-A

Страница 1: ...n Ohio 43506 www bardhvac com Manual No 2100 600C Supersedes 2100 600B Date 5 25 18 Q TECTM SERIES PACKAGED AIR CONDITIONER Models Q24A2 A Q24A2 B Q24A2 C Q30A2 A Q30A2 B Q30A2 C Q36A2 A Q36A2 B Q36A2...

Страница 2: ...ade Setting 37 Tables Table 1 Factory Built In Electric Heat Table 5 Table 2 Electrical Specifications 6 Table 3 Operating Voltage Range 20 Table 4 Wall Thermostats 22 Table 5 Fan Blade Dimensions 37...

Страница 3: ...ummer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditi...

Страница 4: ...reheat if applicable VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate E Economizer Not available on dehumidification versions P Commercial Ventilator Motorized w Exhaust P...

Страница 5: ...08V 1 240V 1 208V 1 480V 3 240V 1 208V 1 240V 1 208V 1 480V 3 KW BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH 5 0 16 380 12 290 16 380 12 290 6 0 20 500 15...

Страница 6: ...60 25 6 10 10 10 Q42A2 B0Z B06 B09 B15 230 208 3 1 1 1 1 26 26 35 53 35 35 35 60 8 8 8 6 10 10 10 10 Q42A2 C0Z C06 C09 C15 460 3 1 1 1 1 13 14 18 27 15 15 20 30 14 14 12 10 14 14 12 10 Q48A2 A0Z A05 A...

Страница 7: ...Manual 2100 600C Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down the...

Страница 9: ...nstructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularl...

Страница 10: ...Manual 2100 600C Page 10 of 38 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...ly adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension c...

Страница 12: ...rom the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be ins...

Страница 13: ...REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 O...

Страница 14: ...Manual 2100 600C Page 14 of 38 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 16: ...Manual 2100 600C Page 16 of 38 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 12C If Used...

Страница 17: ...OVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN BUT AT A S...

Страница 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 19: ...eck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necess...

Страница 20: ...GE WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All Equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable...

Страница 21: ...is set in the cool mode it can cool only to maintain the temperature set on the thermostat When the thermostat is set in the automatic mode the thermostat can change automatically to the heat or cool...

Страница 22: ...nal Auto or Manual changeover 8403 060 1120 445 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover 8403 082 VT8600U5500B 2 stage Cool 2 sta...

Страница 23: ...ons are installed 1 7 1 2 3 4 5 6 7 8 9 11 12 10 F G Y2 Y1 W2 C R W1 E 1 9 2 8 1 G 3 3 Y2 W1 E R C W2 Y1 A G R C Rc W W2 Y Y2 6 5 4 2 8403 082 or 8403 084 BROWN WHITE BROWN BLUE BLACK WHITE RED WHITE...

Страница 24: ...the CS2000A or other field provided means to control ventilation must be used if any of the motorized ventilation options are installed W1 E Orange 2 Yellow Brown 7 G 12 W2 Red White Blue 9 10 1 6 5...

Страница 25: ...FIGURE 19 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION W1 E 8403 060 D THERMOSTAT OPTION Y2 12 Plug 2 Brown G Purple Orange C Blue 9 10 6 5 Black White A 3 11 8 4102 070 4 R Y1 7 Red Wh...

Страница 26: ...Orange 2 Red White Blue 9 10 6 Part 8403 060 5 Black White G 3 11 8 R Y1 Plug 2 C W2 1 Yellow 12 Purple Brown 7 A Brown White 2 Y2 Black White Red White Brown White Out Controller Red White W1 E 4 3 4...

Страница 27: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Страница 28: ...t and the compressor contactor is allowed to energize If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply l...

Страница 29: ...a compressor call is lost the time period must expire before a new call will be initiated High Pressure Detection High pressure switch monitoring allows for a lockout condition in a situation where th...

Страница 30: ...e 280 second mark in less than second Normal operation will resume after power is reset or after the unit has been in test mode for at least 5 minutes Brownout Protection with Adjustment Brownout prot...

Страница 31: ...OR COMMERCIAL ROOM VENTILATOR Option Before starting make sure the power has been turned off The return air grille panel must be removed The economizer EIFM or commercial room ventilator CRV can be se...

Страница 32: ...Manual 2100 600C Page 32 of 38 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 33: ...Manual 2100 600C Page 33 of 38 FIGURE 23 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 34: ...bank of heaters if equipped is energized High Low Pressure control provides protection for the compressor In the event system pressures go above 600 PSI or below 15 PSI in cooling mode the compressor...

Страница 35: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 36: ...n d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and ve...

Страница 37: ...REFRIGERANT CHARGE This unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigeran...

Страница 38: ...2A2 75 DB 62 WB Low Side High Side 116 356 119 380 122 406 124 431 127 457 129 483 131 509 133 535 135 563 80 DB 67 WB Low Side High Side 124 365 127 390 130 416 133 442 136 469 138 495 140 522 142 54...

Отзывы: