background image

Manual 2100-467K 

Page 

16 of 24

start uP

These units require R-410A refrigerant and Polyol Ester 
oil.

General:

1.  Use separate service equipment to avoid cross    
 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A  

 

 refrigerant.

3.  Use manifold gauges rated for R-410A (800  

 

 

psi/250 psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-125.

5.  R-410A is nearly azeotropic - similar to R-22 and  
 

R-12.  Although nearly azeotropic, charge with   

 

liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure than   
 

R-22, and systems designed for R-22 cannot  

 

 

withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero,  
 

but must be reclaimed due to its global warming  

 potential.

8.  R-410A compressors use Polyol Ester oil.

9.  Polyol Ester oil is hygroscopic; it will rapidly    
 

absorb moisture and strongly hold this moisture in  

 

the oil.

10. A liquid line dryer must be used - even a deep    
 

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug  
 

compressor immediately after removal.  Purge with  

 

small amount of nitrogen when inserting plugs.

tOPPInG OFF sYstem charGe

If a leak has occurred in the system, Bard 
Manufacturing recommends reclaiming, evacuating 
(see criteria above), and charging to the nameplate 
charge.  Topping off the system charge can be done 
without problems.

With R-410A, there are no significant changes in the 

refrigerant composition during multiple leaks and 
recharges.  R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant).  The remaining 
refrigerant charge, in the system, may be used after 
leaks have occurred and then “top-off” the charge by 
utilizing the pressure charts on the inner control panel 
cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, 

it must come out of the charging cylinder/tank as a 
liquid to avoid any fractionation, and to insure optimal 
system performance.  Refer to instructions for the 
cylinder that is being utilized for proper method of 
liquid extraction.

saFetY PractIces:

1.  Never mix R-410A with other refrigerants.

2.  Use gloves and safety glasses, Polyol Ester oils can  
 

be irritating to the skin, and liquid refrigerant will  

 

freeze the skin.

3.  Never use air and R-410A to leak check; the  

 

 

mixture may become flammable.

4.  Do not inhale R-410A – the vapor attacks the    
 

nervous system, creating dizziness, loss of  

 

 

coordination and slurred speech.  Cardiac  

 

 

irregularities, unconsciousness and ultimate death  

 

can result from breathing this concentration.

5.  Do not burn R-410A.  This decomposition  

 

 

produces hazardous vapors.  Evacuate the area if  

 exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct  

 

 sunlight.

9.  Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge  

 

lines or cylinders.  R-410A expands significantly  

 

at warmer temperatures.  Once a cylinder or line is  

 

full of liquid, any further rise in temperature will  

 

cause it to burst.

start uP nOtes

For improved start up performance, wash the indoor 
coil with dishwasher detergent.

Содержание PA13242-A

Страница 1: ...362 A PA13362 B PA13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C INSTALLATION INSTRUCTIONS Manual 2100 467K Supersedes 2100 467J File Volume II Tab 10 Date 07...

Страница 2: ...e Ports 19 R 410A Refrigerant Charge 19 Fan Blade Settings 19 Pressure Tables 20 21 Suction and Discharge Tube Brazing 22 Troubleshooting GE Blower Motors 23 24 Figures Figure 1A Unit Dimensions 8 Fig...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...any separate equipment required to make up the entire system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the...

Страница 5: ...Recip Recip Recip Recip Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Volts 230 208 230 208 230 208 230 208 230 208 230 208 460 230 208 230 208 460 230 208 230 208 460 Rated Load Amp...

Страница 6: ...A13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C EHP323 A05 240 208 1 X X X EHP323 A10 240 208 1 X X X EHP323 A15 240 208 1 X X EHP323 B09 240 208 3 X EHP323 B1...

Страница 7: ...KW Capacity 208 Volts 240 208V Htr Amps Heater Internal Circuit Breaker Circuit B KW BTUH KW BTUH No Field Circuits l Min Circuit Ampacity j Max Over Current Protection k Field Power Wiring k Ground...

Страница 8: ...L W B F Condenser air Condenser air intake grille intake grille access door Blower motor Condenser fan G 47 11 16 H Unit Dimension Chart MIS 2142 A A C B C H height L length W width D E F G PA PH1324...

Страница 9: ...GURE 1B Dimensions of Units A B C D F E D A H G UNIT A B C D E F G H PA PH1324 1330 1336 7 3 16 38 13 16 36 3 4 1 3 8 33 5 8 35 1 2 18 3 16 17 1 4 PA PH1342 1348 1360 8 3 16 39 13 16 36 3 4 1 3 8 37 3...

Страница 10: ...All outdoor duct work must be thoroughly insulated and weatherproofed All attic duct work must be thoroughly insulated Two inch thick insulation with suitable vapor barrier is recommended for both out...

Страница 11: ...e Blower Compressor from top units only Condenser fan and motor access above fan Leave 60 min Side View View Top between duct and any combustible material if distance between outside wall and unit is...

Страница 12: ...oth legs must rest on surface of platform 32 F or lower climate 12 min if in 48 min 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Platform can be as shown or sol...

Страница 13: ...hat the trap material be of a type that will allow for expansion of water when it freezes AIR FILTERS Air filters for the return air side of the system are not provided as part of these models and mus...

Страница 14: ...ata on the various insulation grades of wiring material The electrical specifications list fuse and wire sizes 75 F copper for all models including the most commonly used heater sizes The unit rating...

Страница 15: ...ltage Wiring L 2 C O 1 Unit Control Panel Block Y C G R W1 W2 E F Y1 C G R W1 O Y2 W2 D A E L AUX R G E B RC 3 L B Thermostat Subbase Terminal HEAT ON UNITS WITH 15 OR MORE KW YO Unit 24V REMOVE JUMPE...

Страница 16: ...recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after lea...

Страница 17: ...for heating HEATING 2nd Stage If the operation of the 1st Stage electric heaters will not maintain the set room temperature then the thermostat will call for additional heat to help maintain the set...

Страница 18: ...is used to select Delay on Break time from 30 seconds to 5 minutes Delay on Make DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB setting 0 5 mi...

Страница 19: ...the unit by model number R 410A REFRIGERANT CHARGe This unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determine...

Страница 20: ...469 153 494 155 520 157 546 85 DB 72 WB Low Side High Side 144 253 146 278 148 304 151 329 153 355 155 380 157 406 159 432 161 459 163 485 165 512 167 538 169 565 PA1330 75 DB 62 WB Low Side High Side...

Страница 21: ...536 153 565 85 DB 72 WB Low Side High Side 145 257 147 281 149 306 151 330 152 355 154 379 156 404 157 434 159 464 160 494 162 525 163 555 165 585 PA1348 75 DB 62 WB Low Side High Side 125 239 127 263...

Страница 22: ...Areas 2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 9 To connect Recommended brazing materials silfos with minimum5 silverorsi...

Страница 23: ...continue with the Model X13 Communication Diagnostics Manual 2100 467H Page 22 of 23 FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 S...

Страница 24: ...motor is failed and will require replacement Manual 2100 467H Page 23 of 23 FIGURE 11 TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS CONT D Model X13 Communication Diagnostics The X13 motor is communica...

Отзывы: