background image

Manual 2100-653A
Page 

36 of 44

DEFROST CYCLE

The defrost cycle is controlled by temperature and time 
on the solid state heat pump control.

When the outdoor temperature is 32°F or below, 
defrosting of the coil is required.  This coil temperature 
is sensed by the coil temperature sensor mounted near 
the bottom of the outdoor coil.  Once coil temperature 
reaches 30°F or below, the coil temperature sensor 
sends a signal to the control logic of the heat pump 
control and the defrost timer will start accumulating 
run time.

After 30, 60 or 90 minutes of heat pump operation at 
30°F or below, the heat pump control will place the 
system in the defrost mode.

During the defrost mode, the refrigerant cycle switches 
back to the cooling cycle, the outdoor motor stops, 
electric heaters are energized, and hot gas passing 
through the outdoor coil melts any accumulated frost.  
When the temperature rises to approximately 57°F, the 
coil temperature sensor will send a signal to the heat 
pump control which will return the system to heating 
operations automatically.

If some abnormal or temporary condition such as a high 
wind causes the heat pump to have a prolonged defrost 
cycle, the heat pump control will restore the system to 
heating operation automatically after 8 minutes.

The heat pump defrost control board has an option of 
30, 60 or 90-minute setting.  By default, this unit is 
shipped from the factory with the defrost time on the 
30 minute pin.  If circumstances require a change to 
another time, remove the jumper from the 30-minute 
terminal and reconnect to the desired terminal.  Refer 
to Figure 27.

There is a cycle speed up jumper on the control.  This 
can be used for testing purposes to reduce the time 
between defrost cycle operation without waiting for 
time to elapse.

Use a small screwdriver or other metallic object, 
or another ¼" QC, to short between the 

SPEEDUP

 

terminals to accelerate the HPC timer and initiate 
defrost.

Be careful not to touch any other terminals with the 
instrument used to short the 

SPEEDUP

 terminals.  

It may take up to 10 seconds with the 

SPEEDUP

 

terminals shorted for the speedup to be completed and 
the defrost cycle to start.

As soon as the defrost cycle kicks in, remove the 

shorting instrument from the SPEEDUP terminals.

  

Otherwise the timing will remain accelerated and 
run through the 1-minute minimum defrost length 
sequence in a matter of seconds and will automatically 
terminate the defrost sequence.

There is an initiate defrost jumper (sen jump) on the 
control that can be used at any outdoor ambient during 
the heating cycle to simulate a 0° coil temperature.

This can be used to check defrost operation of the unit 
without waiting for the outdoor ambient to fall into the 
defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a 

¼" QC terminal works best) the defrost sensor mounted 
on the outdoor coil is shunted out and will activate 
the timing circuit.  This permits the defrost cycle to 
be checked out in warmer weather conditions without 
the outdoor temperature having to fall into the defrost 
region.

In order to terminate the defrost test the 

SEN JMP

 

jumper must be removed.  If left in place too long, the 
compressor could stop due to the high pressure control 
opening because of  high pressure condition created 
by operating in the cooling mode with outdoor fan off.   
Pressure will rise fairly fast as there is likely no actual 
frost on the outdoor coil in this artificial test condition.

Low Pressure Switch Bypass Operation 

 The control 

has a selectable (SW1) low pressure switch bypass set 
up to ignore the low pressure switch input during the 
first (30, 60, 120 or 180 seconds) of “Y” operation.

After this period expires, the control will then monitor 
the low pressure switch input normally to make sure 
that the switch is closed during “Y” operation.

High Pressure Switch Operation 

 The control has a 

built-in lockout system that allows the unit to have the 
high pressure switch trip up to two times in 1 hour and 
only encounter a “soft” lockout.  A “soft” lockout shuts 
the compressor off and waits for the pressure switch to 
reset, which at that point then allows the compressor 
to be restarted as long as the 5-minute short cycle 
timer has run out.  If the high pressure switch trips a 
third time within 1 hour, the unit is in “hard” lockout 
indicating something is certainly wrong and it will not 
restart itself.

There is also a 5-minute compressor time delay 
function built into the HPC.  This is to protect the 
compressor from short cycling conditions.  The board’s 
LED will have a fast blink rate when in the compressor 
time delay.  In some instances, it is helpful to the 
service technician to override or speed up this timing 
period, and shorting out the 

SPEEDUP

 terminals for a 

few seconds can do this.

Содержание Q-TEC Q30H3DA

Страница 1: ...ryan Ohio 43506 www bardhvac com Manual No 2100 653A Supersedes 2100 653 Date 10 11 17 Q TECTM SERIES PACKAGED HEAT PUMP Models Q24H3DA Q24H3DB Q24H3DC Q30H3DA Q30H3DB Q30H3DC Q36H3DA Q36H3DB Q36H3DC...

Страница 2: ...actory Built In Electric Heat 4 Table 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats and Controls 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of...

Страница 3: ...nd Summer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Con...

Страница 4: ...glass P 2 Pleated Q 36 H 3 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 43 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW COIL OPTIONS X Standard 1 Phenolic c...

Страница 5: ...25 30 30 14 10 10 10 14 10 10 10 Q48H3DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 37 62 87 87 50 70 90 90 8 6 3 3 10 8 8 8 37 37 37 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48...

Страница 6: ...Manual 2100 653A Page 6 of 44 FIGURE 1 Unit Dimensions...

Страница 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid see Figure 3 B The unit can be tipped forward and slid down the...

Страница 8: ...any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels a...

Страница 9: ...Manual 2100 653A Page 9 of 44 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum...

Страница 10: ...Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for duct...

Страница 11: ...rain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall When...

Страница 12: ...RE 11 Rear Drain Top View Wall maximum 10 for rear drain Couplings not shown but recommended for ease of removability for service Sleeve Drain Line Wall Bracket Unit FIGURE 10 Standard Rear Drain FIGU...

Страница 13: ...Manual 2100 653A Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 653A Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...13A Unit Mounting Method 1 Bottom Trim Piece Bottom Trim Extension Mounting Bracket Side Trim 2 PCS Side Trim 2 PCS Cabinet Side Panel Enlarged view of mounting bracket showing sleeve to cabinet atta...

Страница 18: ...sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim...

Страница 19: ...cuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conduct...

Страница 20: ...way valve are energized and the evaporator airflow is reduced The 3 way valve directs hot discharge gas into a separate desuperheating condenser circuit that reheats the conditioned air before it is...

Страница 21: ...ble speed ECM motor The motor is designed to maintain rated airflow up to the maximum static allowed It is important that the blower motor plugs are not plugged in or unplugged while the power is on F...

Страница 22: ...6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 17 Term Block 8403 081 8 WHEN USING 8403 081 TSJDT WITH 15KW HEAT 2 FACTORY INSTALLED JUMPER 1 G Thermostat Black White Red White Brown Blue Yellow Orange...

Страница 23: ...PER E TO W2 ON LOW VOLTAGE TERMINAL BLOCK WHEN Thermostat 12 3 With X Thermostat Option And Demand Ventilation USING 8403 081 THERMOSTAT WITH UNIT WITH 15KW OF HEAT Dehumidification Wiring Diagram MIS...

Страница 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White...

Страница 25: ...OUT CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White TEMP OUT Red White 8403 060 With I Thermostat Option Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E G A Y1 Red Yellow Orange Yellow Bl...

Страница 26: ...2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White Black Red Ye...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...e to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contacto...

Страница 29: ...he cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease in pulling unit out from the wall it may be des...

Страница 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q TEC Energy Recovery Ventilator Option Before starti...

Страница 31: ...Manual 2100 653A Page 31 of 44 FIGURE 22 Fresh Air Damper Removal Mounting Screw...

Страница 32: ...Manual 2100 653A Page 32 of 44 FIGURE 23 QERV Removal Mounting Screws Front Fill Lower Blower Assembly Blower Connector Power Connectors...

Страница 33: ...ft spring to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capi...

Страница 34: ...FOR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inac...

Страница 35: ...Upper and lower service doors must be attached to obtain proper reading This unit employs high flow Coremax valves instead of the typical Shrader type valves WARNING Do NOT use a Schrader valve core r...

Страница 36: ...ll remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate defrost jumper sen...

Страница 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 38: ...V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into def...

Страница 39: ...74 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 138...

Страница 40: ...otor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop fi...

Страница 41: ...ion and orientation d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVA...

Страница 42: ...ty of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity see Table 8 The following pressure tables show nomina...

Страница 43: ...DB 67 WB Low Side High Side 134 341 135 363 136 387 137 412 138 439 140 468 141 498 143 530 144 563 146 598 85 DB 72 WB Low Side High Side 139 353 140 376 141 401 142 426 143 454 145 484 146 515 148...

Страница 44: ...1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X X X X X X X X X X 2nd Sta...

Отзывы: