Manual 2100-759
Page
7 of 16
7. Make the following connections from the CRV wire
harness to the screw terminals on the low voltage
terminal strip:
• Brown/White wire to the "01" terminal
• Black/White wire to the "C" terminal
• Red/White wire to the "R" terminal
• Orange wire to the "G" terminal
• Yellow/White wire to the "Y" terminal
• Purple wire to the "Y1" terminal
8. Close control panel cover
9. Replace left filter support, filter and four (4)
screws in condenser grille.
10. Re-install the blower access panel at top of unit
and secure with sheet metal screws.
11. Ventilator Checkout
A. Resupply power to unit.
B. Move "PP" jumper on CRV control board (Bard
P/N 8201-167) to the 30-minute position.
C. Ventilator should open to the position
set by the "PP" potentiometer. Cycle the
potentiometer from full open to full closed.
Observe damper blade operation throughout
travel to assure free, unobstructed movement.
Return "PP" potentiometer to desired position
for pre-purge airflow (refer to graphs 1 and 2
on pages xx-xx). Move the "PP" jumper to the 0
position. Ventilator should open to the position
set by the "OCC" potentiometer.
Energize Y; ventilator should open to the
position set by the "Y1" potentiometer.
Energize Y1; ventilator should open to the
position set by the "Y2" potentiometer.
D. De-energize evaporator blower. Damper blade
should close.
E. If pre-purge function is desired, move "PP"
jumper to the 30-, 60-, or 90-minute position
depending on desired pre-purge time.
F. This completes ventilator checkout.
12. Replace mist eliminator. Be sure it is installed with
the drain holes to the bottom.
13. Remove blank off plate or barometric fresh air
damper installed on service access door. Plug four
(4) mounting holes with the plastic plugs provided
with the ventilator.
14. Replace service access panel.
15. Ventilator is now ready for operation.
16. If retrofitting an existing unit, thermostat
connection may change. See latest revision of
manual 2100-507, 2100-516 or 2100-554 for
proper thermostat connections to low voltage
terminal strip with this CRVS.
CO
2
Control
For CO
2
-based control, add a CO
2
sensor/controller
(Bard P/N 8403-096) to the wall and run additional
optional wires as shown in Figure 5 on page 9.
The CO
2
controller also must be re-configured from the
standard default settings as it comes out of the box.
See Figure 4 on page 8 for complete details.