INSTALLER 

INFORMATION / 

ADVANCED FEATURES  

 

SAFETY CONSIDERATIONS 

Improper wiring or installation may damage controller.   Wiring must  
conform to local and national electrical codes 

INTRODUCTION 

The controller is a wall mounted, 24VAC low-voltage controller which 
maintains room temperature by controlling the operation of a heating and air 
conditioning system.  Batteries are not required; temperature and mode 
settings are preserved with the power off. 

INSTALLATION CONSIDERATIONS 

The controller requires no batteries.  The controller is not a power stealing 
device and MUST have both R and C connected. 

 

INSTALLATION 

IV.

 

CONTROLLER LOCATION 

Controller should be mounted: 

- Approximately 5 ft. (1.5m) from floor. 
- Close to or in a frequently used room, preferably on an inside  

partitioning wall. 

- On a section of wall without pipes or duct work. 

Controller should NOT be mounted: 

  - Close to a window, on an outside wall, or next to a door leading  

to the outside. 

  - Exposed to direct light and heat from a lamp, sun, fireplace, or  

other temperature-radiating object which may cause a false reading. 

  - Close to or in direct airflow from supply registers and return-air grilles. 
  - In areas with poor air circulation, such as behind a door or in an alcove. 
 

V.

 

INSTALL CONTROLLER 

1.  Turn off all power to unit.  
2.  If an existing thermostat is being replaced:  

A.  Remove existing thermostat from wall. 
B.  Disconnect wires from existing thermostat, one at a time.  Be  

careful not to allow wires to fall back into the wall. 

C.  As each wire is disconnected, record wire color and terminal 

marking. 

D.  Discard or recycle old thermostat. 

NOTE:  Mercury is a hazardous waste and MUST be disposed of 

properly. 

3.  Separate the front and back pieces of plastic. 

4.  Route thermostat wires through hole in back piece of plastic.  Level plastic 

against wall (for aesthetic value only - thermostat need not be leveled for 
proper operation) and mark wall through 2 mounting holes. 

5.  Drill two 3/16-in. mounting holes in wall where marked.   
6.  Secure back plastic to wall with 2 anchors and screws provided making 

sure all wires extend through hole in plastic. 

7.  Use minimum of 22-gauge wiring, 18-gauge is recommended, for basic 

controller wiring. Shielded twisted pair should be used for optional remote 
indoor and outdoor sensors.  Connect wires to proper terminal of the 
connector block in the front plastic.   

8.  Push any excess wire back into wall.  Excess wire inside the controller 

plastic case can interfere with proper air flow across the temperature 
sensor.  Seal hole in wall to prevent air leaks.  Leaks can affect operation. 

9.  Snap front and back pieces of plastic together. 

  10.  Turn on power to the unit. 
 

VI. 

INSTALLER SETTINGS 

NOTE:    These options are intended to be used by the installer.  End users 
are not advised to change or modify any of these settings.  Doing so may 
make your equipment stop working properly and/or may void the warranty 
of the controller as well as the equipment hooked up to the controller.  To 
access the installer setting menu, the mode must be set to OFF.  Then, press 
both the up and down arrows keys at the same time for at least 5 seconds to 
enter the installer screen. 
 
MODEL CONFIGURATION 
 Options to select from: 
HEAT COOL/HEAT PUMP,  
SINGLE STAGE/MULTI STAGE,  
ECONOMIZER/NO ECONOMIZER 
CS2000A INSTALLED..YES OR NO 
PROGRAMMABLE/NONPROGRAMMABLE 
BOLD items are default 

NOTE: - If CS2000A is installed, the controller will inhibit all outputs 
except the Y0/D when there is no 24Vac applied to the L input on the 
thermostat.  When the CS2000A is not installed, the L input is the Lock out 
signal from the heat pump. 

 

ACCESSORIES 
Each of these options has settings for Cumulative Run Time and Calendar 
Time.  Messages will flash at the top of the Main screen when these events 
are met to alert the owner that it is time service these options.   
Air Filter - Cumulative Run Time default is 1000 hours and Calendar Time 

is 3 months.  Values can range from 400-3600 hours for 
Cumulative Run Time (in 100 hour increments), or Calendar 
Time can be set to OFF, or 1-48 months (in 1 month 
increments).   

Humidifier - Cumulative Run Time default is 0 hours (OFF) and Calendar 

Time is OFF.  Values can range from 400-3600 hours for 
Cumulative Run Time (in 100 hour increments), or Calendar 
Time can be set to OFF, or 1-24 months (in 1 month 
increments). 

UV Lamp - Cumulative Run Time default is 0 hours (OFF) and Calendar 

Time is OFF.  Values can range from 400-12000 hours for 
Cumulative Run Time (in 100 hour increments), or Calendar 
Time can be set to OFF, or 1-48 months (in 1 month 
increments). 

Air Cleaner - Cumulative Run Time default is 0 hours (OFF) and Calendar 

Time is OFF.  Values can range from 400-3600 hours for 
Cumulative Run Time (in 100 hour increments), or Calendar 
Time can be set to OFF, or 1-24 months (in 1 month 
increments). 

 
INPUT DEALER INFO 

Contractors are able to input Brand Name, Unit Model Number, 
Contractor Name, and Contractor Phone number into these screens.  
This way, the owner could give this information to the contractor so that 
he would know what system the owner has prior to the service visit.   

 

            

             

 

 

1.

 

Scroll to the info you want to enter and press the center button  

2.

 

Enter the information by scroll through the characters using the up & 
down arrows 

▲▼

.  Once the character you want is set, press the right 

arrow 

 to move to the next space and begin entering another 

character.  

3.

 

Once you’ve completed filling out the field, press the center button 

 

to save the entry and return to the INPUT DEALER INFO screen.  
Repeat this process for all fields you want saved.   

4.

 

Once all fields have been entered, scroll to SAVE and press the center 
button 

 
FAN WITH HEAT OPTION 

    Options are ON or OFF.  This selection determines whether G (fan) 
output is to be ON or OFF when W (auxiliary heat) output is ON.  Default 
is ON. 

 
DEHUMIDIFICATION CONTROL 
    If your system is equipped with dehumidification circuit, this output 
controls that function.   
 

OCCUPIED ONLY 
FULL TIME DEHUMIDIFY 
NONE 
DIFFERENTIAL 
 
To adjust the Set Point for Dehumidification, Select the RH from 
the Main menu.  The values can be selected and adjusted from that 
screen.  Range is 45-95%, default is 60%. 
NOTE: Humidity can be displayed even if not being actively 
controlled.   
 OCCUPIED ONLY - Turns on the D output when the room 

humidity is above the set humidity level only during the 
OCCUPIED (ACTIVE) time. 

 

INPUT DEALER INFO 

BRAND NAME
MODEL NUMBER
CONTRACTOR NAME
CONTRACTOR PHONE
SAVE

SELECT OPTION 

∇∆

PREVIOUS

BRAND NAME

 

DEALER INFO

BRAND NAME 

USE 

∇∆

TO SCROLL

THRU CHARACTERS

A

_____________________________

CHANGE LETTER 

∇∆

PREVIOUS

A