Bard PH13242-A Скачать руководство пользователя страница 9

Manual

2100-468E

Page

9 of 27

INSTALLATION

LOCATION

GENERAL

The unit must be located outside, or in a well ventilated
area.  It must not be in the space being heated or cooled.  A
sound absorbing material should be considered if the unit is
to be installed in such a position or location that might
cause transmission of sound or vibration to the living area
or adjacent buildings.

SLAB MOUNTING

In areas where winter temperatures 

DO NOT 

go below

32°F for periods over twelve hours, the unit may be slab
mounted at grade level.  When installing unit at grade level,
install on a concrete slab at least four inches above finished
grade level.  Slab should have a slope tolerance away from
the building structure of at lease ¼ inch per foot, while
being level from side to side.  This will prevent ice buildup
under the unit during defrost cycles.  Place slab in a
location where runoff water from higher ground will not
collect around unit.  See Figure 2.

A minimum of 24 inches should be provided between the
coil inlet and any building surfaces.  Provide a minimum of
three feet clearance on the service access side of the unit.
See Figure 3.

When a unit is installed in areas where low ambient
temperatures or strong winter winds exist, it should be
placed so prevailing winter winds are not in direct line with
the heat pump coil.  If this is not possible, a wind barrier
should be constructed.  Place barrier 24 inches from the
coil inlet side of the unit and in the direction of prevailing
winds.  Size barrier at least the same height and width as
the unit.  This may be necessary on ground level
installations, also.  See Figure 3.

WINTER INSTALLATION BELOW 32°F

In areas where winter conditions go below 32°F for
extended periods, the unit must be elevated above the
mounting surface to prevent snowfall or defrost ice
accumulation from interfering with the operation of the
unit.  A minimum of twelve inch elevation is
recommended, while greater elevation may be required for
areas of high snow accumulation.  Poured concrete, steel
framework, brick, cement block, etc., can be utilized to
construct a suitable raised mounting platform.  See
Figure 4.

TYPICAL INSTALLATIONS

1.

ROOF MOUNTED

  

–  The unit is mounted on a

sturdy base on the roof of the building.  Return air to
the unit is brought through a single return grille (grilles
with built-in filters are best since they enable easy
access for filter changing).  Return air ducts are
attached to the lower section of the front panel.  Supply
air is brought from the unit to attic duct work or to a
furred down hall.  Supply air duct is attached to the top
of the front panel.

CAUTION:  All outdoor duct work must be thoroughly

insulated and weatherproofed.  All attic duct
work must be thoroughly insulated.  Two inch
thick insulation with suitable vapor barrier is
recommended for both outdoor and attic runs.

In roof top installation, as in all installations, the heat
pump must be level from side to side.  However, the
unit should have a pitch along the length to assure
complete external drainage of precipitation and of
defrost condensate.

2.

CRAWL SPACE

  

–  Duct work installed in crawl

space must be well insulated and provided with a vapor
barrier.  In addition, the crawl space must be
thoroughly ventilated and provided with a good vapor
barrier as a ground cover.  It is most desirable to install
the unit outdoors rather than inside the crawl space, so
that it will be readily accessible for service.  In
addition, it is necessary to dispose of  the condensate
from the outdoor coil on the heating cycle, and this is
virtually impossible with the unit installed inside the
crawl space.

3.

SLAB MOUNTED AT GROUND LEVEL

  

  

This

type installation is ideal for homes with a slab floor
construction where a roof mounted unit is not desired.
The supply and return duct work can be run through a
furred closet space.

4.

THROUGH THE WALL

 

 –  This type installation

requires a suitable framework to be fabricated capable
of withstanding the unit weight.  Normally the unit will
be insulated so as to minimize supply and return duct
work.

Содержание PH13242-A

Страница 1: ...anual 2100 468E Supersedes 2100 468D File Volume II Tab 11 Date 05 28 09 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned MODELS PH13242 A PH13302 A PH13362 A PH...

Страница 2: ...onnections 26 Figure 13 Wiring Connections Voltage 27 Start Up and Operation General 17 Topping Off System Charge 17 Safety Practices 17 Start Up Notes 17 Three Phase Scroll Compressor Start Up Inform...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels...

Страница 5: ...c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2...

Страница 6: ...0 2 0 4 2 X 1 X 1 9 0 B 3 2 3 P H E 3 8 0 2 0 4 2 X 5 1 B 3 2 3 P H E 3 8 0 2 0 4 2 X 2 5 0 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 0 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 5 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X 1...

Страница 7: ...e v O x a M t n e r r u C n o i t c e t o r P 2 d l e i F r e w o P g n i r i W 3 d n u o r G e z i S e r i W 5 0 A 3 2 3 P H E 0 1 A 3 2 3 P H E 5 1 A 3 2 3 P H E 1 8 0 2 0 4 2 1 8 0 2 0 4 2 1 8 0 2...

Страница 8: ...air intake grille intake grille access door Blower motor Condenser fan G 47 11 16 H Unit Dimension Chart MIS 2142 A A C B C H height L length W width D E F G PA PH1324 1330 1336 5 875 32 875 13 875 3...

Страница 9: ...while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick cement block etc can be utilized to construct a suitable raised mounting platform See...

Страница 10: ...e and ressor Blower Motor Heater Package Blower Compressor from top units only Condenser fan and motor access above fan Leave 60 min Side View View Top between duct and any combustible material if dis...

Страница 11: ...ORMS Both legs must rest on surface of platform 32 F or lower climate 12 min if in 48 min 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Platform can be as shown...

Страница 12: ...pped with a coupling that must be piped through a condensate drain trap to a suitable drain C Always mount the unit is such a position that it may be easily reached for servicing and maintenance D Ins...

Страница 13: ...pecified maintain the reversing valve energized when switched into heating mode does not cycle with demand TABLE 7 THERMOSTAT WIRE SIZE t a t s o m r e h T s e r u t a e F t n a n i m o d e r P 8 5 0...

Страница 14: ...o Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material The unit rating plate lists a Maximum Time Delay Fuse or HACR ty...

Страница 15: ...irable not advantageous in terms of efficiency Since most equipment at time of manufacture is not designated for any specific destination of the country and most of the equipment is installed in areas...

Страница 16: ...0 3 2 1 B 2 6 3 3 1 H P 9 0 0 3 2 3 A 2 2 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 2 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 8 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 8 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 0 6 3 1 H P 0 1 5 0 0 3...

Страница 17: ...arges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks ha...

Страница 18: ...e room thermostat is in the On position and the blower is already in operation then the motor will ramp up to the required speed for cooling HEATING 1st Stage On a call for heating from the room therm...

Страница 19: ...urer s recommendation is for 60 minute defrost cycles There is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to el...

Страница 20: ...o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n e p o r o f k c e h...

Страница 21: ...7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4...

Страница 22: ...power fuses or circuit breakers to be sure that they are the correct rating 5 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential PRESSURE SERVICE PO...

Страница 23: ...g i H 7 3 1 2 5 2 8 3 1 6 7 2 0 4 1 9 9 2 1 4 1 3 2 3 2 4 1 7 4 3 4 4 1 0 7 3 5 4 1 4 9 3 6 4 1 0 2 4 8 4 1 6 4 4 9 4 1 2 7 4 1 5 1 8 9 4 2 5 1 4 2 5 3 5 1 0 5 5 5 8 B D 2 7 B W e d i S w o L e d i S...

Страница 24: ...w o L e d i S h g i H 6 3 1 1 5 2 7 3 1 4 7 2 9 3 1 8 9 2 0 4 1 1 2 3 1 4 1 4 4 3 3 4 1 8 6 3 4 4 1 1 9 3 5 4 1 2 2 4 5 4 1 2 5 4 6 4 1 3 8 4 6 4 1 3 1 5 7 4 1 4 4 5 8 4 1 5 7 5 5 8 B D 2 7 B W e d i...

Страница 25: ...y around the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 11 Do not overheat joint FIGURE 11 BRAZING DIAG...

Страница 26: ...within the ranges as listed on the unit serial plate If higher than allowed additional duct work is needed e If the motor does not shut off at the end of the cycle wait for any programmed delays to t...

Страница 27: ...nd the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Also check t...

Отзывы: