Manual 7960-902
Page 

3 of 6

DIP Switch Position 1: CO2 Output Selection

ON: Output set to voltage output 
OFF: Output set to current output

DIP Switch Position 2: Temperature Output Selection

ON: Output set to voltage output 
OFF: Output set to current output

DIP Switch Positions 3 & 4: Current or Voltage Output 

Range Selection

Output Range

DIP Switch 3 

Position

DIP Switch 4 

Position

2-10 V
4-20 mA

ON

OFF

0-10 V
0-20 mA

OFF

OFF

0-5 V
0-10 mA

OFF

ON

1-5 V
2-10 mA

ON

ON

DIP Switch Position 5: Menu Access

ON: Menu Enabled 
OFF: Menu Disabled

CURRENT/VOLTAGE OUTPUT

On the Series CDT, the transmitter may be wired for 
current or voltage output for both carbon dioxide and 
temperature. The transmitter can be powered with either 
16-35 VDC or 19-28 VAC. Wire the transmitter according 
to Figure 4.

Optional relay can be used as either a dry 
contact or low voltage switched circuit up 
to 2 A at 30 VDC

FIGURE 4

Active Output Wiring Diagram

POWER
SUPPLY

TEMP

RECEIVER

CO2

RECEIVER

REMOTE DISPLAY

For models that are ordered without an integral LCD 
display, remote display Model A-449 can be used to 
display the temperature, and carbon dioxide. The mini 
USB plug of the remote display plugs into the receptor on 
the side of the housing. After a short warm up time, the 
display will begin to show the current temperature and 
carbon dioxide measurements unless configured by the 
user to show only temperature or only carbon dioxide.

EDITING MENU PARAMETERS

Before any adjustment can be made to the transmitter, 
the Menu Lockout Dip Switch must be set to the “On” 
position (See Figure 3)

ACCESSING MENU PARAMETERS

Step 1: To enter the menu structure, press Up button and 

Down button simultaneously for 5 seconds (display 
will show RON parameter).

Step 2: Press Up button or Down button to cycle between 

menu items.

Step 3: Press Enter to edit the value for the displayed 

menu item (SET will appear on display).

Step 4: Press Up button or Down button to adjust the 

value of the menu item. Step 5: Press Enter 
button to save the changes (SET will disappear).

Step 6: Repeat Steps 2 through 5 for each of the 

parameters.

Step 7: To exit the menu at any time, press and hold Up 

button and Down button simultaneously for 5 
seconds or wait 10 seconds without pushing any 
buttons.

FIGURE 5

Side View of Transmitter

Содержание 8403-096

Страница 1: ...onal relay with user adjustable set points can be used to control exhaust fans open actuated windows or dampers or signal a light or horn For applications that require visual indication the Series CDT can be ordered with an integral LCD display Model A 449 or Model A 449A remote LCD display that can plug into the mini connector port on the side of the transmitter The CDT can be configured to displ...

Страница 2: ...llation and wiring to prevent equipment damage Avoid locations where severe shock or vibration excessive moisture or corrosive fumes are present Do not exceed ratings of this device permanent damage not covered by warranty may result Upon powering the transmitter the firmware version will fiash on the display A warm up period of 30 minutes is required for the transmitter to adjust to the current C...

Страница 3: ...CD display remote display Model A 449 can be used to display the temperature and carbon dioxide The mini USB plug of the remote display plugs into the receptor on the side of the housing After a short warm up time the display will begin to show the current temperature and carbon dioxide measurements unless configured by the user to show only temperature or only carbon dioxide EDITING MENU PARAMETE...

Страница 4: ...g 2000 5000 PPM depending on model High limit 2000 5000 PPM depending on model AAC Average Atmospheric Carbon Dioxide value Sets the value at which the sensors automatic background calibration will reference Factory setting derived from research from the National Oceanic and Atmospheric Administration NOAA Low limit 200 PPM Factory setting Current NOAA value High limit 9999 PPM TOL Temperature low...

Страница 5: ...ppear Step 10 Exit the parameter menu by pressing and holding the Up and Down buttons simultaneously for 5 seconds or wait 10 seconds Step 11 Flow the full scale reference gas at 0 3 SLPM for 5 minutes Step 12 Repeat steps 6 through 8 Step 13 Press the Up arrow for 3 seconds All dashes will appear on the display then release the button Then after 10 seconds SET will disappear FIGURE 6 Calibration ...

Страница 6: ...23460 00 25392 00 7617 60 101 95 1019 5 53780 00 10 50 0 18780 00 19901 00 5970 30 103 90 1039 0 41560 00 15 59 0 15130 00 15712 00 4713 60 105 85 1058 5 32340 00 20 68 0 12260 00 12493 00 3747 90 107 79 1077 9 25360 00 25 77 0 10000 00 10000 00 3000 00 109 74 1097 4 20000 00 30 86 0 8194 00 8057 00 2417 10 111 67 1116 7 15892 00 35 95 0 6752 00 6531 00 1959 30 113 61 1136 1 12704 00 40 104 0 5592...

Отзывы: