Manual 7960-902
Page 

2 of 6

SPECIFICATIONS

Sensor:

 Single beam, dual-wavelength NDIR.

Range:

 CO2: 0 to 2000 or Oto 5000 PPM (depending on 

model); Temperature: 32 to 122°F (0 to 50°C).

Accuracy:

 CO2: ±40 PPM ±3% of reading; Temperature: 

±1°C @ 25°C.

Temperature Dependence:

 ±8 PPM/°C at 1100 PPM.

Non-Linearity:

 16 PPM.

Pressure Dependence:

 0.13% of reading per mm of Hg.

Response Time:

 2 min for 99% step change. 

Temperature Limits:

 32 to 122°F (0 to 50°C). 

Humidity Limits:

 10 to 95% RH (non-condensing). 

Power Requirements:

 16-35 VDC or 19-28 VAC. 

Power Consumption:

 Average: 2 w; Peak: 3.75 w.

Output:

 Current: 4-20 mA (max. 500 O); Voltage: 0-5 

VDC or 0-10 VDC (min. 500 O); Relay: SPST NO rated 
2A@ 30 VDC; RTD or thermistor per r-t curves on page 6 
(depending on model).

Weight:

 4.4 oz (125 g).

Agency Approvals:

 CE.

INSTALLATION

Disconnect power supply before 
installation to prevent electrical shock and 
equipment damage.

Make sure all connections are in accordance with the job 
wiring diagram and in accordance with national and local 
electrical codes. Use copper conductors only.

Use electrostatic discharge precautions 
(e.g., use of wrist straps) during 
installation and wiring to prevent 
equipment damage.
Avoid locations where severe shock or 
vibration, excessive moisture or corrosive 
fumes are present.
Do not exceed  ratings of this device, 
permanent damage not covered by 
warranty may result.
Upon powering the transmitter, the 
firmware version will fiash on the display. A 
warm up period of 30 minutes is required 
for the transmitter to adjust to the current 
CO2 concentration.
Self calibration feature of the transmitter 
requires exposure to normal outdoor 
equivalent carbon dioxide level once every 
30 days.

MOUNTING

1.  Push tab on top and bottom of cover and lift cover 

from back plate (see Figure 1).

2.  Select the mounting location, away from diffusers, 

lights or any external influences.

3.  Mount transmitter on a vertical surface to a standard 

electrical box using the two #6 M2C type screws 
provided.

FIGURE 1

Removal of Cover from Back Plate

WIRING

Use maximum 18 AWG wire for wiring to terminals. Refer 
to Figure 4 for wiring information.

DIP SWITCH SETTINGS

To access the DIP switch, remove the cover of the unit as 
shown in Figure 2. The DIP switch is located on the back 
of the circuit board.

FIGURE 2

Diagram of Circuit Board

DIP Switch

FIGURE 3

DIP Switches

4.  Pull wires through sub base hole and make necessary 

connections.

5.  Reattach cover to base plate.

Содержание 8403-096

Страница 1: ...onal relay with user adjustable set points can be used to control exhaust fans open actuated windows or dampers or signal a light or horn For applications that require visual indication the Series CDT can be ordered with an integral LCD display Model A 449 or Model A 449A remote LCD display that can plug into the mini connector port on the side of the transmitter The CDT can be configured to displ...

Страница 2: ...llation and wiring to prevent equipment damage Avoid locations where severe shock or vibration excessive moisture or corrosive fumes are present Do not exceed ratings of this device permanent damage not covered by warranty may result Upon powering the transmitter the firmware version will fiash on the display A warm up period of 30 minutes is required for the transmitter to adjust to the current C...

Страница 3: ...CD display remote display Model A 449 can be used to display the temperature and carbon dioxide The mini USB plug of the remote display plugs into the receptor on the side of the housing After a short warm up time the display will begin to show the current temperature and carbon dioxide measurements unless configured by the user to show only temperature or only carbon dioxide EDITING MENU PARAMETE...

Страница 4: ...g 2000 5000 PPM depending on model High limit 2000 5000 PPM depending on model AAC Average Atmospheric Carbon Dioxide value Sets the value at which the sensors automatic background calibration will reference Factory setting derived from research from the National Oceanic and Atmospheric Administration NOAA Low limit 200 PPM Factory setting Current NOAA value High limit 9999 PPM TOL Temperature low...

Страница 5: ...ppear Step 10 Exit the parameter menu by pressing and holding the Up and Down buttons simultaneously for 5 seconds or wait 10 seconds Step 11 Flow the full scale reference gas at 0 3 SLPM for 5 minutes Step 12 Repeat steps 6 through 8 Step 13 Press the Up arrow for 3 seconds All dashes will appear on the display then release the button Then after 10 seconds SET will disappear FIGURE 6 Calibration ...

Страница 6: ...23460 00 25392 00 7617 60 101 95 1019 5 53780 00 10 50 0 18780 00 19901 00 5970 30 103 90 1039 0 41560 00 15 59 0 15130 00 15712 00 4713 60 105 85 1058 5 32340 00 20 68 0 12260 00 12493 00 3747 90 107 79 1077 9 25360 00 25 77 0 10000 00 10000 00 3000 00 109 74 1097 4 20000 00 30 86 0 8194 00 8057 00 2417 10 111 67 1116 7 15892 00 35 95 0 6752 00 6531 00 1959 30 113 61 1136 1 12704 00 40 104 0 5592...

Отзывы: