background image

Manual 7960-902
Page 

4 of 6

MENU DESCRIPTIONS
RON 

Relay on set point

 

Sets the CO2 concentration which the optional relay 
is energized.

ROF 

Relay off set point

 

Sets the CO2 concentration which the optional 
relay is de-energized. Setting value lower than 
RON provides direct action for detecting high 
concentrations of CO2. Setting value higher than 
RON provides indirect action for detecting low 
concentrations of CO2. Up button and Down button 
on the LCD display will be lit to indicate when the 
relay is energized.

 

Low limit: 

0 PPM

 

Factory setting:  950 PPM

 

High limit: 

2000/5000 PPM 

 

 

(depending on model)

DSP 

Display configuration

 

Determines the LCD display configuration during 
normal operation. The LCD display can indicate 
the CO2 concentration, temperature and CO2 
concentration.

 

CT  CO2 concentration and temperature

 

C  CO2 concentration only

 

T  Temperature only

UNI

  Units selection

 

Temperature and barometric pressure 
measurements can be displayed in US engineering 
units or SI engineering units. The factory default is 
to display US engineering units.

 

US units °F for temperature and in Hg for 
barometric pressure 

 

SI units °C for temperature and hPa for barometric 
pressure

COL

  CO2 low output range

 

Sets the CO2 concentration for the lowest output  
(4 mA or O VDC).

 

Low limit: 0 PPM

 

Factory setting: 0 PPM

 

High limit: 2000/5000 PPM (depending on model)

COH

  CO2 high output range

 

Sets the CO2 concentration for the highest output  
(20 mA, 5 VDC or 1O VDC). When COH is set above 
COL, the transmitter is direct acting and the output 
will increase with an increase in CO2 level. When 
COH is below COL, the transmitter is reverse acting 
and the output will increase with a decrease in CO2 
level.

 

Low limit: 0 PPM

 

Factory setting: 2000/5000 PPM (depending on 
model)

 

High limit: 2000/5000 PPM (depending on model)

AAC

  Average Atmospheric Carbon Dioxide value

 

Sets the value at which the sensors automatic 
background calibration will reference. Factory 
setting derived from research from the National 
Oceanic and Atmospheric Administration (NOAA).

 

Low limit: 200 PPM

 

Factory setting: Current NOAA value

 

High limit: 9999 PPM

TOL

  Temperature low output range (Series CDT with 

active temperature only) 

 

Sets the temperature for the lowest output (4 mA or 
O VDC).

 

Low limit: 32.0°F/0.0°C

 

Factory setting: 32.0°F/0.0°C

 

High limit: 122.0°F/150.0°C

TOH

  Temperature high output range (Series CDT with 

active temperature only)

 

Sets the temperature for the highest output (20 
mA, 5 VDC or 10 VDC). When TOH is set above 
TOL, the transmitter is direct acting and the output 
will increase with an increase in temperature. When 
TOH is below TOL, the transmitter is reverse acting 
and the output will increase with a decrease in 
temperature.

 

Low limit: 32.0°F/0.0°C

 

Factory setting: 122.0°F/150.0°C

 

High limit: 122.0°F/150.0°C

BAR

  Barometric pressure

 

Sets the typical barometric pressure for the 
location where the transmitter is mounted. The 
factory setting is for standard pressure at sea 
level. Adjusting the barometric pressure gives a 
more accurate measurement, especially at higher 
elevations. Refer to the elevation charts in Table 1 
for typical barometric pressures at a given elevation.

 

Low limit: 20.0 in Hg/677 hPa

 

Factory setting: 29.9 in Hg/1013 hPa

 

High limit: 32.0 in Hg/1084 hPa

CAL

 Calibration

 

Calibrates the carbon dioxide sensor to a known gas 
value. Read 

CALIBRATING SENSOR

 below before 

using this feature. Hold Enter button for 5 seconds.

RST

  Reset to Factory Defaults

 

Resets all menu settings lo their default value, and 
clears zero and span.

 

YES: Press and hold -- button for several seconds to 
reset settings 

 

NO: Press -- button to exit this menu item without 
resetting

Содержание 8403-096

Страница 1: ...onal relay with user adjustable set points can be used to control exhaust fans open actuated windows or dampers or signal a light or horn For applications that require visual indication the Series CDT can be ordered with an integral LCD display Model A 449 or Model A 449A remote LCD display that can plug into the mini connector port on the side of the transmitter The CDT can be configured to displ...

Страница 2: ...llation and wiring to prevent equipment damage Avoid locations where severe shock or vibration excessive moisture or corrosive fumes are present Do not exceed ratings of this device permanent damage not covered by warranty may result Upon powering the transmitter the firmware version will fiash on the display A warm up period of 30 minutes is required for the transmitter to adjust to the current C...

Страница 3: ...CD display remote display Model A 449 can be used to display the temperature and carbon dioxide The mini USB plug of the remote display plugs into the receptor on the side of the housing After a short warm up time the display will begin to show the current temperature and carbon dioxide measurements unless configured by the user to show only temperature or only carbon dioxide EDITING MENU PARAMETE...

Страница 4: ...g 2000 5000 PPM depending on model High limit 2000 5000 PPM depending on model AAC Average Atmospheric Carbon Dioxide value Sets the value at which the sensors automatic background calibration will reference Factory setting derived from research from the National Oceanic and Atmospheric Administration NOAA Low limit 200 PPM Factory setting Current NOAA value High limit 9999 PPM TOL Temperature low...

Страница 5: ...ppear Step 10 Exit the parameter menu by pressing and holding the Up and Down buttons simultaneously for 5 seconds or wait 10 seconds Step 11 Flow the full scale reference gas at 0 3 SLPM for 5 minutes Step 12 Repeat steps 6 through 8 Step 13 Press the Up arrow for 3 seconds All dashes will appear on the display then release the button Then after 10 seconds SET will disappear FIGURE 6 Calibration ...

Страница 6: ...23460 00 25392 00 7617 60 101 95 1019 5 53780 00 10 50 0 18780 00 19901 00 5970 30 103 90 1039 0 41560 00 15 59 0 15130 00 15712 00 4713 60 105 85 1058 5 32340 00 20 68 0 12260 00 12493 00 3747 90 107 79 1077 9 25360 00 25 77 0 10000 00 10000 00 3000 00 109 74 1097 4 20000 00 30 86 0 8194 00 8057 00 2417 10 111 67 1116 7 15892 00 35 95 0 6752 00 6531 00 1959 30 113 61 1136 1 12704 00 40 104 0 5592...

Отзывы: