Manual 2100-467K 

Page 

14 of 24

table  6

thermOstat WIre sIze

transFOrmer taPs

230/208V, 1 phase and 3 phase equipment employ dual 
primary voltage transformers.  All equipment leaves 
the factory wired on 240V tap.  For 208V operation, 
reconnect from 240V to 208V tap.  The acceptable 
operating voltage range for the 240 and 208V taps are:

 

taP

  

ranGe

 

 240 

253 – 216

 

 208 

220 – 187

NOTE:  The voltage should be measured at the field 

power connection point in the unit and while 
the unit is operating at full load (maximum 
amperage operating condition).

WIrInG  –  maIn POWer

Refer to the unit rating plate for wire sizing information 
and maximum fuse size.  Each outdoor unit is marked 
with a “Minimum Circuit Ampacity”.  This means that 

the field wiring used must be sized to carry that amount 

of current.  If field installed heaters are added to the 

basic unit, a second separate power supply circuit will 
be required.  The heater rating plate located adjacent 
to the basic unit rating plate will show the appropriate 
circuit ampacity fuse size, etc.  (Also see “Electrical 

Specifications” on pages 5 & 7.)  

All models are 

suitable for connection with copper wire only.  

These 

instructions 

must 

be adhered to.  Refer to the National 

Electrical Code for complete current carrying capacity 
data on the various insulation grades of wiring material.  

The electrical specifications list fuse and wire sizes 

(75°F copper) for all models including the most 
commonly used heater sizes.

The unit rating plate lists a “Maximum Time Delay 
Fuse” or “HACR” type circuit breaker that is to be used 
with the equipment.  The correct size must be used for 
proper circuit protection and also to assure that there 
will be no nuisance tripping due to the momentary high 
starting current of the compressor.

WIrInG – 24V lOW VOltaGe cOntrOl 

cIrcuIt

Five (5) wires should be run from thermostat subbase 

to the 24V terminal board in the unit.  A five conductor, 

18 gauge copper, color-coded thermostat cable is 
recommended.  The connection points are shown in 
Figure 6.

thermOstats

See specific wiring information for the different models, heater KWs, and voltages on unit and heating wiring 

diagrams.

IMPORTANT NOTE:  Only the thermostats as shown above will work with this equipment.  The thermostats and    

 

correct operation can be assured only by proper selection and application of these parts.

table 7

Wall thermOstats

transformer

Va

Fla

Wire

Gauge

maximum

Distance  

In Feet

55

2.3

20

18

16

14

12

45

60

100 

160

250

thermostat

Predominant Features

8403-058

(TH5220D1151)

2 stage Cool;  2 stage Heat

Electronic Non-Programmable

Auto or Manual changeover

8403-060

(1120-445)

3 stage Cool;  3 stage Heat

Programmable/Non-Programmable Electronic

HP or Conventional

Auto or Manual changeover

Содержание PA13242-A

Страница 1: ...362 A PA13362 B PA13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C INSTALLATION INSTRUCTIONS Manual 2100 467K Supersedes 2100 467J File Volume II Tab 10 Date 07...

Страница 2: ...e Ports 19 R 410A Refrigerant Charge 19 Fan Blade Settings 19 Pressure Tables 20 21 Suction and Discharge Tube Brazing 22 Troubleshooting GE Blower Motors 23 24 Figures Figure 1A Unit Dimensions 8 Fig...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...any separate equipment required to make up the entire system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the...

Страница 5: ...Recip Recip Recip Recip Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Volts 230 208 230 208 230 208 230 208 230 208 230 208 460 230 208 230 208 460 230 208 230 208 460 Rated Load Amp...

Страница 6: ...A13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C EHP323 A05 240 208 1 X X X EHP323 A10 240 208 1 X X X EHP323 A15 240 208 1 X X EHP323 B09 240 208 3 X EHP323 B1...

Страница 7: ...KW Capacity 208 Volts 240 208V Htr Amps Heater Internal Circuit Breaker Circuit B KW BTUH KW BTUH No Field Circuits l Min Circuit Ampacity j Max Over Current Protection k Field Power Wiring k Ground...

Страница 8: ...L W B F Condenser air Condenser air intake grille intake grille access door Blower motor Condenser fan G 47 11 16 H Unit Dimension Chart MIS 2142 A A C B C H height L length W width D E F G PA PH1324...

Страница 9: ...GURE 1B Dimensions of Units A B C D F E D A H G UNIT A B C D E F G H PA PH1324 1330 1336 7 3 16 38 13 16 36 3 4 1 3 8 33 5 8 35 1 2 18 3 16 17 1 4 PA PH1342 1348 1360 8 3 16 39 13 16 36 3 4 1 3 8 37 3...

Страница 10: ...All outdoor duct work must be thoroughly insulated and weatherproofed All attic duct work must be thoroughly insulated Two inch thick insulation with suitable vapor barrier is recommended for both out...

Страница 11: ...e Blower Compressor from top units only Condenser fan and motor access above fan Leave 60 min Side View View Top between duct and any combustible material if distance between outside wall and unit is...

Страница 12: ...oth legs must rest on surface of platform 32 F or lower climate 12 min if in 48 min 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Platform can be as shown or sol...

Страница 13: ...hat the trap material be of a type that will allow for expansion of water when it freezes AIR FILTERS Air filters for the return air side of the system are not provided as part of these models and mus...

Страница 14: ...ata on the various insulation grades of wiring material The electrical specifications list fuse and wire sizes 75 F copper for all models including the most commonly used heater sizes The unit rating...

Страница 15: ...ltage Wiring L 2 C O 1 Unit Control Panel Block Y C G R W1 W2 E F Y1 C G R W1 O Y2 W2 D A E L AUX R G E B RC 3 L B Thermostat Subbase Terminal HEAT ON UNITS WITH 15 OR MORE KW YO Unit 24V REMOVE JUMPE...

Страница 16: ...recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after lea...

Страница 17: ...for heating HEATING 2nd Stage If the operation of the 1st Stage electric heaters will not maintain the set room temperature then the thermostat will call for additional heat to help maintain the set...

Страница 18: ...is used to select Delay on Break time from 30 seconds to 5 minutes Delay on Make DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB setting 0 5 mi...

Страница 19: ...the unit by model number R 410A REFRIGERANT CHARGe This unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determine...

Страница 20: ...469 153 494 155 520 157 546 85 DB 72 WB Low Side High Side 144 253 146 278 148 304 151 329 153 355 155 380 157 406 159 432 161 459 163 485 165 512 167 538 169 565 PA1330 75 DB 62 WB Low Side High Side...

Страница 21: ...536 153 565 85 DB 72 WB Low Side High Side 145 257 147 281 149 306 151 330 152 355 154 379 156 404 157 434 159 464 160 494 162 525 163 555 165 585 PA1348 75 DB 62 WB Low Side High Side 125 239 127 263...

Страница 22: ...Areas 2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 9 To connect Recommended brazing materials silfos with minimum5 silverorsi...

Страница 23: ...continue with the Model X13 Communication Diagnostics Manual 2100 467H Page 22 of 23 FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 S...

Страница 24: ...motor is failed and will require replacement Manual 2100 467H Page 23 of 23 FIGURE 11 TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS CONT D Model X13 Communication Diagnostics The X13 motor is communica...

Отзывы: