997-060180-4d 

 

3

 

PROGRAM MENU 

SAVE

MONDAY

TUESDAY

WEDNESDAY

THURSDAY

FRIDAY

SATURDAY

SUNDAY

WEEKDAYS

WEEKENDS

COPY

SELECT OPTION 

∇∆

PREVIOUS

EVERY DAY

 

SECURITY LOCKOUT 

TEMP ADJUST ONLY

SELECT OPTION 

∇∆

PREVIOUS

TOTAL KEYPAD LOCKOUT

 

SECURITY LOCKOUT 

ENTER PIN NUMBER

0 0 0 0

CHANGE NUMBER 

∇∆

PREVIOUS

 

INTERMITTENT FAN   

NO HEAT OR COOL CALL

FAN OFF TIME

10

MINUTES

CHANGE SETTING 

∇∆

PREVIOUS

 

EVERY DAY

ACTIVE

HEAT   COOL

FAN

70

78       AUTO

IDLE     

10:00P     62

82       AUTO

SAVE

PREVIOUS

6:00A

 

INTERMITTENT FAN   

NO HEAT OR COOL CALL

FAN ON TIME

5

MINUTES

CHANGE SETTING 

∇∆

PREVIOUS

the MODE to OFF, and then back to the operating mode, 
typically AUTO.  

4.

 

If step 3 is not done within 10-minutes the display will 
automatically return to the SERVICE NEEDED screen in RED.  

 

II.

 

PROGRAMMING YOUR CONTROLLER (programmable 
models only) 

     PROGRAMMING A DAY OR A SERIES OF DAYS 

    After selecting the programming screen, you have the option of 

programming everyday, weekdays, weekends, or individual days.  Once 
you’ve selected a certain day to program, a screen appears that allows 
you to set the time, heat setting, cool setting, and fan operation for each 
event. 

1.

 

From the Main Menu, scroll to MENU and press the center button 

 

on the keypad. 

2.

 

Select PROGRAM 

3.

 

Select PROGRAMMABLE.   

4. 

You can program each day differently

 

by going through each day and 

 

personalizing them.  Or, you can program 

 

everyday the same by scrolling to 

 

EVERYDAY.  Or, you can program 

 

the weekdays or weekends the same by 

 

selecting the appropriate  menu item. 

5. 

To program everyday the same, select 

 

EVERYDAY and then press the center 

 

button 

6. 

Using the right arrow button 

, highlight 

 

the WAKE time, and change to desired 

 

time by using the up and down arrow 

▲▼

 

buttons.  Move to the next entry by using 

 

the right arrow button 

.  To change the 

 

HEAT set point, use the up and down arrows.  

Continue this process  

until all settings are to your liking.   

7. 

The FAN setting will only be used if the Fan is set to 

PROGRAMMED.   

If the Events are set to 2 per day in the 

Business mode, the fan will be  

ON and the Ventilation output 

(A) will be ON when the time is in the  

OCCUPIED (Active) state.  In 

the Unoccupied (IDLE) state, the fan will  

run in the operating 

mode set by the program. 
8. 

To save these setting, scroll to SAVE, and press the center button 

     

 COPYING A PROGRAM FROM ONE DAY TO ANOTHER 
  In the PROGRAM menu, there is an option to COPY.  The option can 

be used to copy the program from one day to another day.  After 
COPY is selected, the controller  will prompt you for which day to 
copy from.  Next, it will prompt you for which day to copy the 
program to.  After these selections, it will then confirm what is being 
copied to where.  At this point you have the option of canceling the 
copy process, by pressing  

 to return to the copy menu, or saving what you have by pressing 

the center button 

.  The SAVED screen will appear returning you to 

the copy menu.  Pressing 

 will return you to the PROGRAM menu.  

Pressing 

 again will return you to the MAIN MENU. 

 

 

  SECURITY LOCKOUT 

 This controller has the option to set security 
features to lockout everything but the adjustment 
of the temperature or a total keypad lockout.   

1.

 

From the Main Menu, scroll to MENU and 
press the center button 

 on the keypad. 

2.

 

Select SECURITY LOCKOUT. 

3.

 

Select whether you want to lockout everything 
but TEMP ADJUST ONLY or TOTAL 
KEYPAD LOCKOUT. 

4.

 

Either selection will bring you to the Enter Pin 
Number screen. 

5.

 

Using the up and down arrows 

▲▼

, select a 

pin number to lock out the thermostat.  The 
right arrow 

 moves you to the next pin digit.   

6.

 

Once you’ve entered the 4-digit pin number, press the center button 

 

to save the pin.  The screen will display LOCKED and return to the 
main Screen. 

7.

 

Once you return to the Main Screen, in the upper left of the screen 
will alternate between LOCKED and the date and time. 

8.

 

If you selected TEMP ADJUST ONLY, you will only be able to 
adjust the set point temperature.  Any other operation will require the 
pin number to unlock the controller. 

9.

 

Once unlocked, you’ll have to set a pin number again to lockout the 
thermostat again.   

 
 

AUTO CHANGEOVER 

With auto changeover, the controller automatically switches itself from 
heating to cooling, or vise versa, based on the setpoints. When setting up 
the controller you have to enter both a cooling setpoint and a heating 
setpoint. The controller will also prevent the user from setting the cooling 
setpoint lower than the heating setpoint.  Mode is set to AUTO for this 
operation to work. 
MENU 

 SETTINGS 

 AUTO CHANGEOVER 

 
Auto Changeover Time - This setting sets the minimum off time before the 

controller can change from one mode to another.  
Default is 10 minutes.  Range is from 5-120 
minutes in 5 minute increments.  Pressing the 
Right and Left buttons together for 3 seconds will 
over ride this delay for one cycle. 

 
Auto or Manual Change – 
Default is AUTO.  If MANUAL is chosen, you 

will need to change from heating to cooling or 
vise versa.  When MANUAL is set, AUTO is 
removed from the MODE screen as a choice.   

 
INTERMITTENT FAN 

MENU 

 SETTINGS 

 INTERMITTENT FAN 

Temperature conditions can vary widely between the controller location 
and extremities of the space the controller serves.   This air stratification 
problem can be especially pronounced during mild outdoor conditions 
when long periods elapse between space conditioning demands from the 
controller.   This intermittent fan operation can also improve the 
performance of air cleaning or special filtration systems that locate the 
cleaning or filtration media at the return air side of the fan.  

     
1.

 

If the FAN hasn’t been on for an hour, the fan 
will start cycling based on these times.  Default is 
OFF.  The first screen is the amount of time you 
want the fan to be energized.  Ranges are OFF, or 
5-20 minutes in 5 minute increments. 

2.

 

After entering this time and pressing the center 
button 

, the next screen is the amount of time the 

fan is OFF.  Ranges are 0 minutes, or 5-40 
minutes in 5 minute increments. 

3.

 

After entering this time and pressing the center 
button 

 you will be returned to the Setting Menu 

screen. 

4.

 

Fan ON and OFF cycles will continue until the 
fan has been energized by a call for heating or cooling.   

 
SERVICE INFORMATION 
 

MENU 

 SETTINGS 

 SERVICE INFORMATION 

These screens help an installer or contractor to have a good understanding 

of what problems might be occurring before arriving for service.  The 
options are TEMPERATURE and INPUTS.  The TEMPERATURE will 
display the internal sensor temperature, the Room temperature and the 
reading from the Outdoor thermistor.  INPUTS displays the status of the 
controller control lines. (W1/E, W2, Y1, Y2, G, O/B, A, Y0/D) 

WARNING:  Before installing controller, turn off all power to unit.  There 
may be more than one power disconnect.  Electrical shock can cause personal 
injury or death. 