TROUBLESHOOTING INDOOR ECM™ BLOWER MOTORS 

(Cont’d.)

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the unit being serviced.  

DO NOT

WORK ON THE MOTOR WITH AC POWER APPLIED.  

To avoid

electric shock from the motor’s capacitors, disconnect power and wait at
least 5 minutes before opening motor.

3. It is not necessary to remove the motor from the blower assembly, nor

the blower assembly from the unit.  Unplug the two cable connectors to the
motor control assembly.  There are latches on each connector.  

DO NOT

PULL ON THE WIRES.  

The plugs remove easily when properly

released.

4. Locate the screws that retain to the motor control bracket to the

sheet metal of the unit and remove them.  Remove two (2) nuts that
retain the control to the bracket and then remove two (2) nuts that
retain sheet metal motor control end plate.  

Refer to Figure 30.

5. Disconnect the three (3) wires interior of the motor control by

using your thumb and forefinger squeezing the latch tab and the
opposite side of the connector plug, gently pulling the connector.  

DO

NOT PULL ON THE WIRES, GRIP THE PLUG ONLY.  

Refer to

Figure 30.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K
ohms.  

Refer to Figure 31.  

(Measure to unpainted motor end plate.)  If

any motor lead fails this test, do not proceed to install the control
module.  

THE MOTOR IS DEFECTIVE AND MUST BE

REPLACED.

  Installing the new control module will cause it to fail

also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

8. Reverse the steps #5, 4, 3 to reconnect the motor control to the

motor wires, securing the motor control cover plate, mounting the
control to the bracket, and mounting the motor control bracket back
into the unit.  

MAKE SURE THE ORIENTATION YOU SELECT

FOR REPLACING THE CONTROL ASSURES THE
CONTROL'S CABLE CONNECTORS WILL BE LOCATED
DOWNWARD IN THE APPLICATION SO THAT WATER
CANNOT RUN DOWN THE CABLES AND INTO THE
CONTROL.

  DO NOT OVERTIGHTEN THE BOLTS.

9. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

10. Plug the 5-pin power connector into the motor.  Even though

the plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO

NOT FORCE THE CONNECTOR.

  It plugs in very easily when

properly oriented.  

REVERSING THIS PLUG WILL CAUSE

IMMEDIATE FAILURE OF THE CONTROL MODULE.

11. Final installation check.  Make sure the motor is installed as follows:

a. Motor connectors should be oriented between the 4 o’clock

and 8 o’clock positions when the control is positioned in its
final location and orientation.

b.Add a drip loop to the cables so that water cannot enter the

motor by draining down the cables.  

Refer to Figure 32.

The installation is now complete.  Reapply the AC power to the
HVAC equipment and verify that the new motor control module is
working properly.  Follow the manufacturer's procedures for
disposition of the old control module.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 

supplied when 
replacing an 

ECM 2.0 
control.

Figure 3

ECM 

2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Figure 31

Figure 30

Figure 32

EON
5.0

Содержание I30H1

Страница 1: ...1 I30H1D I36H1D I42H1D I48H1D I60H1D I TEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 549G...

Страница 2: ...Unit Side 8 Wall Mounting Bracket Location 9 Bracket Wall Sect View Wood Framed Install 10 Figure 3 Center of Gravity 11 Figure 4 Req Clearances Rec Access 12 Figure 5 Compressor Shipping Bolts 13 Fi...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...ation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than...

Страница 5: ...ic Coated ID OD Coil CONTROLS X 24V Terminal Block Only w o CompleteStat 1 CompleteStat THO Temp Humidity Occupancy 2 CompleteStat THO w CO2 3 CompleteStat THO w Ethernet 4 CompleteStat THO w CO2 Ethe...

Страница 6: ...A 1 5 1 A 1 0 2 A 1 8 0 2 0 3 2 1 1 2 r o 1 2 r o 1 2 r o 1 2 r o 1 4 3 4 5 9 5 5 8 5 8 0 1 1 0 5 0 6 0 7 0 9 0 9 0 1 1 8 6 6 3 3 2 0 1 0 1 8 8 8 6 5 3 5 3 5 3 9 5 6 2 2 5 2 5 2 5 5 4 5 4 5 4 0 6 0 3...

Страница 7: ...1 5 47 3 46 1 8 With Sides Removed Vent Intake Disconnect Electrical Air Filters Vent Exhaust Door Latch Locking Filters Return Air 2 12 x 20 Door Latch Locking Air Filters 2 Washable Hinges 4 Lift Of...

Страница 8: ...ttempt to do this manually Failure to do so could result in the unit tipping over causing bodily injury and or damage to the unit 7 The top section can be forked from either the RH or LH side See Figu...

Страница 9: ...nches Figure 7C Several construction options are available for unit installation of the IZ Series Serviceability and filter access must be considered before installing See Figure 5D for required clear...

Страница 10: ...l Top Centered on Higher Sill Heights Acheivable With Base Kit Wall Opening Sleeve Mounting Hole Locations FLOOR MOUNTING HOLE CENTERLINES 17 8 56 8 20 6 7 20 2 8 8 29 32 7 1 20 7 8 43 7 42 3 4 Min 94...

Страница 11: ...O O L F T N E V O N n o i s n e m i D X n o i s n e m i D Y n o i s n e m i D Z n o i s n e m i D Z B A 1 H 0 3 I 4 1 4 2 3 4 7 4 C 1 H 0 3 I 4 1 4 2 3 4 7 4 B A 1 H 6 3 I 4 1 4 2 3 4 7 4 C 1 H 6 3 I...

Страница 12: ...FOR LEFT SIDE ACCESS 12 MIN 12 MIN 12 MIN 12 MIN 0 REQUIRED 12 RECOMENDED 0 REQUIRED 12 RECOMENDED CLOSET CONSTRUCTION TOP VIEW LEFT CORNER CONSTRUCTION TOP VIEW RIGHT CORNER CONSTRUCTION TOP VIEW FI...

Страница 13: ...Manual 2100 549G Page 13 of 59 FIGURE 5 COMPRESSOR SHIPPING BOLTS FIGURE 6 REMOVAL OF AIR DUCT COMPRESSOR SHIPPING BOLT COMPRESSOR SHIPPING BOLT CRV ERV AIR DUCT...

Страница 14: ...NDED TO BOTTOM OF ROOF 9 7 MINIMUM OR FIXED CEILING FLOOR OR FIXED CEILING BOTTOM OF ROOF SUSPENDED CEILING 20 MINIMUM 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED MINIMUM 12 4 MI...

Страница 15: ...ENDED TO BOTTOM OF ROOF 9 10 MINIMUM OR FIXED CEILING 3 RISER FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED 12 MINIMUM 4 MINIMUM FROM TOP OF UNIT TO DUCT BOTTOM MIS 2989 B FLOOR OR FIXED CEILING BOTTO...

Страница 16: ...IXED CEILING 6 RISER 9 8 MINIMUM REQUIRED INSTALLATION HEIGHT BOTTOM OF ROOF FLOOR OR FIXED CEILING SUSPENDED CEILING MINIMUM 20 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT MIS 2988 B TURNING VANES RECOMM...

Страница 17: ...or a duct supply air system The IPBDF Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille When used with a ducted supply an I...

Страница 18: ...it about 12 inches in from the front on both the left and right side are drain holes in the bottom of the base These holes are covered with insulation and are not visible They are located very close t...

Страница 19: ...k bead to Apply liberal amount of caulk to back of flange before installing Use 4 1 1 2 Long Screws to Sleeve Attach Louver Grille to Outer Unit Fan Shroud to Outer Sleeve to Unit Back to Attach Inner...

Страница 20: ...9 INTERIOR FLOOR INSIDE WALL SLEEVE AREA BETWEEN INSULATED WALL AND SLEEVE OUTSIDE WALL SIZE VARIES OUTDOOR GRILLE FILL INSULATION I TEC UNIT INSULATED DRAIN AREA INSULATED WITH 6 BATT MATERIAL MIS 29...

Страница 21: ...information and maximum fuse or HACR Type circuit breaker size Each unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current D...

Страница 22: ...e g a t s 3 c i n o r t c e l E e l b a m m a r g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 7 6 0 3 0 4 8 Y L R D C L 0 4 W 2 T D...

Страница 23: ...Term Strip R 3 SC W1 E A D L O B Y2 Y1 24V G COM W2 Completestat Model CS9B THO or Model CS9BE THO SC SC Thermostat W1 E A YO D L O B Y2 Y1 R G C W2 Bard 8403 060 MIS 3016 1 Additional wire required f...

Страница 24: ...O B Y2 Y1 R G C W2 Bard 8403 060 5 MIS 3017 CRV Wiring Harness 1 Additional wire required for dehumidification models 2 Not needed below 15KW 3 to N C fire alarm circuit if emergency shutdown require...

Страница 25: ...actory installed jumper Remove jumper and connect 4 Connect to G terminal when thermostat has Occupancy Signal Voltage without Occupance Signal is used Install a jumper between G and A only when therm...

Страница 26: ...ed for dehumidification models 2 Not needed below 15KW BROWN WHITE 3 to N C fire alarm circuit if emergency shutdown required Factory installed jumper Remove jumper and connect without Occupance Signa...

Страница 27: ...jumper Remove jumper and connect 4 Connect to G terminal when thermostat has Occupancy Signal without Occupance Signal is used Install a jumper between G and A only when thermostat 1 5 4 5 ERV Wiring...

Страница 28: ...n thermostat has Occupancy Signal C 2 2 ERV Wiring Harness Voltage 1 W2 2 Additional wire required for dehumidification models Bard 8403 067 4 3 MIS 3021 A 4 5 1 to N C fire alarm circuit if emergency...

Страница 29: ...humidification models 4 PURPLE WHITE C G Model CS9B THOC or Term Strip 6 YELLOW BLACK 2 MIS 3270 O B Y1 4 PURPLE 7 2 YELLOW Not needed below 15KW Y0 ORANGE BLACK WHITE RED WHITE L Completestat W1 E G...

Страница 30: ...ing multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system...

Страница 31: ...ng power in such a way as to cause rotation in the reverse direction verification of proper rotation must be made Verification of proper rotation direction is made by observing that suction pressure d...

Страница 32: ...1 heat completes R Y1 circuit pulling in compressor contactor starting compressor and outdoor motor R G also make starting indoor blower motor HEATING STAGE 2 Circuit R Y1 Y2 makes at the thermostat e...

Страница 33: ...P terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals It may take up to 15 seconds with the S...

Страница 34: ...electronic thermostat with auxiliary terminal to control the CRV based on daily programmed occupance periods Bard markets and recommends Bard Part 8403 060 programmable electronic thermostat 2 Use Bar...

Страница 35: ...OPTION INTAKE EXHAUST SPEEDS BROWN WHITE BLACK BLUE ORANGE NOM CFM BLACK BLUE WIRE COLOR SPEED RED WIRE WITH WHITE TRACE 300 375 450 525 LO MED LO MED HI HI RED Move brown white wire to corresponding...

Страница 36: ...CRV SPEED CHANGE TERMINAL ACCESS REMOVE 5 SCREWS FROM CRV DOOR TO ACCESS CRV COMPONENTS MIS 3023 CRV INTAKE BLOWER NOTE CRV EXHAUST BLOWER IS BEHIND INTAKE BLOWER BLOWER SPEED CONTROL LOCATION BLOWER...

Страница 37: ...re set levels of ventilation CFM available These are 300 375 450 and 525 CFM of ventilation air This ventilation package is shipped from the factory set on the 375 CFM ventilation level while the Econ...

Страница 38: ...of relay R2 High Ambient Relay FIGURE 23 ECONOMIZER CONTROL CIRCUIT If outdoor temperature is above outdoor thermostat setpoint On call from CompleteStat for first stage cooling YO thermostat signal p...

Страница 39: ...CFM MIS 3271 HEATING MODE OPERATION CompleteStat should never energize YO terminals in conjunction with B so relay R2 will never energize and neither will Economizer Ventilation Speed Y1 and Y2 signal...

Страница 40: ...re freezing of moisture in the heat transfer wheel can occur Consult the factory if this possibility exists The I TEC ERV can be controlled in different ways It can be turned ON OFF with an occupancy...

Страница 41: ...Then perform the following steps 1 Open front swinging doors of main unit by popping front door latches 2 Throw main power disconnect to the OFF position to eliminate risk of injury or death due to el...

Страница 42: ...0 5 9 0 8 0 9 5 1 3 0 2 7 9 0 7 8 1 2 3 3 5 0 2 8 1 3 6 5 1 2 4 1 5 2 3 6 2 0 0 1 8 5 2 2 8 1 4 7 3 7 1 5 4 3 5 8 2 0 2 1 0 6 0 1 2 0 8 4 6 0 8 5 4 1 0 1 1 4 1 1 4 3 4 8 6 7 9 5 7 5 6 4 1 2 0 2 7 9 4...

Страница 43: ...ng blinks for the TEN COUNT of the FLOW RATE INDEX which then is immediately followed by fast blinks which indicate the second digit For example a Flow Index of 23 would be two long blinks followed by...

Страница 44: ...Manual 2100 549G Page 44 of 59 FIGURE 26 VENTILATION AIRFLOW DIAGRAM EXHAUST Return Air Indoor Air VENT Outdoor Air BLOWER BLOWER INTAKE Supply Air VENT SUPPLY BLOWER MIS 3024...

Страница 45: ...Page 45 of 59 FIGURE 27 ERV ACCESS ERV DOOR TO ACCESS ERV COMPONENTS ASSEMBLIES REMOVE 5 SCREWS FROM PANEL LOCATION MIS 3025 ERV CONTROL ERV CASSETTE NOTE ERV EXHAUST BLOWER IS BEHIND INTAKE BLOWER E...

Страница 46: ...equipment damage Make sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes Use copper conductors only Use electrostatic dischar...

Страница 47: ...gure below Finish installing wiring the control Then refer to Figure 20 and the building ventilation specifications to decide what the maximum ventilation rate desired is and what the minimum maximum...

Страница 48: ...2 low output range Sets the CO2 concentration for the lowest output 4 mA or 0 VDC Low limit 0 PPM Factory setting 0 PPM High limit 2000 5000 PPM depending on model COH CO2 high output range Sets the C...

Страница 49: ...to remove oils grease tars and dirt that can impede performance or generate odors Washing of the desiccant surfaces is required to remove contaminate buildups that can reduce adsorption of water mole...

Страница 50: ...based cleaners aromatic solvents temperatures in excess of 170 F or steam Damage to the wheel may result Do not disassemble and immerse the entire heat wheel in a soaking solution as bearing and othe...

Страница 51: ...n a r t e h t e g a t l o v t i n u e v a h t o n s e o d r e h t i e t i n u e h T l a n g i s t u p t u o r o s s e r p m o C r o f k c e h C 0 1 C C C n e e w t e b C A s t l o v 4 2 e r e h t s I...

Страница 52: ...5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 4 1 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4 7 5 3 3 4 3 6 2 3 3 2 7 1 3 0 4 8...

Страница 53: ...it is tight on the motor shaft Also ensure the motor is secure in its mounting system and the mounting system is secure to the unit c The Bard I TEC is equipped with a low ambient control pressure swi...

Страница 54: ...RODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS Always mount the replacement motor and control according to the manufacturers specifications using all required hardware to reduce vibration Make s...

Страница 55: ...ne if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down...

Страница 56: ...er to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into...

Страница 57: ...CTOR MOTOR HALF R O T C E N N O C R E W O P R E D A E H B W P 0 5 4 9 0 5 3 1 P M A N I P n o i t p i r c s e D 1 r o f 2 n i P o t 1 n i P r e p m u J t u p n I e n i L C A V 0 2 1 y l n O 2 3 d n u...

Страница 58: ...i H 5 2 1 3 0 2 6 2 1 5 2 2 7 2 1 8 4 2 8 2 1 1 7 2 9 2 1 3 9 2 9 2 1 6 1 3 0 3 1 9 3 3 1 3 1 1 6 3 2 3 1 4 8 3 4 3 1 1 1 4 5 3 1 7 3 4 6 3 1 4 6 4 8 3 1 1 9 4 9 3 1 7 1 5 0 4 1 4 4 5 B D 0 8 B W 7 6...

Страница 59: ...2 1 3 8 1 0 3 1 5 0 2 1 3 1 6 2 2 2 3 1 8 4 2 3 3 1 9 6 2 3 3 1 1 9 2 4 3 1 3 1 3 5 3 1 4 3 3 6 3 1 6 5 3 7 3 1 1 8 3 9 3 1 7 0 4 0 4 1 2 3 4 2 4 1 8 5 4 3 4 1 4 8 4 4 4 1 9 0 5 B D 0 8 B W 7 6 e d i...

Отзывы: