Bard PH13242-A Скачать руководство пользователя страница 26

Manual

2100-468E

Page

26 of 27

FIGURE  12

TROUBLESHOOTING  GE  X13-SERIES ECM2.3

 MOTORS

If the Motor is Running

1.  It is normal for the motor to rock back and forth on start up.

Do not replace the motor if this is the only problem identified.

2.  If the system is excessively noisy, does not appear to change

speeds in response to a demand (Heat, Cool, Other), or is having
symptoms during the cycle such as tripping limit or freezing coil,
check the following:

a. Wait for programmed delays to time out.
b.Ensure that the motors control inputs are wired to the factory

supplied wiring diagram to insure motor is getting proper
control signals and sequencing.

c. Remove the filter and check that all dampers, registers, and

grilles are open and free flowing.  If removing the filters
corrects the problem, clean or replace with a less restrictive
filter.  Also check and clean the blower wheel or coil as
necessary.

d.Check the external static pressure (total of both supply and

return) to insure that you are within the ranges as listed on the
unit serial plate.  If higher than allowed, additional duct work
is needed.

e. If the motor does not shut off at the end of the cycle, wait for

any programmed delays to time out (no more than 90
seconds).   Also make sure that there is no call for
“Continuous Fan” on the "G" terminal.

f. If the above diagnostics do not solve the problem, confirm the

voltage checks in the next section below, then continue with
the  “Model X13 Communication Diagnostics”.

If the Motor is Not Running

1.  Check for proper high voltage and ground at the (L/L1) (G) (N/

L2) connections at the motor (see Figure 12).  Correct any voltage
issues before proceeding to the next step.  The X13 Motor is voltage
specific.  Only the correct voltage should be applied to the proper
motor.  Input voltage within plus or minus 10% of the nominal 230
VAC is acceptable.

2.  If the motor has proper high voltage and ground at the (L/L1)

(G) (N/L2) connections, then continue with the “Model X13
Communication Diagnostics”.

L2 LINE
POWER

EARTH

GROUND

L1 LINE
POWER

NOTE:   MOTOR IS CONSTANTLY 

POWERED BY LINE VOLTAGE

NOTE:  Bard Models PH13242; PH13302; PH13362-A, -B; PH13422-A, -B, -C; PH13482-A, -B, -C; PH13602-A, -B, -C

contain the X13-Series Motors.

Содержание PH13242-A

Страница 1: ...anual 2100 468E Supersedes 2100 468D File Volume II Tab 11 Date 05 28 09 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned MODELS PH13242 A PH13302 A PH13362 A PH...

Страница 2: ...onnections 26 Figure 13 Wiring Connections Voltage 27 Start Up and Operation General 17 Topping Off System Charge 17 Safety Practices 17 Start Up Notes 17 Three Phase Scroll Compressor Start Up Inform...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels...

Страница 5: ...c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2...

Страница 6: ...0 2 0 4 2 X 1 X 1 9 0 B 3 2 3 P H E 3 8 0 2 0 4 2 X 5 1 B 3 2 3 P H E 3 8 0 2 0 4 2 X 2 5 0 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 0 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 5 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X 1...

Страница 7: ...e v O x a M t n e r r u C n o i t c e t o r P 2 d l e i F r e w o P g n i r i W 3 d n u o r G e z i S e r i W 5 0 A 3 2 3 P H E 0 1 A 3 2 3 P H E 5 1 A 3 2 3 P H E 1 8 0 2 0 4 2 1 8 0 2 0 4 2 1 8 0 2...

Страница 8: ...air intake grille intake grille access door Blower motor Condenser fan G 47 11 16 H Unit Dimension Chart MIS 2142 A A C B C H height L length W width D E F G PA PH1324 1330 1336 5 875 32 875 13 875 3...

Страница 9: ...while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick cement block etc can be utilized to construct a suitable raised mounting platform See...

Страница 10: ...e and ressor Blower Motor Heater Package Blower Compressor from top units only Condenser fan and motor access above fan Leave 60 min Side View View Top between duct and any combustible material if dis...

Страница 11: ...ORMS Both legs must rest on surface of platform 32 F or lower climate 12 min if in 48 min 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Platform can be as shown...

Страница 12: ...pped with a coupling that must be piped through a condensate drain trap to a suitable drain C Always mount the unit is such a position that it may be easily reached for servicing and maintenance D Ins...

Страница 13: ...pecified maintain the reversing valve energized when switched into heating mode does not cycle with demand TABLE 7 THERMOSTAT WIRE SIZE t a t s o m r e h T s e r u t a e F t n a n i m o d e r P 8 5 0...

Страница 14: ...o Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material The unit rating plate lists a Maximum Time Delay Fuse or HACR ty...

Страница 15: ...irable not advantageous in terms of efficiency Since most equipment at time of manufacture is not designated for any specific destination of the country and most of the equipment is installed in areas...

Страница 16: ...0 3 2 1 B 2 6 3 3 1 H P 9 0 0 3 2 3 A 2 2 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 2 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 8 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 8 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 0 6 3 1 H P 0 1 5 0 0 3...

Страница 17: ...arges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks ha...

Страница 18: ...e room thermostat is in the On position and the blower is already in operation then the motor will ramp up to the required speed for cooling HEATING 1st Stage On a call for heating from the room therm...

Страница 19: ...urer s recommendation is for 60 minute defrost cycles There is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to el...

Страница 20: ...o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n e p o r o f k c e h...

Страница 21: ...7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4...

Страница 22: ...power fuses or circuit breakers to be sure that they are the correct rating 5 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential PRESSURE SERVICE PO...

Страница 23: ...g i H 7 3 1 2 5 2 8 3 1 6 7 2 0 4 1 9 9 2 1 4 1 3 2 3 2 4 1 7 4 3 4 4 1 0 7 3 5 4 1 4 9 3 6 4 1 0 2 4 8 4 1 6 4 4 9 4 1 2 7 4 1 5 1 8 9 4 2 5 1 4 2 5 3 5 1 0 5 5 5 8 B D 2 7 B W e d i S w o L e d i S...

Страница 24: ...w o L e d i S h g i H 6 3 1 1 5 2 7 3 1 4 7 2 9 3 1 8 9 2 0 4 1 1 2 3 1 4 1 4 4 3 3 4 1 8 6 3 4 4 1 1 9 3 5 4 1 2 2 4 5 4 1 2 5 4 6 4 1 3 8 4 6 4 1 3 1 5 7 4 1 4 4 5 8 4 1 5 7 5 5 8 B D 2 7 B W e d i...

Страница 25: ...y around the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 11 Do not overheat joint FIGURE 11 BRAZING DIAG...

Страница 26: ...within the ranges as listed on the unit serial plate If higher than allowed additional duct work is needed e If the motor does not shut off at the end of the cycle wait for any programmed delays to t...

Страница 27: ...nd the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Also check t...

Отзывы: