Bard 8403-060 Скачать руководство пользователя страница 6

997-060180-4d 

 

6

 
 

 OUTDOOR SENSOR 

 
If the system is equipped with an optional outdoor temperature sensor, 
Bard PN 8403-061(1125-2), it is possible to allow the controller to operate 
the heat pump system in the most efficient manner possible.  By setting the 
COOLING LOCKOUT, ELECTERIC HEAT LOCKOUT, and the HEAT 
PUMP LOCKOUT you can avoid running the heat pump when the outdoor 
temperature is too low to operate efficiently.  You can also avoid running 
the electric heat when the outdoor temperature is high enough to allow the 
heat pump to maintain a comfortable temperature. 
 
COOLING LOCKOUT is defaulted to NONE which is disabled.  
Selectable range is from 40˚-55˚ in 5˚ increments.   
ELECTRIC HEAT LOCKOUT is defaulted to NONE which is disabled.  
Selectable range is from 5˚-60˚ in 5˚ increments. 
HEAT PUMP LOCKOUT is defaulted to NONE which is disabled.  
Selectable range is from 5˚-50˚ in 5˚ increments.  OPERATION:  If 
compressor is turned off due to outdoor temperature going below set-point 
while the compressor is operating it will stay off until the room thermostat 
set-point is reached even if the temperature at the outdoor temperature rises 
above the outdoor sensor setting.  The next operating cycle will be based 
on what the temperature is at the outdoor sensor at time of call for heating. 
The OUTDOOR sensor is connected to the OD and GND terminals on the 
controller, and when connected, the outdoor temperature is automatically 
displayed on the controller screen. 
 

REMOTE INDOOR SENSOR 

 

  Allows selection of the optional remote sensor, Bard PN 8403-062(1125-

50),  to determine indoor temperature.  (NOTE: If no Remote Indoor 
Sensor is connected during initial configuration process, the Remote Indoor 
Sensor selection does not display in the Installer Menu.  If a Remote Indoor 
Sensor is connected at a later date, the controller will recognize the 
connection, and the selection step will automatically be added to the 
Installer Menu.)  Options are REMOTE SENSOR ONLY, AVERAGE 
WITH STAT, and NO REMOTE SENSOR.  Selecting  REMOTE 
SENSOR ONLY, allows the indoor sensor to take control of temperature 
sensing(if connected).  Selecting AVERAGE WITH STAT, will average 
the temperature of the on-board sensor to the indoor sensor, and selecting 
NO REMOTE SENSOR, will use the on-board temperature sensor.  
The REMOTE SENSOR is connected to the ID and GND on the controller 
terminals. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

24V CONTROL WIRING 

All excess wire should be pushed back into the wall as far as possible.  Excess 
wire inside the thermostat plastic case may interfere with the air flow across 
the temperature sensor.  

THERMOSTAT CONNECTIONS 

 

     

C – 24V Common for Control Circuit 

 

      

R – 24V Supply for Control Circuit 

 

     

W1/E – E Heat/ First Stage Heat 

 

     

W2 –  Second Stage Heat 

               

O/B – Reversing Valve - energized in HEAT mode(B is default) 

 

     

Y1 – 1st Stage Compressor / Cooling / Heating 

 

     

Y2 – 2nd Stage Compressor / Cooling / Heating 

 

     

Y0/D – Economizer / Dehumidifier output

*

 

 

     

A – Ventilation Output 

 

     

G – Fan 

 

     

L – Input for CS2000A or compressor fault 

 

       

A+, B – Not Used. 

    

  GND – Ground ** 

      

  OD – Outdoor Temperature Sensor **  

 

ID – Indoor Temperature Sensor ** 

 

*

Controller must be configured for “No Economizer”   

for dehumidification control to be active 
 
**Shielded  twisted  pair  should  be  used  for  remote 
Indoor  and  Outdoor  Sensors  to  avoid  any  possible 
interference  from  other  electrical  systems  or  other 
external  sources.  The  shield  (drain)  should  be 
connected to 24V Common (C) at the controller. 

 

 
 

 
 

 

For specific 24V control circuit wiring refer to the Bard Low Voltage 
Control Circuit Wiring manuals or the equipment installation 
instructions packaged with each piece of equipment.
 