EVERY DAY

WAKE

HEAT   COOL

FAN

70

78       AUTO

LEAVE

8:00A

62        85       AUTO

RETURN  

5:00P       70        78       AUTO

SLEEP     

10:00P     62

82       AUTO

SAVE

PREVIOUS

6:00A

EVENTS PER DAY

2 – RESIDENTIAL

2 - BUSINESS

SELECT OPTION 

∇∆

PREVIOUS

4 - RESIDENTIAL

 

EVERY DAY

DAY

HEAT   COOL

FAN

70

78       AUTO

NIGHT     

10:00P     62

82       AUTO

SAVE

PREVIOUS

6:00A

 

EVERY DAY

ACTIVE

HEAT   COOL

FAN

70

78       AUTO

IDLE     

10:00P     62

82       AUTO

SAVE

PREVIOUS

6:00A

FULL TIME DEHUMIDIFY - Turns on the D output when the 

room humidity is above the set humidity level all the time. 

NONE –  Neither is active. 
DIFFERENTIAL – Sets the difference between the 

dehumidification set-point and when this sequence turns off.  
Range is 5-40%, default is 5%. 

 

REVERSING VALVE OPTION - Option of the reversing valve (O/B output) 
 

being on when in cooling or heating.  Default is HEATING. 

 
RESTORE DEFAULTS - This will allow you to revert to the factory default 
settings.  The configuration settings (HEAT COOL / HEAT PUMP, 
MULTI/SINGLE, and ECONOMIZER/NOECONOMIZER are NOT reset by 
this command.  Also, accessory internal settings are not reset when using 
Default Reset. 

OFFSETS

 

TEMPERATURE OFFSETS 

This option allows calibration (or deliberate miscalibration) of the 
room temperature sensor(s). There are various reasons why the 
displayed temperature would be adjusted to a higher or lower value.  

NOTE: 

Do not adjust for 30 minutes after installation because board 

may be heated by handling.  The selected number is the number of 
degrees, plus or minus, which will be added to actual temperature. 
The numbers can range between -5˚ and +5˚.  Default values are set to 
0˚ offset. 

 

Temperature Offset 

 

Remote Indoor Offset (if sensor is attached) 

 

Outdoor Offset (if sensor is attached) 

 
HUMIDITY OFFSET 

This option allows calibration of the humidity sensor. Adjustments 
can range between -10% and +10%.  Default is 0% offset. 

 
ANTICIPATOR 

This adjustment controls the sensitivity and cycle rate of the 
controller. Higher numbers decrease the cycle rate. Lower numbers 
increase the cycle rate.  Default value is 0, and the range is 0-9.   
 

DIFFERENTIAL 

This adjustment will vary the number of degrees, from the set point, 
before a call for heating or cooling is made.  Adjustments can range 
between 1˚ and 4˚ differential.  Default is 2˚ offset.  (If your set point 
is 70˚F in heating, your thermostat will not call for heat until the 
temperature is 68˚F, with a 2˚ differential).  3rd stage Cool 
differential is the same as 2

nd

 stage cool differential.  Third stage heat 

differential in HEAT PUMP is the AUX setting. 

 
CYCLES PER HOUR 

This feature will not allow more than the specified number of equipment 
cycles per hour. Values can range from 4 to 8 Factory default setting is 6. 
(or 1 cycle every 10 minutes.).   This default selection will provide 
optimum performance in nearly all installations. 

 

PROGRAM SETTINGS 
 

SMART RECOVERY 

Smart recovery is a feature of your controller designed to save energy by 
gradually adjusting temperatures.  When it’s time for a programmed 
temperature change, smart recovery begins working in advance, turning 
the 
system on and off as needed to slowly adjust the indoor temperature. 
During these transition periods, you may notice that the actual 
temperature and your temperature setting don’t match. That’s smart 
recovery in action, adjusting temperatures in small increments for 
greater energy efficiency. This is more energy efficient than simply 
allowing the system to operate at full capacity until the desired 
temperature has been met. Smart Recovery helps avoid excessive use of 
auxiliary heat when recovering from night setback in the heating mode.   
 

EVENTS PER DAY 

This is where you can set the number of events per 
day. (An event is a period of time scheduled with a 
certain heating and cooling setpoint.) For instance if 
you are away from your home from 8am to 5pm, 

make this period of time an event and set the thermostat at an energy 
saving setting. You have the option of setting the events per day to 4-
RESIDENTIAL (4 events), 2-RESIDENTIAL (2 events) or 2-
BUSINESS (2 events).  Default is 2 – BUSINESS. 

 

 

 

 

 
 

 

           

4-RESIDENTIAL            2-RESIDENTIAL               2-BUSINESS 

             

 (Default) 

 
SMART HEAT STAGING  

(HEAT PUMP ONLY) 

This will allow the controller to engage in 3

rd

 stage heating if needed.  

Options are ON or OFF.  Default is OFF.  Range for this are 0-120 
minutes in 5 minute increments, if set to ON.  45 minutes is the default 
time.  This is the time before the electric heat is engaged.    
 

COOLING LOCKOUT   
  When an outdoor temperature sensor is installed, you can set it up so 

cooling option doesn’t energize if the outdoor temperature is below a 
certain temperature.  Ranges for this are NONE (default), 40˚F , 45˚F, 
50˚F, or 55˚F.   

 
ELECTRIC HEAT LOCKOUT 
  When an outdoor temperature sensor is installed, you can set it up so the 

electric heat option doesn’t energize if the outdoor temperature is above 
a certain temperature.  Ranges for this are NONE (default), 5˚F to 60˚F 
in 5˚ increments. 

 
HEAT PUMP  LOCKOUT 
  When an outdoor temperature sensor is installed, you can set it up so the 

Heat pump will not operate when the outdoor temperature is below a set 
temperature.  Ranges for this are NONE (default), 5˚F to 50˚F in 5˚ 
increments. 

 
TEST MODE 
  When test mode is selected, the system can be operated in any of the 

available operational modes for 30 minutes.  The system will run the set 
mode regardless of the temperature set point and room temperature.  The 
display will flash a red screen as a reminder that you are in the test 
mode. 

 
RESET TO DEFAULTS 

 

Selecting Reset to Defaults will set all of the options to the factory default 
setting with the exception of the configuration settings.  The configuration 
settings and the accessory internal settings need to be set and reset 
individually. 

 
TEMPERATURE RANGE 
 
 

This is accessed from the Installer Settings menu and regulates the 
maximum Heat and minimum Cool settings the thermostat can be adjusted 
to.  The factory default for occupied set-points is 74°F for Cooling and 
70°F for Heating.  The factory default for the minimum Cooling allowed is 
70°F and the factory default for the maximum Heating is 72°F. 

 
 

When operated in Auto changeover mode there is a default minimum 
differential of 2°F between Cooling and Heating, so if Cooling was 
adjusted down to the 70°F minimum it will force Heating to 68°F. 

 
 

To access and make any changes to the Maximum Heat or Minimum Cool 
settings use the following procedure: 

1.

 

Set Mode to Off 

2.

 

Press center button to SAVE, screen will say SAVED. 

3.

 

Simultaneously press the up and down arrows for 5 seconds 
until Installer Setting screen appears. 

4.

 

Use up or down arrows to scroll the menu to Temperature 
Range, it is on the 2

nd

 screen. 

5.

 

Press center button to access the Maximum Heat and then 
Minimum Cool screens making changes as desired. 

6.

 

Press center button to SAVE, screen will say SAVED and 
then exit out of the Installer Menu using left arrow to get 
back to the normal operating screen. 

7.

 

Change Mode to Heat, Cool or Auto as desired. 