ALARM OUTPUT

Alarm terminal is output connection for applications
where alarm signal is desired.  This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.

NOTE:  Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

ADJUSTABLE DELAY-ON-MAKE AND
DELAY-ON-BREAK TIMER

The potentiometer is used to select Delay-on-Break time
from 30 seconds to 5 minutes.  Delay-on-Make (DOM)
timing on power-up and after power interruptions is equal
to 2 minutes plus 10% of Delay-on-Break (DOB) setting:

0.5 minute

(30 seconds) DOB = 123 second DOM

1.0 minute

(60 seconds) DOB = 126 second DOM

2.0 minute

(120 seconds) DOB = 132 second DOM

3.0 minute

(160 seconds) DOB = 138 second DOM

4.0 minute

(240 seconds) DOB = 144 second DOM

5.0 minute

(300 seconds) DOB = 150 second DOM

Содержание P1060A1

Страница 1: ...MODELS P1142A3 P1148A1 P1060A1 INSTALLATION INSTRUCTIONS Manual 2100 324B Supersedes 2100 324A File Volume II Tab 10 Date 04 01 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead...

Страница 2: ...charge Tube Brazing 12 Pressure Table 13 Figures Figure 1 Prefabricated Rood Curb Specifications 5 Figure 2 Field Fabricated Curbing 5 Figure3 Elevated Mounting Platforms 7 Figure 4 Airflow and Servic...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Co...

Страница 4: ...P 3 0 6 4 6 0 5 4 1 4 2 1 1 0 2 4 1 2 1 2 1 TABLE 1 ELECTRICALDATA Q R R TABLE 2 OPTIONALFIELDINSTALLEDHEATERPACKAGES ONLY TO BE USED WITH THE AIR CONDITIONING MODELS INDICATED S Standard application...

Страница 5: ...0 2 0 4 2 3 8 0 2 0 4 2 3 8 0 2 0 4 2 9 5 1 8 1 0 0 7 0 3 0 0 2 1 5 0 0 4 1 6 5 7 6 5 2 1 1 0 5 3 1 0 0 0 3 2 0 0 4 8 3 0 0 1 6 4 7 1 2 2 6 3 4 3 4 1 1 1 8 2 6 4 5 5 0 3 0 5 0 6 0 1 8 6 0 1 0 1 0 1 9...

Страница 6: ...d be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recom...

Страница 7: ...Return Air Dimension C is length Supply Air Dimension C is length Return Air Dimension H is width Supply Sir Dimension J is width f o o R b r u C A B C D E F J H d o o H f o o R l e d o M g n i n o i...

Страница 8: ...be utilized to construct a suitable raised mounting platform See Figure 6 DUCT WORK Refer to Tables 4 5 and 5A when designing duct work for maximum static pressure available with the specific model a...

Страница 9: ...Manual 2100 324 Page 7 FIGURE 3 ELEVATEDMOUNTINGPLATFORMS MIS 1183 MIS 1185 FIGURE 4 AIRFLOWANDSERVICEACCESSCLEARANCES...

Страница 10: ...Manual 2100 324 Page 8 FIGURE 5 ROOFTOPAPPLICATION MAY ALSO BE REQUIRED FOR GROUND LEVEL INSTALLATIONS MIS 1176 FIGURE 6 SLAB MOUNTING AT GROUND LEVEL ABOVE 32 F OUTSIDE TEMPERATURE MIS 1184...

Страница 11: ...ction size or larger Do not operate unit without trap Unit must be level or slightly inclined toward drain With a trap installed on a unit located in an unconditioned area water in the trap may freeze...

Страница 12: ...g at full load maximum amperage operating condition WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse size Each outdoor unit is marked with a Minimum Circui...

Страница 13: ...Manual 2100 324 Page 11 FIGURE 8 LOWVOLTAGEWIRING MIS 1180...

Страница 14: ...tomatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation HEATING A circuit R W1 is completed on each heating cycle energ...

Страница 15: ...pump unit model The lockout features both soft and manual are a function of the Compressor Control Module ADJUSTMENTS ADJUSTABLE DELAY ON MAKE AND DELAY ON BREAK TIMER The potentiometer is used to sel...

Страница 16: ...at joint l e d o M A n o i s n e m i D 3 A 2 4 1 1 P 1 A 8 4 1 1 P 1 A 0 6 0 1 P 5 7 1 5 7 1 5 7 1 TABLE 9 The above suction line temperatures are based upon 80 F dry bulb 67 F wet bulb 50 RH temperat...

Страница 17: ...6 e d i S w o L e d i S h g i H 3 7 3 0 2 4 7 7 1 2 5 7 1 3 2 6 7 6 4 2 8 7 4 6 2 9 7 8 7 2 0 8 4 9 2 1 8 2 1 3 2 8 0 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 8 7 8 0 2 9 7 2 2 2...

Страница 18: ...Manual 2100 324 Page 16...

Страница 19: ...Manual 2100 324 Page 17...

Страница 20: ...Manual 2100 324 Page 18...

Страница 21: ...Manual 2100 324 Page 19...

Страница 22: ...Manual 2100 324 Page 20...

Страница 23: ...Manual 2100 324 Page 21...

Отзывы: