Manual 2100-467K 

Page 

20 of 24

(c

ontinued on Page 20 in 

table 1

1)

table

  9

Pressure

 t

able

c

OO

lI

n

G

Air 

Temperature Entering Outdoor Coil Degree F

LOW

 SIDE

 PRESSURE

 +4 PSIG

HIGH S

IDE

 P

RESSURE

 +10 

PSIG

T

ables

 based

 upon

 rated

 CFM

 (airflow)

 across

 the

 evaporator

 coil.

If incorrect charge suspected (more than 

+

psig

 suction,

 

+

10

 psig

 liquid),

it 

is

 recommended

 refrigerant

 charge

 be

 reclaimed,

 system

 evacuated

 and

 charged

 to

 serial

 plate

 quantity

.

Model

Return Air  Temperature

Pressure

65°

70°

75°

80°

85°

90°

95°

100°

105°

110°

115°

120°

125°

PA1324

75° DB 62° WB

Low Side High Side

125 238

127 262

129 286

131 310

133 334

135 358

137 382

138 407

140 432

142 457

143 482

145 507

147 532

80° DB 67° WB

Low Side High Side

134 244

136 269

138 293

140 318

142 343

144 367

146 392

148 418

150 443

151 469

153 494

155 520

157 546

85° DB 72° WB

Low Side High Side

144 253

146 278

148 304

151 329

153 355

155 380

157 406

159 432

161 459

163 485

165 512

167 538

169 565

PA1330

75° DB 62° WB

Low Side High Side

126 246

128 267

131 289

133 310

135 332

137 353

139 374

141 402

143 429

145 457

148 484

150 512

152 539

80° DB 67° WB

Low Side High Side

135 252

137 274

140 296

142 318

144 340

147 362

149 400

151 412

153 440

156 469

158 497

160 525

162 553

85° DB 72° WB

Low Side High Side

145 261

148 284

150 306

153 329

155 352

158 375

160 397

163 427

165 456

167 485

170 514

172 543

174 573

PA1336

75° DB 62° WB

Low Side High Side

125 247

127 271

128 295

130 320

132 344

133 369

135 393

136 418

138 443

139 468

141 494

142 519

80° DB 67° WB

Low Side High Side

134 253

136 278

137 303

139 328

141 353

142 378

144 413

146 429

147 455

149 480

150 506

152 532

85° DB 72° WB

Low Side High Side

144 262

146 288

148 314

149 339

151 365

153 391

155 417

157 444

158 471

160 497

162 524

163 551

Содержание PA13242-A

Страница 1: ...362 A PA13362 B PA13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C INSTALLATION INSTRUCTIONS Manual 2100 467K Supersedes 2100 467J File Volume II Tab 10 Date 07...

Страница 2: ...e Ports 19 R 410A Refrigerant Charge 19 Fan Blade Settings 19 Pressure Tables 20 21 Suction and Discharge Tube Brazing 22 Troubleshooting GE Blower Motors 23 24 Figures Figure 1A Unit Dimensions 8 Fig...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...any separate equipment required to make up the entire system should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the...

Страница 5: ...Recip Recip Recip Recip Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Volts 230 208 230 208 230 208 230 208 230 208 230 208 460 230 208 230 208 460 230 208 230 208 460 Rated Load Amp...

Страница 6: ...A13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C EHP323 A05 240 208 1 X X X EHP323 A10 240 208 1 X X X EHP323 A15 240 208 1 X X EHP323 B09 240 208 3 X EHP323 B1...

Страница 7: ...KW Capacity 208 Volts 240 208V Htr Amps Heater Internal Circuit Breaker Circuit B KW BTUH KW BTUH No Field Circuits l Min Circuit Ampacity j Max Over Current Protection k Field Power Wiring k Ground...

Страница 8: ...L W B F Condenser air Condenser air intake grille intake grille access door Blower motor Condenser fan G 47 11 16 H Unit Dimension Chart MIS 2142 A A C B C H height L length W width D E F G PA PH1324...

Страница 9: ...GURE 1B Dimensions of Units A B C D F E D A H G UNIT A B C D E F G H PA PH1324 1330 1336 7 3 16 38 13 16 36 3 4 1 3 8 33 5 8 35 1 2 18 3 16 17 1 4 PA PH1342 1348 1360 8 3 16 39 13 16 36 3 4 1 3 8 37 3...

Страница 10: ...All outdoor duct work must be thoroughly insulated and weatherproofed All attic duct work must be thoroughly insulated Two inch thick insulation with suitable vapor barrier is recommended for both out...

Страница 11: ...e Blower Compressor from top units only Condenser fan and motor access above fan Leave 60 min Side View View Top between duct and any combustible material if distance between outside wall and unit is...

Страница 12: ...oth legs must rest on surface of platform 32 F or lower climate 12 min if in 48 min 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Platform can be as shown or sol...

Страница 13: ...hat the trap material be of a type that will allow for expansion of water when it freezes AIR FILTERS Air filters for the return air side of the system are not provided as part of these models and mus...

Страница 14: ...ata on the various insulation grades of wiring material The electrical specifications list fuse and wire sizes 75 F copper for all models including the most commonly used heater sizes The unit rating...

Страница 15: ...ltage Wiring L 2 C O 1 Unit Control Panel Block Y C G R W1 W2 E F Y1 C G R W1 O Y2 W2 D A E L AUX R G E B RC 3 L B Thermostat Subbase Terminal HEAT ON UNITS WITH 15 OR MORE KW YO Unit 24V REMOVE JUMPE...

Страница 16: ...recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after lea...

Страница 17: ...for heating HEATING 2nd Stage If the operation of the 1st Stage electric heaters will not maintain the set room temperature then the thermostat will call for additional heat to help maintain the set...

Страница 18: ...is used to select Delay on Break time from 30 seconds to 5 minutes Delay on Make DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB setting 0 5 mi...

Страница 19: ...the unit by model number R 410A REFRIGERANT CHARGe This unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determine...

Страница 20: ...469 153 494 155 520 157 546 85 DB 72 WB Low Side High Side 144 253 146 278 148 304 151 329 153 355 155 380 157 406 159 432 161 459 163 485 165 512 167 538 169 565 PA1330 75 DB 62 WB Low Side High Side...

Страница 21: ...536 153 565 85 DB 72 WB Low Side High Side 145 257 147 281 149 306 151 330 152 355 154 379 156 404 157 434 159 464 160 494 162 525 163 555 165 585 PA1348 75 DB 62 WB Low Side High Side 125 239 127 263...

Страница 22: ...Areas 2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 9 To connect Recommended brazing materials silfos with minimum5 silverorsi...

Страница 23: ...continue with the Model X13 Communication Diagnostics Manual 2100 467H Page 22 of 23 FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 S...

Страница 24: ...motor is failed and will require replacement Manual 2100 467H Page 23 of 23 FIGURE 11 TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS CONT D Model X13 Communication Diagnostics The X13 motor is communica...