background image

Manual 2100-600

Page 

20 of 38

WIRING  –  MAIN POWER

Refer to the unit rating plate and/or Table 2 for wire 
sizing information and maximum fuse or “HACR 
Type” circuit breaker size.  Each unit is marked with 
a “Minimum Circuit Ampacity”.  This means that the 

field wiring used must be sized to carry that amount 

of current.  Depending on the installed KW of electric 

heat, there may be two field power circuits required.  If 

this is the case, the unit serial plate will so indicate.  All 
models are suitable only for connection with copper 
wire.  Each unit and/or wiring diagram will be marked 
“Use Copper Conductors Only”.  These instructions 

MUST BE

 adhered to.  Refer to the National Electrical 

Code (NEC) for complete current carrying capacity 
data on the various insulation grades of wiring material.  
All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C 
copper) for all models, including the most commonly 

used heater sizes.  Also shown are the number of field 

power circuits required for the various models with 
heaters.

The unit rating plate lists a “Maximum Time Delay 
Relay Fuse” or “HACR Type” circuit breaker that is to 
be used with the equipment.  The correct size must be 
used for proper circuit protection, and also to assure that 
there will be no nuisance tripping due to the momentary 
high starting current of the compressor motor.

FIGURE  15 

COMPONENT LOCATION

TABLE  3

OPERATING VOLTAGE RANGE

NOTE: The voltage should be measured at the field 

power connection point in the unit and while 
the unit is operating at full load (maximum 
amperage operating condition).

The disconnect access door on this unit may be locked 
to prevent unauthorized access to the disconnect.

See “Start Up” section for information on three phase 
scroll compressor start-ups.

The field wiring connections are located behind the top and 

hinged panel in the circuit breaker panel.  See Figure 15. 

WIRING  –  LOW VOLTAGE WIRING

230/208V, 1 PHASE AND 3 PHASE EQUIPMENT 

DUAL PRIMARY VOLTAGE TRANSFORMERS.

All Equipment leaves the factory wired on 240V tap.  
For 208V operation, reconnect from 240V to 208V tap.  
The acceptable operating voltage range for the 240 and 
208V taps are as noted in Table 3.

TAP

RANGE

240V

253 – 216

208V

220 – 187

OPTIONAL CLIMATE CONTROLS 

SEQUENCE OF OPERATION 

The standard Climate Control 

Option X

 is a remote 

thermostat connection terminal block.  See Figure 17 for 
wiring diagram.  Compatible thermostats are listed in 
Table 4.

The Climate Control 

Option D

 is an electronic, 

programmable thermostat.  The subbase of the thermostat 
is factory wired to the front panel of the unit.  See Figure 
19 for wiring diagram.  Compatible for use with Energy 
Recovery Ventilator or Economizer.  The thermostat can 
be set in the heat, cool or automatic mode.  When the 
thermostat is sent in the heat mode, it can heat only to 
maintain the temperature set on the thermostat.  When 
the thermostat is set in the cool mode, it can cool only 
to maintain the temperature set on the thermostat.  
When the thermostat is set in the automatic mode, the 
thermostat can change automatically to the heat or cool 
modes to maintain the temperature set on the thermostat.

The Climate Control 

Option H

 is an electronic, 

programmable thermostat and a CO

2

 controller.  The 

subbase of the thermostat and CO

2

 controller are factory 

wired to the front panel of the unit.  See Figure 20 
for wiring diagram.  The thermostat can be set in the 
heat, cool or automatic mode.  When the thermostat is 
set in the heat mode, it can heat only to maintain the 
temperature set on the thermostat.  When the thermostat 
is set in the cool mode, it can cool only to maintain the 
temperature set on the thermostat.  When the thermostat 
is set in the automatic mode, the thermostat can change 
automatically to the heat or cool modes to maintain the 
temperature set on the thermostat.

DEHUMIDIFICATION 

CONTROL 

(OPTIONAL)

UNIT 

MOUNTED 

THERMOSTAT 

LOCATION

ELECTRIC 

HEATERS

CIRCUIT  

BREAKER PANEL 

& CONTROLS

INDOOR 

BLOWER

SIDE FIELD WIRE 

ENTRANCE

LOWER

CONTROL 

PANEL

REMOTE 

THERMOSTAT

TERMINAL 

BLOCK

Содержание Q-TEC Q24A2

Страница 1: ...ing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 600 Supersedes NEW File Vol II Tab 14 Date 08 21 13 Models Q24A2 Q30A2 Q36A2 Q42A2 Q48A2 Q60A2 Q TEC SERIES PACKAGE...

Страница 2: ...Built In Electric Heat Table 5 Table 2 Electrical Specifications 6 Table 3 Operating Voltage Range 20 Table 4 Wall Thermostats 22 Table 5 Fan Blade Dimensions 37 Table 6 Indoor Blower Performance 37 T...

Страница 3: ...mmer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditio...

Страница 4: ...reheat if applicable VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate E Economizer Not available on dehumidification versions P Commercial Ventilator Motorized w Exhaust Po...

Страница 5: ...08V 1 240V 1 208V 1 480V 3 240V 1 208V 1 240V 1 208V 1 480V 3 KW BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH 5 0 16 380 12 290 16 380 12 290 6 0 20 500 15...

Страница 6: ...0 25 6 10 10 10 Q42A2 B0Z B06 B09 B15 230 208 3 1 1 1 1 26 26 35 53 35 35 35 60 8 8 8 6 10 10 10 10 Q42A2 C0Z C06 C09 C15 460 3 1 1 1 1 13 14 18 27 15 15 20 30 14 14 12 10 14 14 12 10 Q48A2 A0Z A05 A1...

Страница 7: ...Manual 2100 600 Page 7 of 38 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down the...

Страница 9: ...structions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly...

Страница 10: ...Manual 2100 600 Page 10 of 38 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...y adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension ca...

Страница 12: ...rom the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be ins...

Страница 13: ...EAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 OP...

Страница 14: ...Manual 2100 600 Page 14 of 38 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 16: ...Manual 2100 600 Page 16 of 38 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 17: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 19: ...ck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessa...

Страница 20: ...E WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All Equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable o...

Страница 21: ...thermostat When the thermostat is set in the automatic mode the thermostat can change automatically to the heat or cool modes to maintain the temperature set on the thermostat The CO2 control will en...

Страница 22: ...0 1120 445 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover 8403 058 TH5220D1151 2 stage Cool 2 stage Heat Electronic Non Programmable HP...

Страница 23: ...zed ventilation options are installed 1 Y2 W1 R C W2 Y1 E 1 2 G Y2 A Y1 W2 C R W1 E 1 G Y2 Y W2 C R W 2 3 4 5 6 7 8 9 11 12 10 F Rc G 2 3 BROWN PURPLE RED WHITE BLUE YELLOW TERMINAL BLOCK 8403 060 1 8...

Страница 24: ...the CS2000A or other field provided means to control ventilation must be used if any of the motorized ventilation options are installed W1 E Orange 2 Yellow Brown 7 G 12 W2 Red White Blue 9 10 1 6 5 B...

Страница 25: ...FIGURE 19 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION W1 E 8403 060 D THERMOSTAT OPTION Y2 12 Plug 2 Brown G Purple Orange C Blue 9 10 6 5 Black White A 3 11 8 4102 070 4 R Y1 7 Red Wh...

Страница 26: ...range 2 Red White Blue 9 10 6 Part 8403 060 5 Black White G 3 11 8 R Y1 Plug 2 C W2 1 Yellow 12 Purple Brown 7 A Brown White 2 Y2 Black White Red White Brown White Out Controller Red White W1 E 4 3 4...

Страница 27: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Страница 28: ...event compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light a...

Страница 29: ...lockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer t...

Страница 30: ...pected from the outside of the building by looking through the outdoor grille The mist eliminator can be serviced from the outside by using a vacuum cleaner The outdoor grille must be removed Use the...

Страница 31: ...te slide out of the QERV The mist eliminator can be seen through the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and...

Страница 32: ...Manual 2100 600 Page 32 of 38 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 33: ...Manual 2100 600 Page 33 of 38 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 34: ...bank of heaters if equipped is energized High Low Pressure control provides protection for the compressor In the event system pressures go above 600 PSI or below 15 PSI in cooling mode the compressor...

Страница 35: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 36: ...n d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and ve...

Страница 37: ...REFRIGERANT CHARGE This unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigeran...

Страница 38: ...A2 75 DB 62 WB Low Side High Side 116 356 119 380 122 406 124 431 127 457 129 483 131 509 133 535 135 563 80 DB 67 WB Low Side High Side 124 365 127 390 130 416 133 442 136 469 138 495 140 522 142 549...

Отзывы: