Manual 2100-653A
Page
42 of 44
FAN BLADE SETTING DIMENSIONS
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
in Table 7 be checked and blade adjusted in or out of
the motor shaft accordingly.
Maximum ESP (inches WC) shown is with 1" thick disposable filter (reduced by .2 for 2" filter).
Rated CFM for ducted applications – required for maximum performance rating. To obtain full CFM on models Q36H3D, Q43H3D, Q48H3D
and Q60H3D connect the pink jumper wire (provided) to terminal #G2 and #Y on the low voltage terminal block located in the circuit breaker
box.
Optional CFM – the unit is shipped from the factory set to operate at the optional CFM level shown. This provides lower operating sound
levels for non-ducted, free discharge applications. This reduces system capacity performance by approximately 2% at the same energy
efficiency.
Continuous fan CFM is the total air being circulated during continuous fan mode.
Indoor airflow during periods of high humidity when system is operating under control of optional humidistat for maximum humidity reduction.
o
Model Q24H3D – when operating on 2nd stage heating the indoor air will increase to 1000 CFM.
R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efficiency ratings were determined by testing with
this refrigerant charge quantity (see Table 8).
The following pressure tables show nominal
pressures for the units. Since many installation
specific situations can affect the pressure readings,
this information should only be used by certified
technicians as a guide for evaluating proper system
performance. They shall not be used to adjust charge.
If charge is in doubt, reclaim, evacuate and recharge
the unit to the serial plate charge.
FIGURE 31
Fan Blade Setting
TABLE 7
Fan Blade Dimensions
NOTE:
These units are equipped with a variable speed (ECM) indoor motor that automatically adjust itself to maintain approximately
the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at both 230/208 or 460 volts.
TABLE 9
Indoor Blower Performance
MODEL
DIMENSION A
(INCHES)
All
Q**H3D
Models
.750
Model
Rated
ESP
Max. ESP
Rated CFM
Optional
CFM
Continuous
CFM
CFM @
Max. ESP
Dehum.
CFM
Q24H3D
o
.10
0.5
800
N/A
800
700
800
Q30H3D
.15
0.8
1000
N/A
1000
910
1000
Q36H3D
.15
0.8
1200
1000
1000
1175
1000
Q43H3D
.15
0.8
1200
1000
1000
1175
1000
Q48H3D
.15
0.8
1400
1100
1100
1175
1250
Q60H3D
.20
0.5
1550
1250
1100
1400
1250
TABLE 8
Subcooling at Liquid Line
MODEL RATED
CFM
95°F OD
TEMPERATURE
82°F OD
TEMPERATURE
Q24H3D
800
23 - 25
22 - 24
Q30H3D
1000
23 - 25
23 - 25
Q36H3D
1200
19 - 21
17 - 19
Q43H3D
1200
16 - 18
15 - 17
Q48H3D
1400
19 - 21
19 - 21
Q60H3D
1550
22 - 24
22 - 24
Содержание Q-TEC Q30H3DA
Страница 6: ...Manual 2100 653A Page 6 of 44 FIGURE 1 Unit Dimensions...
Страница 9: ...Manual 2100 653A Page 9 of 44 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum...
Страница 13: ...Manual 2100 653A Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 653A Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 653A Page 31 of 44 FIGURE 22 Fresh Air Damper Removal Mounting Screw...