Manual 2100-653A
Page
4 of 44
TABLE 1
Factory Built-In Electric Heat
(See Table 2 for Available Electric Heat by Unit Model)
Nominal
KW
At 240V
At 208V
At 480V
At 460V
KW
1-Ph
Amps
3-Ph
Amps
BTUH
KW
1-Ph
Amps
3-Ph
Amps
BTUH
KW
3-Ph
Amps
BTUH
KW
3-Ph
Amps
BTUH
5.0
5.0
20.8
17,065
3.75
18.0
12,799
6.0
6.0
14.4
20,478
4.50
12.5
15,359
6.0
7.2
20,478
5.52
6.9
18,840
9.0
9.0
21.7
30,717
6.75
18.7
23,038
9.0
10.8
30,717
8.28
10.4
28,260
10.0
10.0
41.7
34,130
7.50
36.1
25,598
12.0
12.0
28.9
40,956
9.00
25.0
30,717
12.0
14.4
40,956 11.04
13.9
37,680
15.0
15.0
62.5
36.1
51,195 11.25
54.1
31.2
38,396
15.0
18.0
51,195 13.80
17.3
47,099
These electric heaters are available in 230/208V units only.
These electric heaters are available in 480V units only.
Q-TEC
S
eries General Information
Q-TEC MODEL NOMENCLATURE
INTERNAL
CONTROLS
X - Standard
• High Pressure Switch
• Low Pressure Switch
• Compressor Control
Module w/Time Delay
E - Low Ambient Control
Q - Outdoor Thermostat
R - Low Ambient Control
& Outdoor Thermostat
FILTER OPTIONS
X - 1" Fiberglass
(Standard)
F - 2" Fiberglass
P - 2" Pleated
Q
36
H
3
D
A
10
X
X
X
X
X
X
CAPACITY
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
43 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
KW
0Z - 0KW
05 - 5KW
06 - 6KW
09 - 9KW
10 -10KW
12 -12KW
15 -15KW
COIL OPTIONS
X - Standard
1 - Phenolic coated
evaporator*
2 - Phenolic coated
condenser
3 - Phenolic coated
evaporator &
condenser coil*
*and reheat if
applicable
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard)
B - Blank-off Plate
V - Commercial Ventilator - Motorized w/Exhaust Spring Return
P - Commercial Ventilator - Motorized w/Exhaust Power Return
R - Energy Recovery Ventilator w/Independent Intake & Exhaust Control
REVISION
VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
CLIMATE CONTROL OPTIONS
X - None
E - Electronic/Prog/Humidistat
I - Electronic/Prog/Humidistat/CO
2
J - CS9BE-THO (BACnet IP or Ethernet)
K - CS9BE-THOC w/CO
2
(BACnet IP or Ethernet)
COLOR
V - Platinum w/Slate
Front (Vinyl)
X - Beige paint
4 - Gray paint
DEHUMIDIFICATION
REHEAT CYCLE
HEAT
PUMP
MODEL
NUMBER
NOTE:
If “X” control option is selected, thermostat and humidistat, if applicable, or DDC control system must be field supplied.
8403-060 Thermostat
8403-060 Thermostat & 8403-067 CO
2
Controller
Not available with "X" control option, and for all other climate control options is a single sensor that functions with unit-mounted
thermostat.
Содержание Q-TEC Q30H3DA
Страница 6: ...Manual 2100 653A Page 6 of 44 FIGURE 1 Unit Dimensions...
Страница 9: ...Manual 2100 653A Page 9 of 44 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum...
Страница 13: ...Manual 2100 653A Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 653A Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 653A Page 31 of 44 FIGURE 22 Fresh Air Damper Removal Mounting Screw...