START UP AND OPERATION

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with single
phase compressors since they will always start and run in
the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a way
as to cause rotation in the reverse direction, verification of
proper rotation must be made.   Verification of proper
rotation direction is made by observing that suction
pressure drops and discharge pressure rises when the
compressor is energized.  Reverse rotation also results in
an elevated sound level over that with correct rotation, as
well as, substantially reduced current draw compared to
tabulated values.

Verification of proper rotation must be made at the time
the equipment is put into service.
  If improper rotation is
corrected at this time there will be no negative impact on
the durability of the compressor.  However, reverse
operation for over one hour may have a negative impact on
the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes the compressor’s
internal protector will trip.

All three phase ZR*3 compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation, connecting
properly phased power leads to the same Fusite terminals
should maintain proper rotation direction.

The direction of rotation of the motor may be changed by
reversing any two line connections to the unit.

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling in

compressor contactor starting the compressor and outdoor
motor.  The G (indoor motor) circuit is automatically
completed on any call for cooling operation, or can be
energized by manual fan switch on subbase for constant air
circulation.

HEATING

  –  A circuit R-W1 is completed on each

heating cycle energizing electric heat if so equipped.

START UP NOTES

For improved start up performance, wash the indoor coil
with dishwasher detergent

COMPRESSOR CONTROL MODULE

The compressor control is an anti-short cycle/lockout timer
with high and low pressure switch monitoring and alarm
output.

ADJUSTABLE DELAY-ON-MAKE AND BREAK
TIMER

On a call for compressor operation the delay-on-make
period begins which will be 10% of the delay-on-break
setting.  When the delay-on-make is complete and the high
pressure switch (and low pressure switch if employed) is
closed, the compressor contactor is energized.  Upon
shutdown the delay-on-break timer starts and prevents
restart until the delay-on-break and delay-on-make periods
have expired.

HIGH PRESSURE SWITCH AND LOCKOUT
SEQUENCE  (Standard Feature)

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout timer
will go into a soft lockout and stay in soft lockout until the
high pressure switch closes and the delay-on-make time
has expired.  If the high pressure switch opens again in this
same operating cycle the unit will go into manual lockout
condition and the alarm circuit will energize.  Recycling
the wall thermostat resets the manual lockout.

LOW PRESSURE SWITCH, BYPASS, AND
LOCKOUT SEQUENCE

NOTE: The low pressure switch is an optional control

and the bypass and lockout sequence are part of
the standard compressor control module.

If the low pressure switch opens for more that 120
seconds, the compressor contactor will de-energize and go
into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay-on-make time delay has expired.  If the low pressure
switch remains open or opens again for longer than 120
seconds the unit will go into manual lockout condition and
the alarm circuit will energize.  Recycling the wall
thermostat resets the manual lockout.

Содержание P1060A1

Страница 1: ...MODELS P1142A3 P1148A1 P1060A1 INSTALLATION INSTRUCTIONS Manual 2100 324B Supersedes 2100 324A File Volume II Tab 10 Date 04 01 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead...

Страница 2: ...charge Tube Brazing 12 Pressure Table 13 Figures Figure 1 Prefabricated Rood Curb Specifications 5 Figure 2 Field Fabricated Curbing 5 Figure3 Elevated Mounting Platforms 7 Figure 4 Airflow and Servic...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Co...

Страница 4: ...P 3 0 6 4 6 0 5 4 1 4 2 1 1 0 2 4 1 2 1 2 1 TABLE 1 ELECTRICALDATA Q R R TABLE 2 OPTIONALFIELDINSTALLEDHEATERPACKAGES ONLY TO BE USED WITH THE AIR CONDITIONING MODELS INDICATED S Standard application...

Страница 5: ...0 2 0 4 2 3 8 0 2 0 4 2 3 8 0 2 0 4 2 9 5 1 8 1 0 0 7 0 3 0 0 2 1 5 0 0 4 1 6 5 7 6 5 2 1 1 0 5 3 1 0 0 0 3 2 0 0 4 8 3 0 0 1 6 4 7 1 2 2 6 3 4 3 4 1 1 1 8 2 6 4 5 5 0 3 0 5 0 6 0 1 8 6 0 1 0 1 0 1 9...

Страница 6: ...d be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recom...

Страница 7: ...Return Air Dimension C is length Supply Air Dimension C is length Return Air Dimension H is width Supply Sir Dimension J is width f o o R b r u C A B C D E F J H d o o H f o o R l e d o M g n i n o i...

Страница 8: ...be utilized to construct a suitable raised mounting platform See Figure 6 DUCT WORK Refer to Tables 4 5 and 5A when designing duct work for maximum static pressure available with the specific model a...

Страница 9: ...Manual 2100 324 Page 7 FIGURE 3 ELEVATEDMOUNTINGPLATFORMS MIS 1183 MIS 1185 FIGURE 4 AIRFLOWANDSERVICEACCESSCLEARANCES...

Страница 10: ...Manual 2100 324 Page 8 FIGURE 5 ROOFTOPAPPLICATION MAY ALSO BE REQUIRED FOR GROUND LEVEL INSTALLATIONS MIS 1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL ABOVE 32 F OUTSIDE TEMPERATURE MIS 1184...

Страница 11: ...ction size or larger Do not operate unit without trap Unit must be level or slightly inclined toward drain With a trap installed on a unit located in an unconditioned area water in the trap may freeze...

Страница 12: ...g at full load maximum amperage operating condition WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse size Each outdoor unit is marked with a Minimum Circui...

Страница 13: ...Manual 2100 324 Page 11 FIGURE 8 LOWVOLTAGEWIRING MIS 1180...

Страница 14: ...tomatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation HEATING A circuit R W1 is completed on each heating cycle energ...

Страница 15: ...pump unit model The lockout features both soft and manual are a function of the Compressor Control Module ADJUSTMENTS ADJUSTABLE DELAY ON MAKE AND DELAY ON BREAK TIMER The potentiometer is used to sel...

Страница 16: ...at joint l e d o M A n o i s n e m i D 3 A 2 4 1 1 P 1 A 8 4 1 1 P 1 A 0 6 0 1 P 5 7 1 5 7 1 5 7 1 TABLE 9 The above suction line temperatures are based upon 80 F dry bulb 67 F wet bulb 50 RH temperat...

Страница 17: ...6 e d i S w o L e d i S h g i H 3 7 3 0 2 4 7 7 1 2 5 7 1 3 2 6 7 6 4 2 8 7 4 6 2 9 7 8 7 2 0 8 4 9 2 1 8 2 1 3 2 8 0 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 8 7 8 0 2 9 7 2 2 2...

Страница 18: ...Manual 2100 324 Page 16...

Страница 19: ...Manual 2100 324 Page 17...

Страница 20: ...Manual 2100 324 Page 18...

Страница 21: ...Manual 2100 324 Page 19...

Страница 22: ...Manual 2100 324 Page 20...

Страница 23: ...Manual 2100 324 Page 21...

Отзывы: