CHECKING TEMPERATURE SENSOR

1.  Disconnect temperature sensor from board and 

from outdoor coil.

2.  Use an ohmmeter to measure the resistance of the 

sensor.  Also use ohmmeter to check for short or 
open.

3.  Check resistance reading to chart of resistance use 

sensor ambient temperature.  (Tolerance of part is 
±10%.)

4.  If sensor resistance reads very low, then sensor is 

shorted and will not allow proper operation of the 
heat pump control.

5.  If sensor is out of tolerance, shorted, open or reads 

very low ohms, it should be replaced.

TABLE 6 

Temperature (F) vs Resistance (R) of Temperature Sensor

F

R

F

R

F

R

F

R

-25.0

196871

13.0

56985

53.0

19374

89.0

7507

-24.0

190099

14.0

55284

52.0

18867

90.0

7334

-23.0

183585

15.0

53640

53.0

18375

91.0

7165

-22.0

177318

16.0

52051

54.0

17989

92.0

7000

-21.0

171289

17.0

50514

55.0

17434

93.0

6840

-20.0

165487

18.0

49028

56.0

16984

94.0

6683

-19.0

159904

19.0

47590

57.0

16547

95.0

6531

-18.0

154529

20.0

46200

58.0

16122

96.0

6383

-17.0

149355

21.0

44855

59.0

15710

97.0

6239

-16.0

144374

22.0

43554

60.0

15310

98.0

6098

-15.0

139576

23.0

42295

61.0

14921

99.0

5961

-14.0

134956

24.0

41077

62.0

14544

100.0

5827

-13.0

130506

25.0

39898

63.0

14177

101.0

5697

-12.0

126219

26.0

38757

64.0

13820

102.0

5570

-11.0

122089

27.0

37652

65.0

13474

103.0

5446

-10.0

118108

28.0

36583

66.0

13137

104.0

5326

-9.0

114272

29.0

35548

67.0

12810

105.0

5208

-8.0

110575

30.0

34545

68.0

12492

106.0

5094

-7.0

107010

31.0

33574

69.0

12183

107.0

4982

-6.0

103574

32.0

32634

70.0

11883

108.0

4873

-5.0

100260

33.0

31723

71.0

11591

109.0

4767

-4.0

97064

34.0

30840

72.0

11307

110.0

4663

-3.0

93981

35.0

29986

73.0

11031

111.0

4562

-2.0

91008

36.0

29157

74.0

10762

112.0

4464

-1.0

88139

37.0

28355

75.0

10501

113.0

4367

0.0

85371

38.0

27577

76.0

10247

114.0

4274

1.0

82699

39.0

26823

77.0

10000

115.0

4182

2.0

80121

40.0

26092

78.0

9760

116.0

4093

3.0

77632

41.0

25383

79.0

9526

117.0

4006

4.0

75230

42.0

24696

80.0

9299

118.0

3921

5.0

72910

43.0

24030

81.0

9077

119.0

3838

6.0

70670

44.0

23384

82.0

8862

120.0

3757

7.0

68507

45.0

22758

83.0

8653

121.0

3678

8.0

66418

46.0

22150

84.0

8449

122.0

3601

9.0

64399

47.0

21561

85.0

8250

123.0

3526

10.0

62449

48.0

20989

86.0

8057

124.0

3452

11.0

60565

49.0

20435

87.0

7869

12.0

58745

50.0

19896

88.0

7686

Содержание Q-TEC Q30H3DA

Страница 1: ...ryan Ohio 43506 www bardhvac com Manual No 2100 653A Supersedes 2100 653 Date 10 11 17 Q TECTM SERIES PACKAGED HEAT PUMP Models Q24H3DA Q24H3DB Q24H3DC Q30H3DA Q30H3DB Q30H3DC Q36H3DA Q36H3DB Q36H3DC...

Страница 2: ...actory Built In Electric Heat 4 Table 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats and Controls 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of...

Страница 3: ...nd Summer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Con...

Страница 4: ...glass P 2 Pleated Q 36 H 3 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 43 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW COIL OPTIONS X Standard 1 Phenolic c...

Страница 5: ...25 30 30 14 10 10 10 14 10 10 10 Q48H3DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 37 62 87 87 50 70 90 90 8 6 3 3 10 8 8 8 37 37 37 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48...

Страница 6: ...Manual 2100 653A Page 6 of 44 FIGURE 1 Unit Dimensions...

Страница 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid see Figure 3 B The unit can be tipped forward and slid down the...

Страница 8: ...any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels a...

Страница 9: ...Manual 2100 653A Page 9 of 44 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum...

Страница 10: ...Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for duct...

Страница 11: ...rain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall When...

Страница 12: ...RE 11 Rear Drain Top View Wall maximum 10 for rear drain Couplings not shown but recommended for ease of removability for service Sleeve Drain Line Wall Bracket Unit FIGURE 10 Standard Rear Drain FIGU...

Страница 13: ...Manual 2100 653A Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 653A Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...13A Unit Mounting Method 1 Bottom Trim Piece Bottom Trim Extension Mounting Bracket Side Trim 2 PCS Side Trim 2 PCS Cabinet Side Panel Enlarged view of mounting bracket showing sleeve to cabinet atta...

Страница 18: ...sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim...

Страница 19: ...cuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conduct...

Страница 20: ...way valve are energized and the evaporator airflow is reduced The 3 way valve directs hot discharge gas into a separate desuperheating condenser circuit that reheats the conditioned air before it is...

Страница 21: ...ble speed ECM motor The motor is designed to maintain rated airflow up to the maximum static allowed It is important that the blower motor plugs are not plugged in or unplugged while the power is on F...

Страница 22: ...6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 17 Term Block 8403 081 8 WHEN USING 8403 081 TSJDT WITH 15KW HEAT 2 FACTORY INSTALLED JUMPER 1 G Thermostat Black White Red White Brown Blue Yellow Orange...

Страница 23: ...PER E TO W2 ON LOW VOLTAGE TERMINAL BLOCK WHEN Thermostat 12 3 With X Thermostat Option And Demand Ventilation USING 8403 081 THERMOSTAT WITH UNIT WITH 15KW OF HEAT Dehumidification Wiring Diagram MIS...

Страница 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White...

Страница 25: ...OUT CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White TEMP OUT Red White 8403 060 With I Thermostat Option Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E G A Y1 Red Yellow Orange Yellow Bl...

Страница 26: ...2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White Black Red Ye...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...e to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contacto...

Страница 29: ...he cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease in pulling unit out from the wall it may be des...

Страница 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q TEC Energy Recovery Ventilator Option Before starti...

Страница 31: ...Manual 2100 653A Page 31 of 44 FIGURE 22 Fresh Air Damper Removal Mounting Screw...

Страница 32: ...Manual 2100 653A Page 32 of 44 FIGURE 23 QERV Removal Mounting Screws Front Fill Lower Blower Assembly Blower Connector Power Connectors...

Страница 33: ...ft spring to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capi...

Страница 34: ...FOR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inac...

Страница 35: ...Upper and lower service doors must be attached to obtain proper reading This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader valve core r...

Страница 36: ...ll remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate defrost jumper sen...

Страница 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 38: ...V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into def...

Страница 39: ...74 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 138...

Страница 40: ...otor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop fi...

Страница 41: ...ion and orientation d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVA...

Страница 42: ...ty of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity see Table 8 The following pressure tables show nomina...

Страница 43: ...DB 67 WB Low Side High Side 134 341 135 363 136 387 137 412 138 439 140 468 141 498 143 530 144 563 146 598 85 DB 72 WB Low Side High Side 139 353 140 376 141 401 142 426 143 454 145 484 146 515 148...

Страница 44: ...1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X X X X X X X X X X 2nd Sta...