background image

Manual 2100-324
Page

14

FAN BLADE SETTINGS

Shown in Figure 9 are the correct fan blade setting
dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
below be checked and blade adjusted in or out on the
motor shaft accordingly.

FIGURE  9

FAN BLADE SETTING DIMENSIONS

SUCTION AND DISCHARGE TUBE
BRAZING

Compliant Scroll compressors have copper plated steel
suction and discharge tubes.  These tubes are far more
rugged and less prone to leaks than copper tubes used on
other compressors.  Due to different thermal properties of
steel and copper, brazing procedures may have to be
changed from those commonly used.

To disconnect:  heat joint Areas 2 and 3 slowly and
uniformly until braze material softens and the tube can
be pulled out of suction fitting.  (See Figure 10.)

To connect:

Recommended brazing materials:  silfos with
minimum 5% silver or silver braze material with
flux.

Reinsert tube into fitting.

Heat tube uniformly in Area 1 moving slowly to
Area 2.  When joint reaches brazing temperature,
apply brazing material.  (See Figure 10.)

Heat joint uniformly around the circumference to
flow braze material completely around the joint.

Slowly move torch into Area 3 to draw braze
material into joint.  (See Figure 10.)

Do not overheat joint.

l

e

d

o

M

A

n

o

i

s

n

e

m

i

D

3

A

2

4

1

1

P

1

A

8

4

1

1

P

1

A

0

6

0

1

P

"

5

7

.

1

"

5

7

.

1

"

5

7

.

1

TABLE  9

The above suction line temperatures are based upon
80°F dry bulb/67°F wet bulb (50% RH) temperature and
rated airflow across the evaporator during cooling cycle.

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

F

e

e

r

g

e

D

5

9

D

O

e

r

u

t

a

r

e

p

m

e

T

F

e

e

r

g

e

D

2

8

D

O

e

r

u

t

a

r

e

p

m

e

T

3

A

2

4

1

1

P

1

A

8

4

1

1

P

1

A

0

6

1

0

P

0

0

4

1

0

5

5

1

0

0

7

1

9

5

-

7

5

7

5

-

5

5

9

4

-

7

4

0

6

-

8

5

1

6

-

9

5

6

5

-

4

5

SERVICE AND TROUBLESHOOTING

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

that they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full and

unrestricted airflow circulation is essential.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found in Table 10 in this
manual covering all models on cooling cycle.  It is
imperative to match the correct pressure table to the unit
by model number.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating
plate.  Optimum unit performance will occur with a
refrigerant charge resulting in a suction line temperature
(6” from compressor) as shown in Table 9.

Содержание P1060A1

Страница 1: ...MODELS P1142A3 P1148A1 P1060A1 INSTALLATION INSTRUCTIONS Manual 2100 324B Supersedes 2100 324A File Volume II Tab 10 Date 04 01 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead...

Страница 2: ...charge Tube Brazing 12 Pressure Table 13 Figures Figure 1 Prefabricated Rood Curb Specifications 5 Figure 2 Field Fabricated Curbing 5 Figure3 Elevated Mounting Platforms 7 Figure 4 Airflow and Servic...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Co...

Страница 4: ...P 3 0 6 4 6 0 5 4 1 4 2 1 1 0 2 4 1 2 1 2 1 TABLE 1 ELECTRICALDATA Q R R TABLE 2 OPTIONALFIELDINSTALLEDHEATERPACKAGES ONLY TO BE USED WITH THE AIR CONDITIONING MODELS INDICATED S Standard application...

Страница 5: ...0 2 0 4 2 3 8 0 2 0 4 2 3 8 0 2 0 4 2 9 5 1 8 1 0 0 7 0 3 0 0 2 1 5 0 0 4 1 6 5 7 6 5 2 1 1 0 5 3 1 0 0 0 3 2 0 0 4 8 3 0 0 1 6 4 7 1 2 2 6 3 4 3 4 1 1 1 8 2 6 4 5 5 0 3 0 5 0 6 0 1 8 6 0 1 0 1 0 1 9...

Страница 6: ...d be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recom...

Страница 7: ...Return Air Dimension C is length Supply Air Dimension C is length Return Air Dimension H is width Supply Sir Dimension J is width f o o R b r u C A B C D E F J H d o o H f o o R l e d o M g n i n o i...

Страница 8: ...be utilized to construct a suitable raised mounting platform See Figure 6 DUCT WORK Refer to Tables 4 5 and 5A when designing duct work for maximum static pressure available with the specific model a...

Страница 9: ...Manual 2100 324 Page 7 FIGURE 3 ELEVATEDMOUNTINGPLATFORMS MIS 1183 MIS 1185 FIGURE 4 AIRFLOWANDSERVICEACCESSCLEARANCES...

Страница 10: ...Manual 2100 324 Page 8 FIGURE 5 ROOFTOPAPPLICATION MAY ALSO BE REQUIRED FOR GROUND LEVEL INSTALLATIONS MIS 1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL ABOVE 32 F OUTSIDE TEMPERATURE MIS 1184...

Страница 11: ...ction size or larger Do not operate unit without trap Unit must be level or slightly inclined toward drain With a trap installed on a unit located in an unconditioned area water in the trap may freeze...

Страница 12: ...g at full load maximum amperage operating condition WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse size Each outdoor unit is marked with a Minimum Circui...

Страница 13: ...Manual 2100 324 Page 11 FIGURE 8 LOWVOLTAGEWIRING MIS 1180...

Страница 14: ...tomatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation HEATING A circuit R W1 is completed on each heating cycle energ...

Страница 15: ...pump unit model The lockout features both soft and manual are a function of the Compressor Control Module ADJUSTMENTS ADJUSTABLE DELAY ON MAKE AND DELAY ON BREAK TIMER The potentiometer is used to sel...

Страница 16: ...at joint l e d o M A n o i s n e m i D 3 A 2 4 1 1 P 1 A 8 4 1 1 P 1 A 0 6 0 1 P 5 7 1 5 7 1 5 7 1 TABLE 9 The above suction line temperatures are based upon 80 F dry bulb 67 F wet bulb 50 RH temperat...

Страница 17: ...6 e d i S w o L e d i S h g i H 3 7 3 0 2 4 7 7 1 2 5 7 1 3 2 6 7 6 4 2 8 7 4 6 2 9 7 8 7 2 0 8 4 9 2 1 8 2 1 3 2 8 0 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 8 7 8 0 2 9 7 2 2 2...

Страница 18: ...Manual 2100 324 Page 16...

Страница 19: ...Manual 2100 324 Page 17...

Страница 20: ...Manual 2100 324 Page 18...

Страница 21: ...Manual 2100 324 Page 19...

Страница 22: ...Manual 2100 324 Page 20...

Страница 23: ...Manual 2100 324 Page 21...

Отзывы: