Manual 2100-600
Page
21 of 38
LOW VOLTAGE CONNECTIONS
FOR DDC CONTROL
Fan Only
Energize G
Cooling Mode
Energize Y1, G
1st Stage Heating
Energize G, W1
2nd State Heating
Energize G, W2
(if employed)
Ventilation
Energize G, F
GENERAL
This unit is equipped with a variable speed ECM
motor. The motor is designed to maintain rated airflow
up to the maximum static allowed.
It is important
that the blower motor plugs are not plugged in or
unplugged while the power is on. Failure to remove
power prior to unplugging or plugging in the motor
could result in motor failure.
CAUTION
Do not plug in or unplug blower motor
connectors while the power is on.
Failure to do so may result in motor failure.
The Climate Control
Option B
is an electronic,
programmable thermostat and is BACnet compatible.
The thermostat can be set in the heat, cool or automatic
mode. When the thermostat is set in the heat mode, it
can heat only to maintain the temperature set on the
thermostat. When the thermostat is set in the cool
mode, it can cool only to maintain the temperature set
on the thermostat. When the thermostat is set in the
automatic mode, the thermostat can change
automatically to the heat or cool modes to maintain the
temperature set on the thermostat. This thermostat
supports BACnet IP, MS/TP and Ethernet protocols.
The Climate Control
Option C
is an electronic,
programmable thermostat with CO
2
control and is
BACnet compatible. The thermostat can be set in the
heat, cool or automatic mode. When the thermostat is
set in the heat mode, it can heat only to maintain the
temperature set on the thermostat. When the thermostat
is set in the cool mode, it can cool only to maintain the
temperature set on the thermostat. When the thermostat
is set in the automatic mode, the thermostat can change
automatically to the heat or cool modes to maintain the
temperature set on the thermostat. The CO
2
control
will energize the vent option and the ID blower when
the room CO
2
levels rise over set level. Default CO
2
set
point is 1000 ppm. See Figure 23.
The CO
2
controller will energize the vent option and the
ID blower when the room CO
2
levels rise over set level.
Default CO
2
set point is 1000 ppm. See Figure 23.
NOTE: On option X, field provided means to control
ventilation must be used if any of the motorized
ventilation options are installed.
NOTE: Thermostats are shipped in the bottom of
the unit and must be mounted to the factory
mounted subbase at time of installation.
LOW VOLTAGE CONNECTIONS
These units use a grounded 24 volt AC low voltage
circuit.
The
“R”
terminal is the
hot
terminal and the
“C”
terminal is
grounded.
“G”
terminal or pin 6 of P2 is the
fan input
. If the
climate control option is abandoned and connections
are made directly to P2 pin 6 of P2 must be energized
for proper operation.
“Y1”
terminal or pin 7 of P2 is the
compressor input
.
“W1”
terminal or pin 8 of P2 is the
fist stage heat.
“R”
terminal or pin 10 of P2 is
24 VAC hot
.
“C”
terminal or pin 11 of P2 is
24 VAC grounded.
“L”
terminal or pin 12 of P2 is
compressor lockout
output.
This terminal is activated on a high or low
pressure trip by the electronic heat pump control. This
is a 24 VAC output.
“W2”
terminal or pin 9 of P2 is
second stage heat
(if
equipped). If the unit is equipped with an optional hot
water coil plenum box or electric heat these will be
energized by this terminal.
“F”
terminal of pin 5 of P2 is the
ventilation input
.
This terminal energizes any factory installed ventilation
option.
NOTE: For total and proper control using DDC, a total
of 5 controlled outputs are required (4 if no
ventilation system is installed).
Содержание Q-TEC Q24A2
Страница 7: ...Manual 2100 600 Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...
Страница 10: ...Manual 2100 600 Page 10 of 38 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...
Страница 14: ...Manual 2100 600 Page 14 of 38 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 16: ...Manual 2100 600 Page 16 of 38 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 32: ...Manual 2100 600 Page 32 of 38 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...