Bard PH13242-A Скачать руководство пользователя страница 19

Manual

2100-468E

Page

19 of 27

MIS-1191

DEFROST CYCLE

The defrost cycle is controlled by temperature and time on
the solid state heat pump control.  See Figure 9.

When the outdoor temperature is in the lower 40°F
temperature range or colder, the outdoor coil temperature is
32°F or below.  This coil temperature is sensed by the
defrost sensor mounted near the bottom of the outdoor coil.
Once the Heat Pump Control board sees the resistance of
the defrost sensor has been below the resistance of 34545
(30°F) for 60 minutes of accumulated run time.  The Heat
Pump Control Board will start the defrost cycle by de-
energizing the reversing valve and condenser fan.  It will
also send a signal to W2 to energize the electric heat if
equipped.  When the Heat Pump Control Board reads the
resistance of the defrost sensor has risen to 16547 (57°F) or
it has been in defrost for 10 minutes the defrost cycle will
terminate.

After 30 minutes at 30°F or below, the heat pump control
will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops, electric
heaters are energized, and hot gas passing through the
outdoor coil melts any accumulated frost.  When the
temperature rises to approximately 57°F the coil sensor will
send a signal to the heat pump control which will return the
system to heating operations automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

There are three settings on the heat pump control – 30
minute, 60 minute and 90 minute.  Models are shipped
wired on the 60 minute setting for greatest operating

FIGURE  9

HEAT PUMP CONTROL BOARD

economy.  If special circumstances require a change to
another time, remove wire connected to terminal 60 and
reconnect to desired terminal.  Refer to Figure 9.  The
manufacturer’s recommendation is for 60 minute defrost
cycles.

There is a cycle speed up jumper on the control.  This can
be used to reduce the time between defrost cycle operation
without waiting for time to elapse.

Use a small screwdriver or other metallic object, or another
1/4 inch QC to short between the 

SPEEDUP

 terminals to

accelerate the HPC timer and initiate defrost.

Be careful not to touch any other terminals with instrument
used to short the 

SPEEDUP

 terminals.  It may take up to 10

seconds with the 

SPEEDUP

 terminals shorted for the

speedup to be completed and the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the 

SPEEDUP

 terminals.

Otherwise the timing will remain accelerated and run
through the 1 minute maximum defrost length sequence in
a matter of seconds and will automatically terminate the
defrost sequence.

There is an initiate defrost jumper (sen jump) on the control
that can be used at any outdoor ambient during the heating
cycle to simulate a 0° coil temperature.  This can be used to
check defrost operation of the unit without waiting for the
outdoor ambient to fall into the defrost region.

By placing a jumper across the SEN JMP terminals (a 1/4
inch QC terminal works best) the defrost sensor mounted
on the outdoor coils is shunted out and will activate the
timing circuit.  This permits the defrost cycle to be checked
out in warmer weather conditions without the outdoor
temperature having to fall into the defrost region.

In order to terminate the defrost test in the 

SEN JMP

jumper must be removed.  If left in
place too long the compressor could
stop due to the high pressure control
opening because of the high pressure
condition created by operating in the
cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is
likely no actual frost on the outdoor coil
in this artificial test condition.

There is also a 5 minute compressor
time delay function built into the HPC,
This is to protect the compressor from
instances it is helpful to the service
technician to override or speed up this
timing period, and shorting out the
speedup terminals for a few seconds can
do this.

Содержание PH13242-A

Страница 1: ...anual 2100 468E Supersedes 2100 468D File Volume II Tab 11 Date 05 28 09 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned MODELS PH13242 A PH13302 A PH13362 A PH...

Страница 2: ...onnections 26 Figure 13 Wiring Connections Voltage 27 Start Up and Operation General 17 Topping Off System Charge 17 Safety Practices 17 Start Up Notes 17 Three Phase Scroll Compressor Start Up Inform...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels...

Страница 5: ...c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2...

Страница 6: ...0 2 0 4 2 X 1 X 1 9 0 B 3 2 3 P H E 3 8 0 2 0 4 2 X 5 1 B 3 2 3 P H E 3 8 0 2 0 4 2 X 2 5 0 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 0 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X X X 5 1 A 3 1 5 P H E 1 8 0 2 0 4 2 X 1...

Страница 7: ...e v O x a M t n e r r u C n o i t c e t o r P 2 d l e i F r e w o P g n i r i W 3 d n u o r G e z i S e r i W 5 0 A 3 2 3 P H E 0 1 A 3 2 3 P H E 5 1 A 3 2 3 P H E 1 8 0 2 0 4 2 1 8 0 2 0 4 2 1 8 0 2...

Страница 8: ...air intake grille intake grille access door Blower motor Condenser fan G 47 11 16 H Unit Dimension Chart MIS 2142 A A C B C H height L length W width D E F G PA PH1324 1330 1336 5 875 32 875 13 875 3...

Страница 9: ...while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick cement block etc can be utilized to construct a suitable raised mounting platform See...

Страница 10: ...e and ressor Blower Motor Heater Package Blower Compressor from top units only Condenser fan and motor access above fan Leave 60 min Side View View Top between duct and any combustible material if dis...

Страница 11: ...ORMS Both legs must rest on surface of platform 32 F or lower climate 12 min if in 48 min 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Platform can be as shown...

Страница 12: ...pped with a coupling that must be piped through a condensate drain trap to a suitable drain C Always mount the unit is such a position that it may be easily reached for servicing and maintenance D Ins...

Страница 13: ...pecified maintain the reversing valve energized when switched into heating mode does not cycle with demand TABLE 7 THERMOSTAT WIRE SIZE t a t s o m r e h T s e r u t a e F t n a n i m o d e r P 8 5 0...

Страница 14: ...o Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material The unit rating plate lists a Maximum Time Delay Fuse or HACR ty...

Страница 15: ...irable not advantageous in terms of efficiency Since most equipment at time of manufacture is not designated for any specific destination of the country and most of the equipment is installed in areas...

Страница 16: ...0 3 2 1 B 2 6 3 3 1 H P 9 0 0 3 2 3 A 2 2 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 2 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 8 4 3 1 H P 0 1 5 0 0 3 2 1 C B 2 8 4 3 1 H P 9 0 0 6 4 0 3 2 3 A 2 0 6 3 1 H P 0 1 5 0 0 3...

Страница 17: ...arges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks ha...

Страница 18: ...e room thermostat is in the On position and the blower is already in operation then the motor will ramp up to the required speed for cooling HEATING 1st Stage On a call for heating from the room therm...

Страница 19: ...urer s recommendation is for 60 minute defrost cycles There is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to el...

Страница 20: ...o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n e p o r o f k c e h...

Страница 21: ...7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4...

Страница 22: ...power fuses or circuit breakers to be sure that they are the correct rating 5 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential PRESSURE SERVICE PO...

Страница 23: ...g i H 7 3 1 2 5 2 8 3 1 6 7 2 0 4 1 9 9 2 1 4 1 3 2 3 2 4 1 7 4 3 4 4 1 0 7 3 5 4 1 4 9 3 6 4 1 0 2 4 8 4 1 6 4 4 9 4 1 2 7 4 1 5 1 8 9 4 2 5 1 4 2 5 3 5 1 0 5 5 5 8 B D 2 7 B W e d i S w o L e d i S...

Страница 24: ...w o L e d i S h g i H 6 3 1 1 5 2 7 3 1 4 7 2 9 3 1 8 9 2 0 4 1 1 2 3 1 4 1 4 4 3 3 4 1 8 6 3 4 4 1 1 9 3 5 4 1 2 2 4 5 4 1 2 5 4 6 4 1 3 8 4 6 4 1 3 1 5 7 4 1 4 4 5 8 4 1 5 7 5 5 8 B D 2 7 B W e d i...

Страница 25: ...y around the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 11 Do not overheat joint FIGURE 11 BRAZING DIAG...

Страница 26: ...within the ranges as listed on the unit serial plate If higher than allowed additional duct work is needed e If the motor does not shut off at the end of the cycle wait for any programmed delays to t...

Страница 27: ...nd the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Also check t...

Отзывы: